| 2020-06-01 08:38:44 | 1ST REVIEW FBC-2017 PLUMBING |
| | PERMIT- 20040827 |
| | 5/29/20 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017 |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET A0.01: THE SCOPE OF WORK FOR THE PROJECT IS |
| | INDICATED AS A NEW INTERIOR BUILD-OUT HOWEVER THE PLANS |
| | ARE INDICATING RENOVATION WORK IN THE CORE AREA ONLY. |
| | CONCERNING THE PLUMBING PLEASE PROVIDE A CLEAR SCOPE OF |
| | WORK OUTLINE FOR THE RENOVATION- SECTION 107.2.1 AND |
| | ADDRESS THE LIST OF COMMENTS BELOW. A THOROUGH REVIEW |
| | OF THE PLUMBING PLANS CANNOT BE COMPLETED AT THIS TIME. |
| | |
| | 2) PROVIDE PLUMBING FIXTURE CALCULATIONS BASED ON TABLE |
| | 403.3 FBC P. PROVIDE A SCHEDULE THAT INDICATES THE |
| | REQUIRED AND PROVIDED NUMBER OF FIXTURES. |
| | |
| | 3) PROVIDE DEMOLITION AND PROPOSED PLANS FOR THE |
| | EXISTING TOILET ROOMS INDICATING WHAT ELEMENTS OF |
| | CONSTRUCTION-WALLS, FLOORS, PLUMBING FIXTURES, STALLS, |
| | ACCESSORIES ETC. ARE BEING REMOVED, REPLACED OR NEWLY |
| | INSTALLED- SECTION 107.2.1 WPB. |
| | |
| | 4) PROVIDE ENLARGED DIMENSIONED TOILET ROOM FLOOR PLANS |
| | AND DETAILS SHOWING COMPLIANCE WITH THE FBC-17 |
| | ACCESSIBILITY. THE ENLARGED DRAWINGS SHALL SHOW: |
| | A) CLEAR FLOOR SPACE DIMENSIONS FOR THE WATER CLOSETS- |
| | SECTION 604.3 FBC ACC. |
| | B) CLEAR FLOOR SPACE DIMENSIONS FOR THE LAVATORIES- |
| | SECTION 606.2. |
| | C) TOILET COMPARTMENT WIDTH AND LENGTH MEASUREMENTS- |
| | SECTIONS 604.2-604.8. FBC ACC, AND SECTION 405.3.1 FBC |
| | P. |
| | D) TOILET COMPARTMENT DOOR WIDTHS, DOOR SWINGS, AND |
| | WHEELCHAIR APPROACHES- SECTION 604.8.1.2 & 604.8.1.3 |
| | FBC ACC. |
| | E) TURNING SPACE DIAMETERS- SECTION 304.3. |
| | F) CENTERLINES OF THE WATER CLOSETS FROM THE SIDE WALLS |
| | OR PARTITIONS- SECTION 604.2. |
| | |
| | 5) PROVIDE TOILET ROOM ELEVATION DRAWINGS INDICATING: |
| | A) HEIGHTS OF THE WATER CLOSET SEATS FROM THE FINISHED |
| | FLOORS- SECTION 604.4. |
| | B) HEIGHTS OF THE FRONT RIM OF THE LAVATORY FROM THE |
| | FINISHED FLOOR- SECTION 606.3. |
| | C) KNEE AND TOE CLEARANCES FOR THE LAVATORIES- SECTION |
| | 306. |
| | D) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB |
| | BARS- SECTION 604.5. |
| | E) LOCATIONS OF THE WATER CLOSET FLUSH CONTROLS- |
| | SECTION 604.6. |
| | F) LOCATIONS, CLEARANCES, AND MOUNTING HEIGHTS FOR |
| | PAPER DISPENSERS- SECTION 604.7, |
| | G) HEIGHTS OF THE MIRROR FROM THE FINISHED FLOOR TO THE |
| | BOTTOM OF THE REFLECTIVE SURFACES- SECTION 603.3. |
| | |
| | 6) A1.11, P6.1, P6.2: TOILET ROOM 612 APPEARS TO BE |
| | DESIGNED AS AN ACCESSIBLE UNISEX TOILET ROOM, HOWEVER |
| | SEPARATE FACILITIES FOR MALE AND FEMALE USE ARE |
| | REQUIRED- SECTION 403.2 FBC P AND SECTION 213.2 FBC |
| | ACC. |
| | |
| | 7) A1.11, P6.1, P6.2: REFER TO SECTION 211.1.2 FBC ACC, |
| | AND TABLE 404.3 FBC P. NO FEWER THAN TWO DRINKING |
| | FOUNTAINS SHALL BE PROVIDED. ONE DRINKING FOUNTAIN |
| | SHALL COMPLY WITH SECTIONS 602.1 ? 602.6, AND ONE SHALL |
| | COMPLY WITH 602.7. SECTION 602.7 REQUIRES THAT SPOUT |
| | OUTLETS FOR STANDING PERSONS SHALL BE 38 INCHES MINIMUM |
| | AND 43 INCHES MAXIMUM FROM THE FINISHED FLOOR. SHOW THE |
| | LOCATIONS OF THE FOUNTAIN AND SHOW: |
| | A) THE CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR |
| | FORWARD WHEELCHAIR APPROACH- SECTION 602.2. FBC ACC. |
| | B) KNEE AND TOE CLEARANCES- SECTION 306. |
| | C) SPOUT HEIGHT AND SPOUT LOCATION- SECTION 602.4 AND |
| | 602.5. |
| | |
| | 8) SHOW THE LOCATION OF THE REQUIRED SERVICE SINK- |
| | TABLE 403.3. FBC P. |
| | |
| | 9) P6.1 & P6.2: REVISE THE PLUMBING PLANS TO SHOW THE |
| | WATER SUPPLY LINES AND DWV PIPING FOR THE DRINKING |
| | FOUNTAIN AND SERVICE SINK- SECTION 107.2.1 WPB. |
| | |
| | 10) P6.1: PROVIDE TRAP SEAL PRIMERS FOR THE FLOOR |
| | DRAINS- SECTION 1002.4.1.1. |
| | |
| | 11) P6.1: THE 2" VENT FOR THE WATER CLOSETS SHALL |
| | CONNECT TO THE HORIZONTAL BRANCH DRAIN BETWEEN THE TWO |
| | MOST UPSTREAM WOMEN'S WATER CLOSETS- SECTION 914.2 FBC |
| | P. |
| | |
| | 12) SUBMIT MANUFACTURER'S SPECIFICATIONS AND |
| | INSTALLATION INSTRUCTIONS FOR THE WATER HEATER- SECTION |
| | 502.1 FBC P, AND PROVIDE THE UNIT'S EFFICIENCY RATING |
| | IN THE SCHEDULE- SECTION C404.2 FBC EC. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |