Plan Review Details - Permit 20040706
Plan Review Stops For Permit 20040706
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2020-07-24 Cont ID  
Sent By shill Date 2020-07-24 Time 16:08 Rev Time 0.00
Received By shill Date 2020-07-24 Time 16:08 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2020-05-27 Cont ID  
Sent By jwitmer Date 2020-05-27 Time 10:18 Rev Time 0.00
Received By jwitmer Date 2020-05-27 Time 10:00 Sent To  
Notes
2020-05-27 10:11:04NOTE: THE PROPOSED DISTANCE, SEPARATION MEETS THE 2017
 FBC-B REQUIREMENTS OF TABLE 602.4 FOR FIRE-RESISTANCE
 RATING REQUIREMENTS FOR EXTERIOR WALLS BASED ON FIRE
 SEPARATION DISTANCE BUT THE FIRE CODES MAY HAVE A MORE
 STRINGENT REQUIREMENT. WHEN THERE IS A DIFFERENCE
 BETWEEN THE 2 CODES THE MOST STRINGENT CODE MOST BE
 MET.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2020-07-24 Cont ID  
Sent By pleduc Date 2020-07-24 Time   Rev Time 0.00
Received By pleduc Date 2020-07-24 Time 10:07 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2020-07-01 Cont ID  
Sent By pleduc Date 2020-07-01 Time   Rev Time 0.00
Received By pleduc Date 2020-07-01 Time 12:31 Sent To  
Notes
2020-07-01 12:40:17THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THE ATTACHED LETTER WAS REVIEWED; HOWEVER, THE CODE
 BELOW CLEARLY STATES "TEMPORAY OFFICES" AND IS INCLUDED
 FOR SEPARATION DISTANCE PURPOSES.
  
 THE PROPOSED SEPARATION DISTANCE OF 15' IS CLEARLY IN
 VIOLATION OF THE REQUIRED 48'.
  
 SHOULD YOU TURN THE TRAILER 180 DEGRESS SO THAT THE
 SHORT END(12') OF THE TRALER IS DIRECTLY EXPOSED TO LOT
 66 UNDER CONSTRUCTION, THE SEPARATION DISTANCE OF 15'
 WOULD BE ACCEPTABLE.
  
 PLEASE REVIEW AND MAKE CORRECTIONS.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  
  
  
 THE BELOW PREVIOUS COMMENTS ARE RESTATED BELOW:
  
  
 THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THE PROPOSED LOCATION DOES NOT MEET THE SEPARATION
 DISTANCE REQUIRED PER NFPA 241.
  
 PER NFPA 241, 4.2 TEMPORARY OFFICES AND SHEDS; TABLE
 4.2.1 SEPARATION DISTANCES, FIRE SPRINKLERS ARE
 REQUIRED IN EACH TRAILER.
  
 4.2.1* SEPARATION DISTANCES BETWEEN BUILDINGS UNDER
 CONSTRUCTION AND CONSTRUCTION-RELATED STRUCTURES, SUCH
 AS TEMPORARY OFFICES, TRAILERS, SHEDS, AND OTHER
 FACILITIES FOR THE STORAGE OF TOOLS AND MATERIALS
 HAVING COMBUSTIBLE CONSTRUCTION OR CONTENTS, SHALL BE
 IN ACCORDANCE WITH TABLE 4.2.1.
  
 1) 20 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 30 FEET
 2) 30 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 35 FEET
 3) 40 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 40 FEET
 4) 50 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 45 FEET
 5) 60 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 50 FEET
 6) GREATER THAN 60 FEET EXPOSED LENGTH SHALL BE
 SEPARATED FROM ADJACENT STRUCTURES BY AT LEAST 60 FEET
 **A 75 PERCENT REDUCTION IN SEPARATION DISTANCES SHALL
 BE PERMITTED TO BE APPLIED, PROVIDED AUTOMATIC
 SPRINKLER PROTECTION IS USED IN THE EXPOSING STRUCTURE.
  
 NOTES:
 (1) WHERE THE SEPARATION DISTANCE BETWEEN TEMPORARY
 STRUCTURES IS LESS THAN THE MINIMUM SEPARATION
 DISTANCE, THEN THE EXPOSING WALL LENGTH SHALL BE
 CONSIDERED TO BE THE SUM OF THE INDIVIDUAL EXPOSING
 WALL LENGTHS OF THE TEMPORARY STRUCTURES.
 (2) A 75 PERCENT REDUCTION IN SEPARATION DISTANCES
 SHALL BE PERMITTED TO BE APPLIED, PROVIDED AUTOMATIC
 SPRINKLER PROTECTION IS USED IN THE EXPOSING STRUCTURE.
 (3) THE SEPARATION DISTANCES APPLY TO SINGLE-LEVEL
 STRUCTURES ONLY. THIS TABLE DOES NOT APPLY TO
 MULTILEVEL, UNSPRINKLERED STRUCTURES. A LEVEL, WHERE
 APPLYING THIS TABLE, IS 3600 MM (144 IN.).
  
 4.2.2* DETACHMENT BETWEEN TEMPORARY STRUCTURES,
 ADEQUATE TEMPORARY FIXED FIRE PROTECTION SYSTEMS, AND
 PORTABLE EQUIPMENT SHALL BE PROVIDED AS REQUIRED BY THE
 AUTHORITY HAVING JURISDICTION.
  
  
 THE 56' WIDE TRALIER IS REQUIRED TO BE AT LEAST 48'.
  
 PLEASE REVIEW AND CORRECT.
  
  
 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2020-05-22 Cont ID  
Sent By pleduc Date 2020-05-22 Time   Rev Time 0.00
Received By pleduc Date 2020-05-22 Time 09:53 Sent To  
Notes
2020-05-22 10:04:24THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THE PROPOSED LOCATION DOES NOT MEET THE SEPARATION
 DISTANCE REQUIRED PER NFPA 241.
  
 PER NFPA 241, 4.2 TEMPORARY OFFICES AND SHEDS; TABLE
 4.2.1 SEPARATION DISTANCES, FIRE SPRINKLERS ARE
 REQUIRED IN EACH TRAILER.
  
 4.2.1* SEPARATION DISTANCES BETWEEN BUILDINGS UNDER
 CONSTRUCTION AND CONSTRUCTION-RELATED STRUCTURES, SUCH
 AS TEMPORARY OFFICES, TRAILERS, SHEDS, AND OTHER
 FACILITIES FOR THE STORAGE OF TOOLS AND MATERIALS
 HAVING COMBUSTIBLE CONSTRUCTION OR CONTENTS, SHALL BE
 IN ACCORDANCE WITH TABLE 4.2.1.
  
 1) 20 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 30 FEET
 2) 30 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 35 FEET
 3) 40 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 40 FEET
 4) 50 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 45 FEET
 5) 60 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 50 FEET
 6) GREATER THAN 60 FEET EXPOSED LENGTH SHALL BE
 SEPARATED FROM ADJACENT STRUCTURES BY AT LEAST 60 FEET
 **A 75 PERCENT REDUCTION IN SEPARATION DISTANCES SHALL
 BE PERMITTED TO BE APPLIED, PROVIDED AUTOMATIC
 SPRINKLER PROTECTION IS USED IN THE EXPOSING STRUCTURE.
  
 NOTES:
 (1) WHERE THE SEPARATION DISTANCE BETWEEN TEMPORARY
 STRUCTURES IS LESS THAN THE MINIMUM SEPARATION
 DISTANCE, THEN THE EXPOSING WALL LENGTH SHALL BE
 CONSIDERED TO BE THE SUM OF THE INDIVIDUAL EXPOSING
 WALL LENGTHS OF THE TEMPORARY STRUCTURES.
 (2) A 75 PERCENT REDUCTION IN SEPARATION DISTANCES
 SHALL BE PERMITTED TO BE APPLIED, PROVIDED AUTOMATIC
 SPRINKLER PROTECTION IS USED IN THE EXPOSING STRUCTURE.
 (3) THE SEPARATION DISTANCES APPLY TO SINGLE-LEVEL
 STRUCTURES ONLY. THIS TABLE DOES NOT APPLY TO
 MULTILEVEL, UNSPRINKLERED STRUCTURES. A LEVEL, WHERE
 APPLYING THIS TABLE, IS 3600 MM (144 IN.).
  
 4.2.2* DETACHMENT BETWEEN TEMPORARY STRUCTURES,
 ADEQUATE TEMPORARY FIXED FIRE PROTECTION SYSTEMS, AND
 PORTABLE EQUIPMENT SHALL BE PROVIDED AS REQUIRED BY THE
 AUTHORITY HAVING JURISDICTION.
  
  
 THE 56' WIDE TRALIER IS REQUIRED TO BE AT LEAST 48'.
  
 PLEASE REVIEW AND CORRECT.
  
  
 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2020-07-24 Cont ID  
Sent By shill Date 2020-07-24 Time 16:09 Rev Time 0.00
Received By shill Date 2020-07-23 Time 08:44 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-07-07 Cont ID  
Sent By lmarchan Date 2020-07-07 Time 14:29 Rev Time 0.00
Received By lmarchan Date 2020-06-29 Time 16:37 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-06-02 Cont ID  
Sent By lmarchan Date 2020-06-02 Time 15:15 Rev Time 0.00
Received By lmarchan Date 2020-05-21 Time 09:50 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status N Date 2020-07-24 Cont ID  
Sent By shill Date 2020-07-24 Time 16:08 Rev Time 0.00
Received By shill Date 2020-07-24 Time 16:08 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status N Date 2020-07-01 Cont ID  
Sent By shill Date 2020-07-01 Time 16:37 Rev Time 0.00
Received By shill Date 2020-07-01 Time 16:37 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 4 Status P Date 2020-07-24 Cont ID  
Sent By jroach Date 2020-07-24 Time 09:11 Rev Time 0.00
Received By jroach Date 2020-07-24 Time 09:11 Sent To  
Notes
2020-07-24 09:11:20PROVISO
  
 ALL CONSTRUCTION TRAILERS SHALL BE REMOVED WITHIN SEVEN
 DAYS OF THE FINAL CONSTRUCTION INSPECTION BY THE CITY
 AND PRIOR TO THE ISSUANCE OF A CERTIFICATE OF
 OCCUPANCY.
  
 QUESTIONS/COMMENTS, CONTACT JOHN ROACH, PRINCIPAL
 PLANNER, AT [email protected] OR (561) 822-1448.

Review Stop Z ZONING
Rev No 3 Status P Date 2020-07-10 Cont ID  
Sent By jroach Date 2020-07-10 Time 15:14 Rev Time 0.00
Received By jroach Date 2020-07-10 Time 15:14 Sent To  
Notes
2020-07-10 15:15:07PROVISO
  
 ALL CONSTRUCTION TRAILERS SHALL BE REMOVED WITHIN SEVEN
 DAYS OF THE FINAL CONSTRUCTION INSPECTION BY THE CITY
 AND PRIOR TO THE ISSUANCE OF A CERTIFICATE OF
 OCCUPANCY.
  
 QUESTIONS/COMMENTS, CONTACT JOHN ROACH, PRINCIPAL
 PLANNER, AT [email protected] OR (561) 822-1448.

Review Stop Z ZONING
Rev No 2 Status F Date 2020-07-07 Cont ID  
Sent By jroach Date 2020-07-07 Time 14:24 Rev Time 0.00
Received By jroach Date 2020-07-07 Time 14:24 Sent To  
Notes
2020-07-07 14:24:57ZONING PLAN REVIEW
 ________________________________________
  
 DATE OF REVIEW: 07.07.2020
 PERMIT NO.: 20040706
 ________________________________________
  
 REVIEW STATUS: FAILED
 ________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. [ NOT SATISFIED ] - THE PROPOSED LOCATION OF THE
 CONSTRUCTION TRAILER IS OUTSIDE OF THAT PORTION OF THE
 DEVELOPMENT THAT IS OWNED BY SOBELCO. PLEASE PROVIDE
 DOCUMENTATION INDICATING THAT THE DEVELOPER HAS
 AUTHORIZATION TO PLACE THE CONSTRUCTION TRAILER IN THE
 PROPOSED LOCATION.
 ________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN P. ROACH, AICP, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1448
 TTY: 800.955.8771
 E: [email protected]
  
 W: WPB.ORG
  

Review Stop Z ZONING
Rev No 1 Status F Date 2020-06-02 Cont ID  
Sent By jroach Date 2020-06-02 Time 14:16 Rev Time 0.00
Received By jroach Date 2020-06-02 Time 14:16 Sent To  
Notes
2020-06-02 14:16:43ZONING PLAN REVIEW
 ________________________________________
  
 DATE OF REVIEW: 05.02.2020
 PERMIT NO.: 20040706
 ________________________________________
  
 REVIEW STATUS: FAILED
 ________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. THE PROPOSED LOCATION OF THE CONSTRUCTION TRAILER IS
 OUTSIDE OF THAT PORTION OF THE DEVELOPMENT THAT IS
 OWNED BY SOBELCO. PLEASE PROVIDE DOCUMENTATION
 INDICATING THAT THE DEVELOPER HAS AUTHORIZATION TO
 PLACE THE CONSTRUCTION TRAILER IN THE PROPOSED
 LOCATION.
 ________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN P. ROACH, AICP, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1448
 TTY: 800.955.8771
 E: [email protected]
  
 W: WPB.ORG
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved