Plan Review Details - Permit 20040759
Plan Review Stops For Permit 20040759
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2020-04-28 Cont ID  
Sent By jwitmer Date 2020-04-28 Time 10:01 Rev Time 0.00
Received By jwitmer Date 2020-04-28 Time 09:28 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2020-05-06 Cont ID  
Sent By jleahy Date 2020-05-06 Time 15:56 Rev Time 0.00
Received By jleahy Date 2020-05-06 Time 15:56 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2020-04-21 Cont ID  
Sent By fstal Date 2020-04-21 Time   Rev Time 0.00
Received By fstal Date 2020-04-21 Time   Sent To  
Notes
2020-04-21 17:13:31PERMIT# 20040759: DIGITAL FIRE PLAN REVIEW PASS.
  
 JOB DESCRIPTION: INSTALLATION OF CROSS CORRIDORS DOORS
 IN TRAUMA AREA TO CREATE SUITE. LOCATION: BETWEEN
 TRAUMA #3 /TG314 ,TRAUMA#2/TG13.
  
 NOTED COMMENTS; DOORS SHALL BE TIED INTO FIRE ALARM.
  
  
 ROBERT LAKE, WESTBROOKE CORPORATION 561-395-4126.
  
  
 FRANK STALLWORTH FIRE SAFETY INSPECTOR I
 WEST PALM BEACH FIRE DEPARTMENT

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-05-06 Cont ID  
Sent By jleahy Date 2020-05-06 Time 16:03 Rev Time 0.00
Received By jleahy Date 2020-04-20 Time 10:26 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2020-05-11 Cont ID  
Sent By medwards Date 2020-04-23 Time 10:09 Rev Time 0.00
Received By medwards Date 2020-05-11 Time 09:14 Sent To  
Notes
2020-05-11 09:14:30DESIGNER SENT EXISTING DRAWINGS FOR THE MECHANICAL
 SYSTEM IN THIS AREA. I CAN NOW SEE HOW THE SYSTEM WAS
 DESIGNED. NO ADDITIONAL DUCTWORK NEEDED.
2020-04-23 10:10:001ST REVIEW FBC-2017 MECHANICAL
 PERMIT-20040759
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) IT APPEARS THAT THIS PROJECT IS TAKING AN OPEN
 CORRIDOR AND INSTALLING DOORS TO CREATE A SUITE. PLEASE
 PROVIDE A COMPLETE SET OF MECHANICAL DRAWINGS SHOWING
 EXISTING CONDITIONS, DEMO CONDITIONS AND PLANNED REWORK
 OF THE MECHANICAL SYSTEM IN THIS AREA. SHOW HOW THE
 SYSTEM WILL BE PROVIDING AIR TO THE NEW SUITE. FBC FS
 107.2.1
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2020-05-06 Cont ID  
Sent By jleahy Date 2020-05-06 Time 16:03 Rev Time 0.00
Received By jleahy Date 2020-05-06 Time 16:03 Sent To  
Notes
***NONE***