Plan Review Details - Permit 20040876
Plan Review Stops For Permit 20040876
Review Stop AD ADDRESSING
Rev No 2 Status P Date 2020-08-10 Cont ID  
Sent By cpuell Date 2020-08-10 Time 10:47 Rev Time 0.00
Received By cpuell Date 2020-08-10 Time 10:47 Sent To  
Notes
2020-08-10 10:47:34SPOKE WITH STEPHANIE AND WAS ABLE TO CONFIRM TENANTS
 TAKING OVER SPACE PREVIOUSLY OCCUPIED BY LEATHER
 EXPRESS, ADDRESS IS 2271 PALM BEACH LAKES BLVD.

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2020-04-24 Cont ID  
Sent By cpuell Date 2020-04-24 Time 08:33 Rev Time 0.00
Received By cpuell Date 2020-04-24 Time 08:33 Sent To  
Notes
2020-04-24 08:33:42PLEAE IDNETIFY WHICH SUITE NUMBER THIS PERMIT IS FOR.
 PLEASE EMAIL [email protected]

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 6 Status P Date 2020-10-25 Cont ID  
Sent By jwitmer Date 2020-10-25 Time 12:58 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 5 Status F Date 2020-10-18 Cont ID  
Sent By jwitmer Date 2020-10-18 Time 14:45 Rev Time 0.00
Received By jwitmer Date 2020-10-18 Time 14:32 Sent To  
Notes
2020-10-18 14:44:57TO THE BUILDING CONTRACTOR:
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN PDF
 FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE
 THE PERMIT NUMBER AND "ASBESTOS" IN THE SUBJECT LINE.
  

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 4 Status F Date 2020-10-13 Cont ID  
Sent By jwitmer Date 2020-10-13 Time 10:42 Rev Time 0.00
Received By jwitmer Date 2020-10-13 Time 10:32 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 3 Status F Date 2020-09-22 Cont ID  
Sent By jwitmer Date 2020-09-22 Time 07:59 Rev Time 0.00
Received By jwitmer Date 2020-09-22 Time 07:56 Sent To  
Notes
2020-09-22 07:58:43PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN PDF
 FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE
 THE PERMIT NUMBER AND "ASBESTOS" IN THE SUBJECT LINE.
  

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status F Date 2020-08-03 Cont ID  
Sent By jwitmer Date 2020-08-03 Time 14:32 Rev Time 0.00
Received By jwitmer Date 2020-08-03 Time 13:30 Sent To  
Notes
2020-08-03 14:32:09PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN PDF
 FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE
 THE PERMIT NUMBER AND "ASBESTOS" IN THE SUBJECT LINE.
  
  

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2020-04-28 Cont ID  
Sent By jwitmer Date 2020-04-28 Time 17:20 Rev Time 0.00
Received By jwitmer Date 2020-04-28 Time 14:03 Sent To  
Notes
2020-04-28 17:20:10ASBESTOS COMMERCIAL. PLEASE PROVIDE A SIGNED
 ACKNOWLEDGEMENT FROM THE CONTRACTOR, ON LETTERHEAD,
 STATING THAT THE INSTRUCTIONS ON THE WEBSITE OF
 ASBESTOS PROGRAM COORDINATOR, FLORIDA DEPARTMENT OF
 HEALTH PALM BEACH COUNTY WILL BE FOLLOWED AND THAT
 NOTIFICATION WILL BE GIVEN TIMELY. ADDITIONAL
 INFORMATION REGARDING ASBESTOS REQUIREMENTS CAN BE
 FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
 19120504
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN PDF
 FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE
 THE PERMIT NUMBER AND ?ASBESTOS? IN THE SUBJECT LINE.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status P Date 2020-10-25 Cont ID  
Sent By jwitmer Date 2020-10-25 Time 12:59 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2020-10-18 Cont ID  
Sent By jwitmer Date 2020-10-18 Time 14:45 Rev Time 0.00
Received By jwitmer Date 2020-10-18 Time 14:32 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2020-10-13 Cont ID  
Sent By jwitmer Date 2020-10-13 Time 10:44 Rev Time 0.00
Received By jwitmer Date 2020-10-13 Time 10:32 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2020-09-22 Cont ID  
Sent By jwitmer Date 2020-09-22 Time 07:57 Rev Time 0.00
Received By jwitmer Date 2020-09-22 Time 07:56 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2020-09-22 Cont ID  
Sent By jwitmer Date 2020-09-22 Time 07:57 Rev Time 0.00
Received By jwitmer Date 2020-09-22 Time 07:32 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2020-08-03 Cont ID  
Sent By jwitmer Date 2020-08-03 Time 14:29 Rev Time 0.00
Received By jwitmer Date 2020-08-03 Time 13:30 Sent To  
Notes
2020-08-03 14:28:51BUILDING PROVISO 2017 FBC- ACCESSIBILITY CODE:
 PROTRUDING OBJECTS 307.2 PROTRUSION LIMITS 307.2.
 OBJECTS WITH LEADING EDGES MORE THAN 27
 INCHES AND NOT MORE THAN 80 INCHES ABOVE THE FLOOR
 SHALL NOT PROTRUDE MORE THAN 4 INCHES
 HORIZONTALLY IN TO THE CIRCULATION PATH. OR ADD WING
 WALLS TO NOT BUMP INTO THE DRINKING
 FOUNTAINS. SEE SHEET A-03 AND DETAIL 3/A-08.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-04-28 Cont ID  
Sent By jwitmer Date 2020-04-28 Time 17:18 Rev Time 0.00
Received By jwitmer Date 2020-04-28 Time 14:03 Sent To  
Notes
2020-04-28 16:55:492017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 20040876
 ADD: 2271 PALM BEACH LAKES BLVD.
 CONT: XT HOLDING
 TEL: 561-599-3166
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. APRIL 28TH/2020
 ACTION: DENIED
  
 1) SHEET A-10 LIFE SAFETY SHEET OCCUPANT LOAD
 CALCULATIONS:
  
 1A) THE MERCANTILE OCCUPANT LOAD FACTOR IS BEING TAKEN
 AT 30 WHEN IT SHOULD BE TAKEN AT 60, (A CHANGE IN THE
 2017 FBC-B BLACK LINE IN THE MARGIN). PLEASE UPDATE THE
 PLANS.
  
 1B) THE OCCUPANT LOAD CALCULATION IS TAKING THE
 RESTROOMS AS A BUSINESS OCCUPANCY. PLEASE REVIEW IN THE
 2017 FBC-B TABLE 1004.1.2 FOR MERCANTILE YOU ARE
 SUPPOSED TO TAKE THE GROSS AREA FOR THE MERCANTILE, SEE
 FLOOR AREA GROSS.
 2017 FBC-B 201 DEFINITIONS: FLOOR AREA, GROSS. THE
 FLOOR AREA WITHIN THE INSIDE PERIMETER OF THE EXTERIOR
 WALLS OF THE BUILDING UNDER CONSIDERATION, EXCLUSIVE OF
 VENT SHAFTS AND COURTS, WITHOUT DEDUCTION FOR
 CORRIDORS, STAIRWAYS, CLOSETS, THE THICKNESS OF
 INTERIOR WALLS, COLUMNS OR OTHER FEATURES. THE FLOOR
 AREA OF A BUILDING, OR PORTION THEREOF, NOT PROVIDED
 WITH SURROUNDING EXTERIOR WALLS SHALL BE THE USABLE
 AREA UNDER THE HORIZONTAL PROJECTION OF THE ROOF OR
 FLOOR ABOVE. THE GROSS FLOOR AREA SHALL NOT INCLUDE
 SHAFTS WITH NO OPENINGS OR INTERIOR COURTS.
  
 2017 FBC-B 201: FLOOR AREA, NET. THE ACTUAL OCCUPIED
 AREA NOT INCLUDING UNOCCUPIED ACCESSORY AREAS SUCH AS
 CORRIDORS, STAIRWAYS, TOILET ROOMS, MECHANICAL ROOMS
 AND CLOSETS.
  
 2)SHEET A-11:
  
 2A) SHEET A-11 THE LIFE SAFETY PLAN ONLY SHOWS THE EXIT
 LIGHTS AND BATTERY BACKUP LIGHTS. THERE ARE NO
 DIRECTIONAL SIGNS INDICATING THERE IS A SECONDARY REAR
 EXIT. NOR IS THERE ANY DIRECTIONAL LIGHTS WITHIN THE
 STOCKROOM INDICATING THE EGRESS PATH. WITH STORAGE
 SHELVING IN THE STOREROOM EGRESS LIGHTS MAYBE BLOCKED.
 SEE THE 2017 FBC-B SECTION 1013.1. THE PATH OF EGRESS
 TRAVEL TO EXITS AND WITHIN EXITS SHALL BE MARKED BY
 READILY VISIBLE EXIT SIGNS TO CLEARLY INDICATE THE
 DIRECTION OF EGRESS TRAVEL IN CASES WHERE THE EXIT OR
 THE PATH OF EGRESS TRAVEL IS NOT IMMEDIATELY VISIBLE TO
 THE OCCUPANT.
  
 2B) THE DOOR THAT LEADS INTO THE NEXT TENANT SPACE IS
 NOT STATED AS AN EXIT BUT SHOULD BE MARKED NOT AN EXIT
 SINCE YOU DO NOT KNOW WHEN THIS DOOR MAYBE LOCKED OR
 BLOCKED FROM THE OTHER TENANTS SIDE. 2017 FBC-B SECTION
 1016.2 , 2 AND 3.
  
 3)SHEET A-03:
  
 3A) IDENTIFIES A SINGLE WATER FOUNTAIN. PLEASE REVIEW
 IN THE 2017 ACCESSIBILITY CODE SECTION 211.2 MINIMUM
 NUMBER OF DRINKING FOUNTAINS AND HEIGHTS AT WHICH THEY
 ARE TO BE INSTALLED.
  
 3B) THIS SAME FLOOR PLAN INDICATES A KITCHEN, YOU MAY
 WANT TO DEFINE THIS SPACE AS A BREAK AREA. COMMERCIAL
 KITCHENS ARE TO HAVE A HOOD AND ENSILE SYSTEM. THE
 BREAK AREA WILL ALSO NEED TO SHOW COMPLIANCE THAT THE
 CABINETRY AND SINK ARE AT 34 INCHES ABOVE FINISH FLOOR.
 PLEASE SHOW COMPLIANCE WITH THE 2017 ACCESSIBILITY CODE
 SECTIONS:
 606.2-606.5.
 902.3 WORKING SURFACES SHALL BE A MAXIMUM 34 INCHES.
  
 3C) RECEPTION DESK INDICATES DETAIL ON SHEET A-06. THIS
 AREA DOES NOT PROVIDE A AREA FOR HANDICAPPED PERSONS IN
 WHEEL CHAIRS TO WRITE CHECKS. SEE 904.3.3 CHECK WRITING
 SURFACES.
  
 4) SHEET A07 SHOWS THE REMOVAL OF AN EXTERIOR INFILLED
 WALL AND NEW ROLL-UP EXTERIOR DOOR. THE PLANS DO NOT
 PROVIDE ANY WIND DESIGN CRITERIA. 2017 FBC-B 1603.1.4
 WIND DESIGN DATA.
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE
 STRUCTURE:
  
 4.1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST),
 MILES PER HOUR AND NOMINAL DESIGN WIND SPEED, VASD, AS
 DETERMINED IN ACCORDANCE WITH SECTION 1609.3.1.
  
 4.2. RISK CATEGORY.
  
 4.3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE
 THAN ONE WIND EXPOSURE IS UTILIZED. TABLE 1609.7.2.
 HEIGHT AND EXPOSURE. ASCE 7-10 TABLE 30.3.1.
  
 4.4. APPLICABLE INTERNAL PRESSURE COEFFICIENT.
  
 4.5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR
 COMPONENTS AND CLADDING MATERIALS SPECIFICALLY DESIGNED
 BY THE REGISTERED DESIGN PROFESSIONAL RESPONSIBLE FOR
 THE DESIGN OF THE STRUCTURE, PSF.
  
 4.6. TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT &
 EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE
 BUILDING. 1609.3.1 WIND SPEED CONVERSION VULT TO VASD.
  
 5) 2017 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005,
 RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS
 OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(A) EXTERIOR DOORS/ ROLL-UP DOORS
  
 6A) W. P. B. 107.3.4. PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY FLORIDA ADMINISTRATIVE CODE RULE
 61G20 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE
 ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING
 ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC..
  
 6B) 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF
 THIS SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE
 PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE
 TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO
 THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD.
 DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR
 APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST
 THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS
 FOR REVIEW BY THE BUILDING OFFICIAL.
  
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 6C) WILL THERE BE WOOD BUCKS THAT THE ROLL-UP DOOR BE
 ANCHORED TO? THIS IS NOT PART OF THE PRODUCT APPROVAL.
 107.2.1.2. ADDITIONAL INFORMATION IS REQUIRED.
  
 7) SHEET A-09 THE LAYOUT OF THE 2 RESTROOMS BUT THERE
 ARE NO MEASUREMENTS FOR THE ELEMENTS LISTED FOR
 ACCESSIBILITY IN CHAPTER 6 OF THE 2017 ACCESSIBILITY
 CODE.
 7A) MIRRORS SHALL COMPLY WITH SECTION 603.3.
 7B) WATER CLOSETS SHALL SHOW COMPLIANCE WITH 604.3.1
 AND FIGURE 604.3.1.
 7C) WATER CLOSET SEATS SHALL COMPLY WITH 604.4.
 7D) GRAB BARS SHALL SHOW COMPLIANCE WITH 604.5, SIDE
 WALL 604.5.1, REAR WALL 604.5.2.
 7E) FLUSH CONTROLS 604.6.
 7F)TOILET PAPER DISPENSERS SHALL COMPLY WITH 604.7.
 7G) SINKS AND LAVATORIES SHALL SHOW COMPLIANCE WITH
 606.2-606.5
  
 8) THE PERMIT VALUE OF THE JOB STATED IS $70.000.00
 DOLLARS IN VALUE. THE 2017 ACCESSIBILITY CODE REQUIRES
 UP TO 20% OF THE JOB VALUE TO BE MADE IN ACCESSIBLE
 UPGRADES. IF ALL OF THE REQUIRED CODE SECTIONS CAN NOT
 BE COMPLETED (NOT NEW WORK) PLEASE REVIEW SECTION
 202.4.1 FOR DISPROPORTIONATE COST AND IN WHAT ORDER THE
 FUNDS ARE TO BE SPENT. WE WILL NEED AN ITEMIZED LETTER
 FROM EITHER THE CONTRACTOR OR DESIGN PROFESSIONAL ON
 THEIR LETTER HEAD LISTING IN ORDER GIVEN IN SECTION
 202.4.1 AND THE ASSOCIATED COST FOR EACH ITEM ON THE
 ITEMIZED LIST.
  
 9) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE
 THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED
 DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE
 MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS
 AND INFORMATION LACKING UNDER THE PRIOR REVIEW.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2020-09-24 Cont ID  
Sent By jleahy Date 2020-09-24 Time 13:03 Rev Time 0.00
Received By jleahy Date 2020-09-24 Time 13:03 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2020-08-11 Cont ID  
Sent By jleahy Date 2020-08-11 Time 08:55 Rev Time 0.00
Received By jleahy Date 2020-08-11 Time 08:55 Sent To  
Notes
2020-08-11 09:01:17ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 PREVIOUS COMMENTS THAT HAVE BEEN SATSFIED WILL BE
 MARKED AS SUCH.
  
 1) RISER SUPPLIED BUT IT SHOWS A 400A MAIN FEEDING A
 GUTTER AND A TAP GOING TO A 600A MDP THEN TO PANEL "B"
  
 2) LOAD CALCULATION FOR PANEL "B" IS COMPLETE BUT YOU
 NEED TO SUPPLY ONE FOR THE 400A MAIN AND THE 600 MDP
  
 3) FAULT CURRENT CALCULATION IS DONE BUT STATES
 EXISTING ON PANE L"B".
  
 4) LIGHTING CONTROL NOT SHOWN FBC 405.2
  
 5) COMPLETE.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-05-12 Cont ID  
Sent By jleahy Date 2020-05-12 Time 15:41 Rev Time 0.00
Received By jleahy Date 2020-05-12 Time 15:31 Sent To  
Notes
2020-05-12 15:53:24ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 1) RISER DIAGRAM SHOWIING SERVICE DISCONNETS AND
 PANELS, 215.5
 PROVIDE RISER DIAGRAM, SHOWING ALL DETAILS OF SERVICE
 EQUIPMENT, UNDERGROUND OR OVERHEAD SERVICE, WIRE AND
 BREAKER SIZES FOR SERVICE AND FEED TO INTERIOR PANEL.
 SHOW GEC SIZE AND SYSTEM, SHOW INTERSYSTEM BONDING
 TERMINATION POINT. NEC 215.5, 230, 250.50, 250.94,
 408.30
  
 2) LOAD CALCULATION FOR THE TENNANT SPACE 220.2
 PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE EXISTING
 AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE IS
 ADEQUATE. NEC 215.2, 220, 408.30
  
 3) AIC RATING OF SERVICE DISCONNECT AND PANELS 110.
 PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH
 PANEL INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR
 THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE
 SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE.
 NEC 110.9, 110.10
  
 4) NO LIGHTING CONTROL SHOWN OR LIGHTING DENSITIES
 PROVIDE A NOTE TO INDICATE COMPLIANCE WITH FBC CE 405.2
 AUTOMATIC LIGHTING CONTROL AND LIGHTING DENSITIES PER
 CODE SECTION.
  
 5) NEED TO LABEL AREAS IN BUILDING BACK AREA IS BEING
 USED FOR ?????

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2020-10-20 Cont ID  
Sent By pleduc Date 2020-10-20 Time   Rev Time 0.00
Received By pleduc Date 2020-10-20 Time 12:12 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2020-07-29 Cont ID  
Sent By sathomas Date 2020-07-29 Time 00:00 Rev Time 0.00
Received By sathomas Date 2020-07-29 Time 00:00 Sent To M
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2020-04-30 Cont ID  
Sent By sathomas Date 2020-04-30 Time 00:00 Rev Time 0.00
Received By sathomas Date 2020-04-30 Time 00:00 Sent To E
Notes
2020-04-30 15:53:081). A THOROUGH AND COMPLETE PLAN REVIEW CANNOT BE
 COMPLETED AT THIS TIME DUE TO LACK OF INFORMATION
 SUBMITTED ON THE PLANS. ADDITIONAL PLAN REVIEW COMMENTS
 MAY BE GENERATED DURING PLAN RESUBMISSION.
 2). SHEET A 11 - THERE IS NO INDICATION OF A MIXED OR
 SEPARATED OCCUPANCY; MERCANTILE IS INDICATED.
 3). INDICATE IF THE UNIT IS DESIGNED FOR MIXED USE
 (NON-SEPARATED) OR SEPARATED USE PER SECTION 6.1.14.1
 OF NFPA 101 FLORIDA EDITION 2015. FOR NON-SEPARATED
 MIXED USE OCCUPANCIES, THE MOST STRINGENT FIRE AND LIFE
 SAFETY REQUIREMENTS OF EACH OCCUPANCY SHALL APPLY TO
 THE BUILDING.
 4). PER NFPA 101 CH 6, OCCUPANCY CLASSIFICATION
  
 6.1 CLASSIFICATION OF OCCUPANCY.
 6.1.1 GENERAL.
 6.1.1.1 OCCUPANCY CLASSIFICATION. THE OCCUPANCY OF A
 BUILDING OR
 STRUCTURE, OR PORTION OF A BUILDING OR STRUCTURE, SHALL
 BE CLASSIFIED IN
 ACCORDANCE WITH 6.1.2 THROUGH 6.1.13. OCCUPANCY
 CLASSIFICATION SHALL BE
 SUBJECT TO THE RULING OF THE AUTHORITY HAVING
 JURISDICTION WHERE THERE IS A
 QUESTION OF PROPER CLASSIFICATION IN ANY INDIVIDUAL
 CASE.
  
 6.1.14.2 DEFINITIONS.
 6.1.14.2.1 MULTIPLE OCCUPANCY. A BUILDING OR STRUCTURE
 IN WHICH TWO
 OR MORE CLASSES OF OCCUPANCY EXIST.
 6.1.14.2.2 MIXED OCCUPANCY. A MULTIPLE OCCUPANCY WHERE
 THE
 OCCUPANCIES ARE INTERMINGLED.
 6.1.14.2.3 SEPARATED OCCUPANCY. A MULTIPLE OCCUPANCY
 WHERE THE
 OCCUPANCIES ARE SEPARATED BY FIRE RESISTANCE RATED
 ASSEMBLIES.
 6.1.14.3 MIXED OCCUPANCIES.
 6.1.14.3.1 EACH PORTION OF THE BUILDING SHALL BE
 CLASSIFIED AS TO ITS USE IN
 ACCORDANCE WITH SECTION 6.1.
 6.1.14.3.2* THE BUILDING SHALL COMPLY WITH THE MOST
 RESTRICTIVE
 REQUIREMENTS OF THE OCCUPANCIES INVOLVED, UNLESS
 SEPARATE SAFEGUARDS
 ARE APPROVED.
 6.1.14.4 SEPARATED OCCUPANCIES. (SEE ALSO 6.1.14.1.2.)
 6.1.14.4.1 WHERE SEPARATED OCCUPANCIES ARE PROVIDED,
 EACH PART OF THE
 BUILDING COMPRISING A DISTINCT OCCUPANCY, AS DESCRIBED
 IN THIS CHAPTER,
 SHALL BE COMPLETELY SEPARATED FROM OTHER OCCUPANCIES BY
 FIRE-RESISTIVE
 ASSEMBLIES, AS SPECIFIED IN 6.1.14.4.2, 6.1.14.4.3,
 TABLE 6.1.14.4.1(A),
 AND TABLE 6.1.14.4.1(B), UNLESS SEPARATION IS PROVIDED
 BY APPROVED
 EXISTING SEPARATIONS OR AS OTHERWISE PERMITTED BY
 6.1.14.4.6.
  
 5).PER FBC SECTION 508.2 AGGREGATE ACCESSORY
 OCCUPANCIES SHALL NOT OCCUPY MORE THAN TEN PERCENT IN
 WHICH THEY ARE LOCATED.
 6).PER SECTION 8.7, ANY AREA (STORAGE) HAVING A DEGREE
 OF HAZARD GREATER THAN NORMAL TO THE GENERAL OCCUPANCY
 (MERCANTILE) OF THE BUILDING, SHALL BE SEPARATED FROM
 NON-STORAGE AREAS WITH A 1-HOUR FIRE-RATED BARRIER OR
 BE PROTECTED WITH AN AUTOMATIC SPRINKLER SYSTEM. DOORS
 SHALL BE SELF CLOSING, POSITIVE LATCHING, AND
 FIRE-RATED FOR AT LEAST 45-MINUTES.
 7).NO DIMENSIONS GIVEN FOR CORRIDOR WIDTH.
  
 8).PER NFPA , CH 7 MEANS OF EGRESS
 7.2.1.5 LOCKS, LATCHES, AND ALARM DEVICES.
 7.2.1.5.1 DOOR LEAVES SHALL BE ARRANGED TO BE OPENED
 READILY FROM
 THE EGRESS SIDE WHENEVER THE BUILDING IS OCCUPIED.
 7.2.1.5.2* THE REQUIREMENT OF 7.2.1.5.1 SHALL NOT APPLY
 TO DOOR
 LEAVES OF LISTED FIRE DOOR ASSEMBLIES AFTER EXPOSURE TO
 ELEVATED
 TEMPERATURE IN ACCORDANCE WITH THE LISTING, BASED ON
 LABORATORY
 FIRE TEST PROCEDURES.
 7.2.1.5.3 LOCKS, IF PROVIDED, SHALL NOT REQUIRE THE USE
 OF A KEY, A
 TOOL, OR SPECIAL KNOWLEDGE OR EFFORT FOR OPERATION FROM
 THE EGRESS
 SIDE.
 7.2.1.5.4 THE REQUIREMENTS OF 7.2.1.5.1 AND 7.2.1.5.3
 SHALL NOT
 APPLY WHERE OTHERWISE PROVIDED IN CHAPTERS 18 THROUGH
 23.
  
 9). WHAT MEASURES WILL BE IMPLEMENTED TO ENSURE THAT
 THE ROLLUP DOOR WILL NOT BE CLOSED WHEN THE BUILDING IS
 OCCUPIED.
 10). MANUFACTURER SPECIFICATION SHEETS TO BE PROVIDED
 FOR ALL EQUIPMENT TO BE INSTALLED FOR EGRESS DOORS.
 11).WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
 12).NEW RESTROOM INSTALLATION APPEARS TO BLOCK THE
 MEANS OF EGRESS WITH AN OUTWARD SWINGING DOOR.
  
 S. THOMAS
 561-804-4728

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2020-10-25 Cont ID  
Sent By jwitmer Date 2020-10-25 Time 13:00 Rev Time 0.00
Received By jwitmer Date 2020-10-21 Time 13:56 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2020-10-20 Cont ID  
Sent By pleduc Date 2020-10-20 Time   Rev Time 0.00
Received By pleduc Date 2020-10-16 Time 08:21 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2020-10-13 Cont ID  
Sent By jwitmer Date 2020-10-13 Time 10:44 Rev Time 0.00
Received By jwitmer Date 2020-10-07 Time 16:02 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2020-09-24 Cont ID  
Sent By jleahy Date 2020-09-24 Time 13:04 Rev Time 0.00
Received By jleahy Date 2020-09-16 Time 11:01 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-08-11 Cont ID  
Sent By jleahy Date 2020-08-11 Time 09:01 Rev Time 0.00
Received By jleahy Date 2020-07-27 Time 09:26 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2020-05-15 Time   Rev Time 0.00
Received By lmarchan Date 2020-04-24 Time 08:12 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2020-04-28 Cont ID  
Sent By jwitmer Date 2020-04-28 Time 17:20 Rev Time 0.00
Received By jwitmer Date 2020-04-28 Time 17:20 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2020-09-21 Cont ID  
Sent By medwards Date 2020-09-21 Time 09:47 Rev Time 0.00
Received By medwards Date 2020-09-21 Time 09:47 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2020-08-05 Cont ID  
Sent By hmoser Date 2020-08-05 Time 11:31 Rev Time 0.00
Received By hmoser Date 2020-08-05 Time 10:35 Sent To  
Notes
2020-08-05 11:31:10PLAN DENIED
 1) PROVIDE DUCT SIZE ON ALL DUCT NEW AND EXISTING
 SECTION 107 FBC 2017
 2) DUCT DETECTORS SHALL BE INSTALLED ON THE SUPPLY SIDE
 OF THE AIR CONDITIONING
 EQUIPMENT. SECTION 606.2.1 FBC (M) 2017
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2020-04-28 Cont ID  
Sent By medwards Date 2020-04-28 Time 11:19 Rev Time 0.00
Received By medwards Date 2020-04-28 Time 09:08 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 5 Status P Date 2020-10-19 Cont ID  
Sent By ccole Date 2020-10-19 Time 08:21 Rev Time 0.00
Received By ccole Date 2020-10-19 Time 07:12 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 4 Status F Date 2020-10-09 Cont ID  
Sent By ccole Date 2020-10-09 Time 09:00 Rev Time 0.00
Received By ccole Date 2020-10-08 Time 11:58 Sent To  
Notes
2020-10-09 09:00:214TH REVIEW FBC-2017 PLUMBING
 PERMIT 20040876
 10/9/2020
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 DENIED.
  
 1) SHEET A.09-: THE MIRROR SHALL BE INSTALLED WITH THE
 BOTTOM EDGE OF THE REFLECTING SURFACE 40 INCHES MAXIMUM
 ABOVE THE FINISH FLOOR OR GROUND- SECTION 603.3.
 PLEAASE CORRECT THE DETAIL.
  
 2) SHEETS P-00 & P-02: LAVATORY PLUMBING DETAIL 1-
 MIXING VALVE CONFLICTS WITH DETAIL- 4 TANKLESS WATER
 HEATER- SECTION 107.2.1 WPB. PROVIDE A DETAIL THAT
 SHOWS THE WATER HEATER AND VALVE PLUMBING COMBINED.
  
 3) SHEET A.08: THE SPOUT HEIGHTS OF THE DRINKING
 FOUNTAINS ARE NOT SHOWN BUT WOULD NOT BE IN COMPLIANCE
 BASED ON THE MEASUREMENTS SHOWN TO THE RIMS OF THE
 FOUNTAINS- SEE SECTIONS 602.4- 602.7 FBC ACC. THE
 DETAILS ARE FOUND ON A DOOR AND WINDOW SHEET. IT MAY BE
 HELPFUL TO RELOCATE THE DETAILS TO A MORE RELEVANT PLAN
 SHEET- SECTION 107.2.1 WPB.
  
 4) 3RD REQUEST TO SUBMIT A PLUMBING SUB-PERMIT
 APPLICATION PER SECTION 105.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 3 Status F Date 2020-09-17 Cont ID  
Sent By ccole Date 2020-09-17 Time 13:34 Rev Time 0.00
Received By ccole Date 2020-09-17 Time 07:49 Sent To  
Notes
2020-09-17 13:36:133RD REVIEW FBC-2017 PLUMBING
 PERMIT 20040876
 9/17/2020
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
 COMMENTS 5F, 5J, & 8 LISTED BELOW FROM THE 1ST AND 2ND
 REVIEWS LISTED BELOW HAVE NOT BEEN ADDRESSED- PLEASE
 COMPLY WITH THE COMMENTS.
  
 5) SHEET A.09-
 F) FAILED. LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF
 GRAB BARS- SECTION 604.5 REFER TO FIGURES 604.5.1 AND
 604.5.2 FOR CORRECT POSITIONING AND LENGTHS OF THE GRAB
 BARS. REFER TO SECTION 609.4 CORRECT MOUNTING HEIGHTS
 OF THE BARS- 33 INCHES MINIMUM AND 36 INCHES MAXIMUM
 ABOVE THE FINISH FLOOR MEASURED TO THE TOP OF THE
 GRIPPING SURFACE. (SEE FIGURE 604.5.2: THE REAR GRAB
 SHALL BE LOCATED TO PROVIDE A MINIMUM 12 IN. EXTENSION
 FROM THE CENTER OF THE WATER CLOSET TO THE ADJACENT
 WALL. THE DRAWING SHOWS AN EXTENSION OF 16-18 IN. FROM
 THE CENTER TO THE WALL AND A 6 IN. SPACE BETWEEN THE
 BAR AND THE WALL, THEREFORE THE 18 IN. EXTENSION WOULD
 BE COMPLIANT, BUT A 16 IN. EXTENSION WOULD NOT BECAUSE
 THE BAR WOULD ONLY EXTEND 10IN. FROM THE CENTER OF THE
 WATER CLOSET- PLEASE CORRECT THE DETAIL.)
 J) MIRROR: THE MIRROR SHALL BE INSTALLED WITH THE
 BOTTOM EDGE OF THE REFLECTING SURFACE 40 INCHES MAXIMUM
 ABOVE THE FINISH FLOOR OR GROUND- SECTION 603.3.
  
 8) FAILED. SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE
 WATER HEATERS- SECTION 502.1 FBC P. THE SPECS WERE NOT
 SUBMITTED HOWEVER A REVIEW OF THE SPECS ON THE EEEMAX
 WEBSITE INDICATE THE SELECTED EX2412 IS LIMITED TO 0.5
 GPM FLOW RATE AT 33 DEGREE F TEMPERATURE RISE. THE
 TANKLESS HEATERS ARE ADEQUATE FOR THE REQUIRED 0.4 GPM
 FLOW RATE AT THE LAVATORIES, HOWEVER THEY ARE
 UNDERSIZED FOR THE MOP SINK AND THE KITCHEN SINK WHICH
 REQUIRE FLOW RATES OF 3 AND 1.75 GPM FLOW RATES.
  
 9) SHEET A-01: PLEASE OUTLINE THE SLAB DEMOLITION AREA
 FOR NEW DRAIN INSTALLATIONS, AND PROVIDE A SLAB REPAIR
 DETAIL- SECTION 107.2.1 WPB AND SECTION 1816 FBC B.
  
 10) SUBMIT A PLUMBING SUB-PERMIT APPLICATION PER
 SECTION 105.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2020-08-05 Cont ID  
Sent By ccole Date 2020-08-05 Time 16:52 Rev Time 0.00
Received By ccole Date 2020-08-05 Time 15:09 Sent To  
Notes
2020-08-05 17:02:122ND REVIEW FBC-2017 PLUMBING
 PERMIT 20040876
 8/5/2020
  
 CODES IN EFFECT:
  
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
 COMMENTS FROM THE 1ST REVIEW LISTED BELOW WILL BE
 MARKED AS PASSED OR FAILED. ADDITIONAL NOTES IN CAPITOL
 LETTERS WILL BE ADDED TO FAILED COMMENTS.
  
 1) PASSED. SHEET P.01: SHOW A FULL-OPEN TYPE VALVE WILL
 BE INSTALLED ON THE DISCHARGE SIDE OF THE WATER METER-
 SECTION 606.1(3) FBC P.
  
 2) PASSED. P-01 & P.02: MODIFY THE DRAWINGS TO INCLUDE
 ANY PLUMBING FIXTURES IN THE KITCHEN- ICE MAKER,
 DISHWASHER ETC- SECTION 107.2.1 WPB.
  
 3) PASSED. P-02: SHOW THE REQUIRED WATER HAMMER
 ARRESTORS FOR THE WATER LINE TO THE EWC- 604.9 FBC P.
 PLEASE NOTE THAT WATER HAMMER ARRESTORS ARE ALSO
 REQUIRED ON THE REFRIGERATOR ICE MAKER LINE AND
 DISHWASHER SUPPLY LINE IF THOSE ITEMS ARE BEING
 INSTALLED. - SECTION 604.9 FBC P.
  
 4) PASSED. SHEET A.09: THE TOILET ROOMS SHALL BE
 IDENTIFIED AS EITHER MALE OR FEMALE PER SECTION 403.2
 FBC P.
  
 5) A.09: PLEASE PROVIDE ENLARGED DIMENSIONED DRAWINGS
 OF THE MEN'S AND WOMEN'S TOILET ROOMS TO SHOW
 COMPLIANCE WITH SECTION 213.2 FBC ACC. THE ENLARGED
 DRAWINGS AND ELEVATION VIEWS SHALL SHOW:
 A) PASSED. CLEAR FLOOR SPACES FOR THE WATER CLOSETS-
 SECTION 604.3 FBC ACC.
 B) PASSED. CLEAR FLOOR SPACES FOR THE LAVATORIES-
 SECTION 606.2.
 C) PASSED. TURNING SPACES IN THE TOILET ROOMS- SECTION
 304.3.
 D) PASSED. CENTERLINES OF THE WATER CLOSETS FROM THE
 SIDE WALLS OR PARTITIONS- SECTION 604.2.
 E) FAILED. HEIGHTS OF THE WATER CLOSET SEATS FROM THE
 FINISHED FLOORS- SECTION 604.4. THE DETAIL SHOWS THE
 HEIGHT DIMENSION TO THE RIM AND NOT THE SEAT.
 F) FAILED. LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF
 GRAB BARS- SECTION 604.5 REFER TO FIGURES 604.5.1 AND
 604.5.2 FOR CORRECT POSITIONING AND LENGTHS OF THE GRAB
 BARS. REFER TO SECTION 609.4 CORRECT MOUNTING HEIGHTS
 OF THE BARS- 33 INCHES MINIMUM AND 36 INCHES MAXIMUM
 ABOVE THE FINISH FLOOR MEASURED TO THE TOP OF THE
 GRIPPING SURFACE.
 G) PASSED. LOCATIONS OF FLUSH CONTROLS- SECTION 604.6.
 H) FAILED LOCATIONS, CLEARANCES, AND MOUNTING HEIGHTS
 FOR DISPENSERS- SECTION 604.7. MOUNTING HEIGHT NOT
 SHOWN.
 I) THE KNEE AND TOE CLEARANCES FOR THE LAVATORY ARE NOT
 SHOWN- SEE SECTIONS 306 AND FIGURES 306.2 AND 306.3.
 J) MIRROR: THE MIRROR SHALL BE INSTALLED WITH THE
 BOTTOM EDGE OF THE REFLECTING SURFACE 40 INCHES MAXIMUM
 ABOVE THE FINISH FLOOR OR GROUND- SECTION 603.3.
  
 6) FAILED. PROVIDE ACCESSIBILITY COMPLIANCE DETAILS FOR
 THE NEW DRINKING FOUNTAIN- CLEAR FLOOR SPACE APPROACH,
 KNEE AND TOE CLEARANCES, SPOUT HEIGHTS ETC- SECTION
 602.1 FBC ACC. NOT PROVIDED ON THE PLANS.
  
 7) PASSED. PROVIDE ACCESSIBILITY COMPLIANCE DETAILS FOR
 THE KITCHENETTE SINK- CLEAR FLOOR SPACE APPROACHES
 WAITING SINK RIM OR COUNTER HEIGHT, AND KNEE AND TOE
 CLEARANCES- SECTION 606.1 FBC ACC.
  
 8) PASSED. SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE
 WATER HEATERS- SECTION 502.1 FBC P.
  
 9) TEMPERED WATER IS REQUIRED FOR THE NEW LAVATORIES
 PER SECTION 416.5 FBC P. PLEASE MODIFY THE ISOMETRIC
 AND FLAT LINE DRAWINGS TO SHOW THE LOCATIONS OF THE
 MIXING VALVE SHOWN ON SHEET P-00.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2020-05-15 Cont ID  
Sent By ccole Date 2020-05-15 Time 15:13 Rev Time 0.00
Received By ccole Date 2020-05-15 Time 13:22 Sent To  
Notes
2020-05-15 15:14:12 
 1ST REVIEW FBC-2017 PLUMBING
 PERMIT 20040876
 5/15/2020
  
 CODES IN EFFECT:
  
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET P.01: SHOW A FULL-OPEN TYPE VALVE WILL BE
 INSTALLED ON THE DISCHARGE SIDE OF THE WATER METER-
 SECTION 606.1(3) FBC P.
  
 2) P-01 & P.02: MODIFY THE DRAWINGS TO INCLUDE ANY
 PLUMBING FIXTURES IN THE KITCHEN- ICE MAKER, DISHWASHER
 ETC- SECTION 107.2.1 WPB.
  
 3) P-02: SHOW THE REQUIRED WATER HAMMER ARRESTORS FOR
 THE WATER LINE TO THE EWC- 604.9 FBC P. PLEASE NOTE
 THAT WATER HAMMER ARRESTORS ARE ALSO REQUIRED ON THE
 REFRIGERATOR ICE MAKER LINE AND DISHWASHER SUPPLY LINE
 IF THOSE ITEMS ARE BEING INSTALLED. - SECTION 604.9 FBC
 P.
  
 4) SHEET A.09: THE TOILET ROOMS SHALL BE IDENTIFIED AS
 EITHER MALE OR FEMALE PER SECTION 403.2 FBC P.
  
 5) A.09: PLEASE PROVIDE ENLARGED DIMENSIONED DRAWINGS
 OF THE MEN'S AND WOMEN'S TOILET ROOMS TO SHOW
 COMPLIANCE WITH SECTION 213.2 FBC ACC. THE ENLARGED
 DRAWINGS AND ELEVATION VIEWS SHALL SHOW:
 A) CLEAR FLOOR SPACES FOR THE WATER CLOSETS- SECTION
 604.3 FBC ACC.
 B) CLEAR FLOOR SPACES FOR THE LAVATORIES- SECTION
 606.2.
 C) TURNING SPACES IN THE TOILET ROOMS- SECTION 304.3.
 D) CENTERLINES OF THE WATER CLOSETS FROM THE SIDE WALLS
 OR PARTITIONS- SECTION 604.2.
 E) HEIGHTS OF THE WATER CLOSET SEATS FROM THE FINISHED
 FLOORS- SECTION 604.4.
 F) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB
 BARS- SECTION 604.5
 G) LOCATIONS OF FLUSH CONTROLS- SECTION 604.6.
 H) LOCATIONS, CLEARANCES, AND MOUNTING HEIGHTS FOR
 DISPENSERS- SECTION 604.7.
  
 6) PROVIDE ACCESSIBILITY COMPLIANCE DETAILS FOR THE NEW
 DRINKING FOUNTAIN- CLEAR FLOOR SPACE APPROACH, KNEE AND
 TOE CLEARANCES, SPOUT HEIGHTS ETC- SECTION 602.1 FBC
 ACC.
  
 7) PROVIDE ACCESSIBILITY COMPLIANCE DETAILS FOR THE
 KITCHENETTE SINK- CLEAR FLOOR SPACE APPROACHES WAITING
 SINK RIM OR COUNTER HEIGHT, AND KNEE AND TOE
 CLEARANCES- SECTION 606.1 FBC ACC.
  
 8) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE WATER
 HEATERS- SECTION 502.1 FBC P.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 6 Status P Date 2020-10-26 Cont ID  
Sent By shill Date 2020-10-26 Time 08:43 Rev Time 0.00
Received By shill Date 2020-10-26 Time 08:43 Sent To  
Notes
2020-10-26 08:43:44A1 OK ON MY COMPUTER; P0 DOES NOT HAVE A DIGITAL
 SIGNTURE BUT PASSING REVIEW PER FBPE EMERGENCY ORDER
 (COVID-19)
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 5 Status F Date 2020-10-19 Cont ID  
Sent By ccole Date 2020-10-19 Time 08:25 Rev Time 0.00
Received By ccole Date 2020-10-19 Time 08:21 Sent To  
Notes
2020-10-19 08:29:46SIGNATURE REVIEW
 10/19/2020
  
 1) NEW SHEETS A.00 AND P.00: I AM UNABLE TO VERIFY THE
 VALIDITY OF THE DIGITAL SEALS AND SIGNATURES USING THE
 ADOBE SYSTEM. THE SHEETS MAY BEAR COPIED SEALS AND
 SIGNATURES.
  
 SIGNATURE REVIEW
 10/9/2020
  
 1) ERROR MESSAGES ON NEW PLAN SHEETS A07, A08, A09,
 P00, P01, & P02:
 "SIGNATURE CONTAINS INCORRECT, UNREGOGNIZED, CORRUPTED,
 OR SUSPICIOUS DATA."
 VERIFICATION OF ORIGINAL ELECTRONIC SEALS AND
 SIGNATURES COULD NOT BE DONE.
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status F Date 2020-10-09 Cont ID  
Sent By ccole Date 2020-10-09 Time 09:13 Rev Time 0.00
Received By ccole Date 2020-10-09 Time 09:02 Sent To  
Notes
2020-10-09 09:13:35SIGNATURE REVIEW
 10/9/2020
 1) ERROR MESSAGES ON NEW PLAN SHEETS A07, A08, A09,
 P00, P01, & P02:
 "SIGNATURE CONTAINS INCORRECT, UNREGOGNIZED, CORRUPTED,
 OR SUSPICIOUS DATA."
 VERIFICATION OF ORIGINAL ELECTRONIC SEALS AND
 SIGNATURES COULD NOT BE DONE.
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2020-09-21 Cont ID  
Sent By medwards Date 2020-09-21 Time 10:05 Rev Time 0.00
Received By medwards Date 2020-09-21 Time 09:49 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2020-08-05 Cont ID  
Sent By ccole Date 2020-08-05 Time 17:09 Rev Time 0.00
Received By ccole Date 2020-08-05 Time 17:09 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-05-15 Cont ID  
Sent By ccole Date 2020-05-15 Time 15:29 Rev Time 0.00
Received By ccole Date 2020-05-15 Time 15:29 Sent To  
Notes
2020-05-15 15:36:39THE PLANS ARE INDICATED BE DIGITALLY "SIGNED" BUT NOT
 "SEALED BY THE AOR . ALL RESUBMITTED ELECTRONIC PLANS
 SHALL STATE "THIS ITEM HAS BEEN ELECTRONICALLY SIGNED
 AND SEALED BY _________ON DATE________USING A SHA-1
 AUTHENTICATION CODE"- SECTION 61G15-23.005 FAC.
  
  