| 2020-05-07 10:01:40 | 2017 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 20040872 |
| | ADD: 300 27TH ST. |
| | CONT: BLUE WATER VENTURES OF THE PALM BEACHES |
| | TEL: 561-339-6128 |
| | E-MAIL: [email protected] |
| | |
| | 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: THURS. MAY 7, 2020 |
| | ACTION: DENIED |
| | |
| | 1) THE FLOOR PLAN WAS NOT DESIGNED BY EITHER AN |
| | ENGINEER OR ARCHITECT. CERTIFICATION BY CONTRACTOR. THE |
| | CONTRACTOR (QUALIFIER) THAT CREATED / DRAWN THE SET OF |
| | PLANS WILL NEED TO IDENTIFY THEMSELVES AS THE AUTHOR OF |
| | THE PLANS. PLEASE PRINT YOUR NAME, SIGN YOUR NAME AND |
| | LICENSE NUMBER FOR THE TRADE YOU ARE LICENSED IN AND |
| | PLANS DRAWN. 107.3.4.3 CERTIFICATION BY CONTRACTOR. |
| | |
| | 2) THE PERMIT VALUE SEEMS TO BE LOW FOR THE SCOPE OF |
| | WORK THAT IS TO BE COMPLETED UNDER THIS PERMIT. 109.3* |
| | BUILDING PERMIT VALUATION. |
| | IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE |
| | CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE, |
| | ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS |
| | APPEARS TO BE UNDER ESTIMATED ON THE APPLICATION, THE |
| | PERMIT SHALL BE DENIED. FOR PERMITTING PURPOSES, |
| | VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL |
| | REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND |
| | SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE |
| | STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR |
| | FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR |
| | BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING |
| | COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE. |
| | VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED |
| | DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES |
| | (MARSHALL-SWIFT, MEANS, ETC.) WITH REGIONAL ADJUSTMENTS |
| | FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE |
| | CONGRESS. |
| | |
| | THIS MAIN BUILDING PERMIT WILL INCLUDE THE FEES FOR THE |
| | MECHANICAL, ELECTRICAL, PLUMBING & ROOFING PERMITS. |
| | WHEN THE GENERAL CONTRACTOR COMES IN FOR A BUILDING |
| | PERMIT WITH THE SIGNED PERMIT APPLICATION FORM BY THE |
| | QUALIFIER AND OWNER AND BRINGS IN THE LISTED |
| | SUB-PERMITS M-E-P & ROOFING PERMITS SIGNED BY THE |
| | QUALIFIER OF EACH COMPANY, THEIR INSURANCES AND |
| | LICENSURE UP TO DATE, THE M-E-P AND ROOFING PERMITS ARE |
| | FREE OF CHARGE. IF THE M-E-P & ROOFING PERMITS COME IN |
| | LATER THERE WILL BE AN $80.00 ADMINISTRATIVE FEE FOR |
| | EACH PERMIT. |
| | |
| | 3) LAST YEAR THERE WAS A PERMIT ISSUED 19041186 TO |
| | REPLACE FAUCETS IN 3 UNITS. THE PROPOSED PLAN SHOWS 2 |
| | EXTERIOR DOORS, HAS THERE BEEN A DEMISING WALL REMOVED |
| | BETWEEN TWO OF THE UNITS? PLEASE PROVIDE A FLOOR PLAN |
| | OF THE EXISTING BUILDING BEFORE ANY WORK HAD STARTED. |
| | PLEASE PROVIDE AN OVERALL FLOOR PLAN OF THE 2 BUILDINGS |
| | SHOWING THE TENANT SPACES. 107.2.1.2. |
| | |
| | 4) THE PROPOSED FLOOR PLAN IS MISSING REQUIRED |
| | INFORMATION FOR COMMERCIAL BUILDING PLAN REVIEW. 2017 |
| | WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| | CODE, CHAPTER 1, ADMINISTRATIVE CODE: |
| | 107.3.5.1 COMMERCIAL BUILDINGS |
| | 107.3.5.1.1. BUILDING |
| | |
| | 2. OCCUPANCY TYPE/ PROVIDE USE FOR EACH ROOM, NOT JUST |
| | ROOM 3. ADDITIONAL COMMENTS MAY OCCUR ONCE THE USES ARE |
| | KNOWN. |
| | |
| | 3. MINIMUM TYPE OF CONSTRUCTION |
| | |
| | 4. REQUIRED TO BE FIRE SPRINKLERED OR NOT |
| | |
| | 5. LIFE SAFETY SHALL INCLUDE: |
| | OCCUPANCY LOAD NET OR GROSS |
| | MEANS OF EGRESS PROVIDE THE SIZE OF ALL DOORWAYS. |
| | EXIT LIGHTS AND DIRECTIONAL. |
| | COMMON PATH OF TRAVEL FROM THE MOST REMOTE POINT |
| | PROVIDE LOCKING INFORMATION FOR EXTERIOR DOORS |
| | |
| | 8) STRUCTURAL REQUIREMENTS: |
| | WIND DESIGN CRITERIA: 2017 FBC-B 1603.1.4 WIND DESIGN |
| | DATA. |
| | THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL |
| | BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE |
| | DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE |
| | STRUCTURE: |
| | |
| | 8.1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST), |
| | MILES PER HOUR AND NOMINAL DESIGN WIND SPEED, VASD, AS |
| | DETERMINED IN ACCORDANCE WITH SECTION 1609.3.1. |
| | |
| | 8.2. RISK CATEGORY. |
| | |
| | 8.3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE |
| | THAN ONE WIND EXPOSURE IS UTILIZED. TABLE 1609.7.2. |
| | HEIGHT AND EXPOSURE. ASCE 7-10 TABLE 30.3.1. |
| | |
| | 8.4. APPLICABLE INTERNAL PRESSURE COEFFICIENT. |
| | |
| | 8.5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR |
| | COMPONENTS AND CLADDING MATERIALS SPECIFICALLY DESIGNED |
| | BY THE REGISTERED DESIGN PROFESSIONAL RESPONSIBLE FOR |
| | THE DESIGN OF THE STRUCTURE, PSF. |
| | |
| | 8.6. TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT & |
| | EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE |
| | BUILDING. 1609.3.1 WIND SPEED CONVERSION VULT TO VASD. |
| | |
| | 10) ACCESSIBILITY REQUIREMENTS SHALL INCLUDE: |
| | ACCESSIBLE ENTRANCE |
| | VERTICAL ACCESSIBILITY |
| | TOLIET AND OR BATHING FACILITIES |
| | DRINKING FOUNTAINS |
| | ACCESSIBLE SINKS AND VANITIES |
| | |
| | 11) PLEASE REVIEW HOW YOU ARE TO MEET DISPROPORTIONATE |
| | COST. EITHER THE CONTRACTOR OR THE DESIGNER OF RECORD |
| | ON THEIR LETTERHEAD ARE TO PROVIDE ON THEIR LETTERHEAD |
| | HOW THEY ARE GOING TO SPEND THE 20% DISPROPORTIONATE |
| | FUNDS IN THE ORDER LISTED BELOW. 2017 FBC-ACCESSIBILITY |
| | CODE: |
| | |
| | |
| | 11A) ACCESS CODE 404.2.4.1 SWINGING DOORS AND GATES. |
| | SWINGING DOORS AND GATES SHALL HAVE MANEUVERING |
| | CLEARANCES COMPLYING WITH TABLE 404.2.4.1. |
| | DOORS NEED TO BE IDENTIFIED AND PROVIDE WIDTH OF DOORS. |
| | MINIMUM MANEUVERING CLEARANCES AT DOORS AND GATES SHALL |
| | COMPLY WITH 404.2.4. MANEUVERING CLEARANCES SHALL |
| | EXTEND THE FULL WIDTH OF THE DOORWAY AND THE REQUIRED |
| | LATCH SIDE FOR SIDE CLEARANCE. |
| | |
| | 11B) PROVIDE RESTROOM DETAILS FLOOR PLAN AND ELEVATIONS |
| | TO DETERMINE COMPLIANCE WITH CHAPTER 6 OF THE |
| | ACCESSIBILITY CODE. |
| | |
| | 11C) DRINKING FOUNTAINS. |
| | |
| | |
| | 12) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE |
| | THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED |
| | DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE |
| | MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS |
| | AND INFORMATION LACKING UNDER THE PRIOR REVIEW. |
| | |
| | |
| | JAMES A. WITMER BN, PX, SFP, CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT |
| | 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 |
| | TEL: 561-805-6717 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |