| 2020-04-28 11:59:25 | 2017 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 20040762 |
| | ADD: 3515 S DIXIE HWY. |
| | CONT: BEST INDUSTRIES |
| | TEL: 772-460-8130 |
| | E-MAIL: [email protected] |
| | |
| | 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: TUES. APRIL 28TH/2020 |
| | ACTION: DENIED |
| | |
| | 1) THE DOCUMENT SUBMITTED FROM MDM SERVICES BY ENG. |
| | RICHARD R. MORRIS, A-1.03 & 8X11 SHEET WOULD APPEAR TO |
| | HAVE BEEN DIGITALLY SIGNED THEN DOWNLOADED AND THEN |
| | RE-UPLOADED. THIS DOCUMENT CANNOT BE OPENED TO VERIFY |
| | AUTHORIZATION. 61G15-23.005 PROCEDURES FOR SIGNING AND |
| | SEALING ELECTRONICALLY TRANSMITTED PLANS, |
| | SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS. |
| | |
| | FLORIDA ADMINISTRATIVE CODE 61G15-23.005 (3)(C) A |
| | SCANNED, FACSIMILE, DIGITALLY CREATED OR COPIED IMAGE |
| | OF THE LICENSEE?S SIGNATURE SHALL NOT BE USED ON |
| | ELECTRONICALLY SIGNED AND SEALED ENGINEERING PLANS, |
| | SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS. |
| | |
| | 2) SHEET A1-03 WIND DESIGN LIST THE PRESSURES AS IN |
| | ZONE 1 -36.7, ZONE 2 -43.4 AND ZONE 3 AS -43.4. WE |
| | CALCULATE THE PRESSURES FOR 10 SQ. FT./ MEAN ROOF 15 |
| | FEET, EXP. C AS ZONE 1, -37.9, ZONE 2 -63.9 AND ZONE 3 |
| | -95.7. PLEASE NOTE IN VIEWING THIS PROPERTY ON P. B. C. |
| | MY GEO NAV THERE IS ONLY A PARAPET ON 3 SIDES OF THE |
| | ROOF NONE SHOWN ON THE BACK OF THE STRUCTURE. |
| | ROOFS NO ZONE 3/ PARAPET. ASCE 7-10 FIGURE 30.4-2A. |
| | FOOTNOTE 5. IF A PARAPET IS EQUAL TO OR HIGHER THAN 3 |
| | FEET IS PROVIDED AROUND THE PERIMETER OF THE ROOF WITH |
| | 0<7 DEGREES THE NEGATIVE VALUE OF GCP IN ZONE 3 SHALL |
| | BE EQUAL TO THOSE IN ZONE 2 AND THE POSITIVE VALUES OF |
| | GCP IN ZONES 2 AND 3 SHALL BE EQUAL TO THOSE IN WALL |
| | ZONES 4 AND 5 RESPECTIVELY, SEE FIGURE 30.4-1. |
| | |
| | 3) WELDED OR BOLTED CONNECTIONS. THE CONTRACTOR IS |
| | REQUIRED TO PROVIDE WELD PROCEDURE SPECIFICATIONS & |
| | WELDER OPERATOR PERFORMANCE QUALIFICATION RECORDS IN |
| | ACCORDANCE WITH THE REFERENCED STANDARDS AT TIME OF |
| | INSPECTION. |
| | 2017 FBC-B 2204.1 WELDING |
| | 1. WELD PROCEDURES SPECIFICATIONS |
| | 2) QUALIFICATIONS OF WELDING PERSONAL |
| | 2017 FBC-B 2204.2 BOLTING. |
| | IF THERE ARE ANY QUESTIONS ABOUT THESE REQUIREMENTS |
| | PLEASE CONTACT KEN CONRAD CHIEF BUILDING INSPECTOR AT |
| | 561-805-6666. |
| | |
| | 4) NOTE ONLY. ROOF COVERING UNDER SEPARATE PERMIT. |
| | |
| | 5) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | JAMES A. WITMER BN, PX, SFP, CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT |
| | 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 |
| | TEL: 561-805-6717 |
| | |
| | |