Plan Review Details - Permit 20040853
Plan Review Stops For Permit 20040853
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2020-06-30 Cont ID  
Sent By cthroop Date 2020-06-30 Time 13:36 Rev Time 0.00
Received By cthroop Date 2020-06-30 Time 07:37 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2020-05-07 Cont ID  
Sent By rmcphers Date 2020-05-07 Time 08:55 Rev Time 0.00
Received By rmcphers Date 2020-05-06 Time 16:23 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2020-06-30 Cont ID  
Sent By jleahy Date 2020-06-30 Time 10:23 Rev Time 0.00
Received By jleahy Date 2020-06-30 Time 10:06 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-05-07 Cont ID  
Sent By jleahy Date 2020-05-07 Time 15:33 Rev Time 0.00
Received By jleahy Date 2020-05-07 Time 15:02 Sent To  
Notes
2020-05-07 15:35:34ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 1) VALUE FOR WORK SHOW IS LOW, PLEASE SUBMIT A SIGNED
 CONTRACT FOR THE WORK.
  
 109.3 BUILDING PERMIT VALUATIONS. IF, IN THE OPINION OF
 THE BUILDING OFFICIAL, THE CLAIMED VALUATION OF
 BUILDING, ALTERATION, STRUCTURE, ELECTRICAL, GAS,
 MECHANICAL OR PLUMBING SYSTEMS APPEARS TO BE
 UNDERESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE
 DENIED, UNLESS THE APPLICANT CAN SHOW DETAILED,
 QUANTITY ESTIMATES, AND/OR BONA FIDE SIGNED CONTRACTS
 (EXCLUDING LAND VALUE) TO MEET THE APPROVAL OF THE
 BUILDING OFFICIAL. FOR PERMITTING PURPOSES, VALUATION
 OF BUILDINGS AND SYSTEMS SHALL BE TOTAL REPLACEMENT
 VALUE TO INCLUDE STRUCTURAL, ELECTRIC, PLUMBING,
 MECHANICAL, INTERIOR FINISH, RELATIVE SITE WORK,
 ARCHITECTURAL AND DESIGN FEES, MARKETING COSTS,
 OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY
 INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT
 VALUATION SHALL BE SET BY THE BUILDING OFFICIAL.
  
  

Review Stop G GAS REVIEW
Rev No 2 Status N Date 2020-06-30 Cont ID  
Sent By rmcdouga Date 2020-06-30 Time 15:25 Rev Time 0.00
Received By rmcdouga Date 2020-06-30 Time 15:25 Sent To  
Notes
2020-06-30 15:25:59REVIEW BY JERALD SMITH.

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2020-06-04 Cont ID  
Sent By jpearson Date 2020-06-04 Time 14:06 Rev Time 0.00
Received By jpearson Date 2020-06-04 Time 14:05 Sent To  
Notes
2020-06-04 14:05:56REVIEWED BY JERRY SMITH.
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION
 NFPA 54 = NATIONAL FUEL GAS CODE
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 20040853 1500 CENTREPARK BLVD
  
 THIS PERMIT IS FOR CONSTRUCTION OF A POOL SHOWN ON
 MASTER PERMIT 19030235
  
 A SEPARATE FUEL GAS PERMIT IS REQUIRED FOR THE GAS POOL
 HEATERS. A SEPARATE FUEL GAS PERMIT WAS ALSO REQUIRED
 ON PLUMBING APPROVAL NOTED ON THE MASTER PERMIT
 19030235 (SEE APPROVED PLAN SHEET 169-P.2.1.C). NO
 PLANS OR PERMIT APPLICATION (SEE GAS SUB PERMIT
 20020590 ATTACHED TO MASTER PERMIT 19030235) FOR GAS
 HAVE BEEN FILED TO THIS DATE.
 A GAS PLAN HAS NOT BEEN INCLUDED IN THIS SUBMITTAL
 PACKAGE. A GAS PLAN REVIEW HAS NOT BEEN PERFORMED AT
 THIS TIME. A SEPARATE GAS PERMIT AND PLANS WILL BE
 REQUIRED FOR A CONTRACTOR TO PERFORM THE RELATED WORK.
 PROVIDE COMPLETE PLANS, APPLIANCE/EQUIPMENT
 SPECIFICATIONS AND GAS RISER AND PLAN VIEW THAT REFLECT
 THE ENTIRE SCOPE OF WORK TO BE PERFORMED PER WPB FBC
 107.2.1.
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
 ALL PLANS TO BE DIGITALLY SIGNED AND SEALED BY THE
 DESIGNER IN ACCORDANCE WITH FAC AND FS.
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-246-0882 MOBILE
  
 20040853 1500 CENTREPARK BLVD
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-07-01 Cont ID  
Sent By lmarchan Date 2020-07-01 Time 08:00 Rev Time 0.00
Received By lmarchan Date 2020-06-24 Time 16:17 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-06-12 Cont ID  
Sent By cpuell Date 2020-06-12 Time 11:46 Rev Time 0.00
Received By cpuell Date 2020-04-21 Time 12:26 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2020-06-30 Cont ID  
Sent By rmcdouga Date 2020-06-30 Time 15:26 Rev Time 0.00
Received By rmcdouga Date 2020-06-30 Time 14:03 Sent To  
Notes
2020-06-30 15:26:21REVIEW BY JERALD SMITH.

Review Stop P PLUMBING
Rev No 1 Status F Date 2020-06-04 Cont ID  
Sent By jpearson Date 2020-06-04 Time 14:06 Rev Time 0.00
Received By jpearson Date 2020-06-04 Time 09:11 Sent To  
Notes
2020-06-04 09:11:42REVIEWED BY JERRY SMITH.
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION
 NFPA 54 = NATIONAL FUEL GAS CODE
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
  
 20040853 1500 CENTREPARK BLVD
  
 1ST REVIEW
  
 THIS PERMIT IS FOR CONSTRUCTION OF A POOL SHOWN ON
 MASTER PERMIT 19030235
  
 A SEPARATE FUEL GAS PERMIT IS REQUIRED FOR THE GAS POOL
 HEATERS. A SEPARATE FUEL GAS PERMIT WAS ALSO REQUIRED
 ON PLUMBING APPROVAL NOTED ON THE MASTER PERMIT
 19030235 (SEE APPROVED PLAN SHEET 169-P.2.1.C). NO
 PLANS OR PERMIT APPLICATION (SEE GAS SUB PERMIT
 20020590 ATTACHED TO MASTER PERMIT 19030235) FOR GAS
 HAVE BEEN FILED TO THIS DATE.
 A GAS PLAN HAS NOT BEEN INCLUDED IN THIS SUBMITTAL
 PACKAGE. A GAS PLAN REVIEW HAS NOT BEEN PERFORMED AT
 THIS TIME. A SEPARATE GAS PERMIT AND PLANS WILL BE
 REQUIRED FOR A CONTRACTOR TO PERFORM THE RELATED WORK.
 PROVIDE COMPLETE PLANS, APPLIANCE/EQUIPMENT
 SPECIFICATIONS AND GAS RISER AND PLAN VIEW THAT REFLECT
 THE ENTIRE SCOPE OF WORK TO BE PERFORMED PER WPB FBC
 107.2.1.
  
 PLUMBING COMMENTS: DENIED
 1. VALUE FOR WORK SHOWN IS LOW, PLEASE SUBMIT A SIGNED
 CONTRACT FOR THE WORK.
 PER WPB FBC 109.3 BUILDING PERMIT VALUATIONS. IF, IN
 THE OPINION OF THE BUILDING OFFICIAL, THE CLAIMED
 VALUATION OF BUILDING, ALTERATION, STRUCTURE,
 ELECTRICAL, GAS, MECHANICAL OR PLUMBING SYSTEMS APPEARS
 TO BE UNDERESTIMATED ON THE APPLICATION, THE PERMIT
 SHALL BE DENIED, UNLESS THE APPLICANT CAN SHOW
 DETAILED, QUANTITY ESTIMATES, AND/OR BONA FIDE SIGNED
 CONTRACTS (EXCLUDING LAND VALUE) TO MEET THE APPROVAL
 OF THE BUILDING OFFICIAL. FOR PERMITTING PURPOSES,
 VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL
 REPLACEMENT VALUE TO INCLUDE STRUCTURAL, ELECTRIC,
 PLUMBING, MECHANICAL, INTERIOR FINISH, RELATIVE SITE
 WORK, ARCHITECTURAL AND DESIGN FEES, MARKETING COSTS,
 OVERHEAD AND PROFIT, EXCLUDING ONLY LAND VALUE.
 VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY
 INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT
 VALUATION SHALL BE SET BY THE BUILDING OFFICIAL.
 2. SEE PLAN SHEET SP 1.02: NOTE 13 DOES NOT ACCURATELY
 REFLECT THE REQUIRED AND PROVIDED QUANTITIES OF
 RESTROOM FIXTURES THAT ARE ACTUALLY SHOWN ON THE PLAN.
 PER WPB FBC 107.2.1, CLARIFY.
 3. AS REQUIRED BY THE DEPARTMENT OF HEALTH 454.1.6.5.14
 AND WPB FBC 107.2.1, PROVIDE AND SHOW THE REQUIRED
 THERMOMETER ON THE DISCHARGE PIPING DOWNSTREAM OF THE
 POOL HEATERS.
  
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
 ALL PLANS TO BE DIGITALLY SIGNED AND SEALED BY THE
 DESIGNER IN ACCORDANCE WITH FAC AND FS.
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-246-0882 MOBILE
  
 20040853 1500 CENTREPARK BLVD
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2020-06-30 Cont ID  
Sent By cthroop Date 2020-06-30 Time 13:36 Rev Time 0.00
Received By cthroop Date 2020-06-30 Time 07:37 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2020-05-07 Cont ID  
Sent By rmcphers Date 2020-05-07 Time 09:04 Rev Time 0.00
Received By rmcphers Date 2020-05-07 Time 09:04 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2020-06-25 Cont ID  
Sent By jroach Date 2020-06-25 Time 16:54 Rev Time 0.00
Received By jroach Date 2020-06-25 Time 16:54 Sent To  
Notes
2020-06-25 16:55:07THE SCOPE OF THIS REVIEW IS LIMITED TO THE POOL ONLY!
  
 PROVISO(S)
  
 1. ALL MECHANICAL EQUIPMENT SHALL BE ENCLOSED BY A
 SOLID/OPAQUE FENCE, WALL, OR HEDGE THAT COMPLETELY
 SCREENS IT FROM VIEW. A PICKET FENCE DOES NOT MEET THIS
 REQUIREMENT.
 _______________________________________________________
 _____________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN P. ROACH, AICP, PRINCIPAL PLANNER
 P: 561.822.1448 | E: [email protected]

Review Stop Z ZONING
Rev No 1 Status F Date 2020-06-12 Cont ID  
Sent By jroach Date 2020-06-12 Time 11:26 Rev Time 0.00
Received By jroach Date 2020-06-12 Time 11:26 Sent To  
Notes
2020-06-12 11:26:59ZONING PLAN REVIEW
 ________________________________________
  
 DATE OF REVIEW: 06.12.2020
 PERMIT NO.: 20040853
 ________________________________________
  
 REVIEW STATUS: FAILED
 ________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. CURRENT AND ACCURATE SURVEY SHALL BE PROVIDED.
  
 2. SETBACK DIMENSIONS SHALL BE PROVIDED FROM THE
 VARIOUS POOL EQUIPMENT ELEMENTS TO THE ADJACENT
 PROPERTY LINE.
  
 3. THE POOL EQUIPMENT EXTENDS OUTSIDE OF THE AREA THAT
 WAS SHOWN ON THE APPROVED SITE PLAN, AND APPEARS TO BE
 ENCROACHING INTO A DRAINAGE EASEMENT.
  
 4. ALL ABOVEGROUND POOL EQUIPMENT WILL NEED SCREENED
 WITH AN OPAQUE FENCE/WALL OR LANDSCAPING.
 ________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN P. ROACH, AICP, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1448
 TTY: 800.955.8771
 E: [email protected]
  
 W: WPB.ORG
  