Plan Review Details - Permit 20040685
Plan Review Stops For Permit 20040685
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2020-04-20 Cont ID  
Sent By jwitmer Date 2020-04-20 Time 08:30 Rev Time 0.00
Received By jwitmer Date 2020-04-20 Time 06:31 Sent To  
Notes
2020-04-20 08:22:53REVIEW ASBESTOS COMMERCIAL. PLEASE PROVIDE A SIGNED
 ACKNOWLEDGEMENT FROM THE CONTRACTOR, ON LETTERHEAD,
 STATING THAT THE INSTRUCTIONS ON THE WEBSITE OF
 ASBESTOS PROGRAM COORDINATOR, FLORIDA DEPARTMENT OF
 HEALTH PALM BEACH COUNTY WILL BE FOLLOWED AND THAT
 NOTIFICATION WILL BE GIVEN TIMELY. ADDITIONAL
 INFORMATION REGARDING ASBESTOS REQUIREMENTS CAN BE
 FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-04-20 Cont ID  
Sent By jwitmer Date 2020-04-20 Time 08:26 Rev Time 0.00
Received By jwitmer Date 2020-04-20 Time 06:31 Sent To  
Notes
2020-04-20 08:18:402017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 20040685
 ADD: 935 25TH CT.
 CONT: BIRCH CONSTRUCTION INC.
 TEL: 561-574-9383
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION.
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MONDAY APRIL 20TH/2020
 ACTION: DENIED
  
 1) SHEET A1. IN THE TITLE BLOCK THE DESIGN PROFESSIONAL
 SANTIAGO BOLIVAR P. E. # 53326 HAS NOT SIGNED AND
 SEALED THE PLAN AT ALL. SINCE THIS IS AN ELECTRONIC /
 DIGITAL PLAN THE PLANS NEED TO COMPLY WITH FL.
 ADMINISTRATIVE CODE 61G15-23.003 PROCEDURES FOR SIGNING
 AND SEALING ELECTRONICALLY TRANSMITTED PLANS,
 SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS.
 (1) ENGINEERING WORK WHICH MUST BE SEALED UNDER THE
 PROVISIONS OF CHAPTER 471, F.S., STORED OR TRANSMITTED
 IN AN ELECTRONIC FORMAT, SHALL BE SIGNED, DATED AND
 SEALED BY THE PROFESSIONAL ENGINEER IN RESPONSIBLE
 CHARGE.
  
 2) SHEET A1 IN THE TITLEBLOCK THE ADDRESS IS INDICATED
 TO BE 935 35TH CT. THE PERMIT APPLICATION INDICATES THE
 ADDRESS TO BE 935 25TH CT. THE PBC PROPERTY APPRAISER?S
 SITE PAPA ALSO LIST THIS PCN NUMBER AS 935 25TH CT.
 DISCREPANCY IN ADDRESS PLEASE CORRECT THE ADDRESS.
 107.2.1.2. ADDITIONAL INFORMATION IS REQUIRED.
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL BE OF
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED.
 2017 FBC-B 501.2 ADDRESS IDENTIFICATION. NEW AND
 EXISTING BUILDINGS SHALL BE PROVIDED WITH APPROVED
 ADDRESS IDENTIFICATION.
  
 3) SHEET A1 THE TITLEBLOCK STATES THE SCOPE OF WORK IS
 NEW OFFICE THE PERMIT APPLICATION FOR THE DESCRIPTION
 OF WORK INDICATES INTERIOR ALTERATIONS. ON 2/06/2020
 THERE WAS A RED TAG ISSUED FOR THIS PROPERTY FOR THE
 BUILDING A MEZZANINE WITHOUT THE BENEFIT OF A PERMIT.
 THIS REVIEW WILL ALSO INCLUDE THIS VIOLATION AS PART OF
 THE REVIEW, MISSING DESIGN ELEMENTS FOR THE MEZZANINE.
 PLEASE REVIEW THE 2017 FBC-B SECTIONS:
  
 3A) 505.2 MEZZANINES. THE CLEAR HEIGHT ABOVE AND BELOW
 THE MEZZANINE FLOOR CONSTRUCTION SHALL NOT BE LESS THAN
 7 FEET.
  
 3B) PLEASE PROVIDE THE SIZE LIMITATIONS (AREA FOR 1ST
 FLOOR AND ALLOWABLE AREA OF THE MEZZANINE LEVEL) FOUND
 IN THE 2017 FBC-B SECTION:
  
 3C) 502.2.2 MEANS OF EGRESS FOR MEZZANINES SHALL COMPLY
 WITH APPLICABLE PROVISIONS OF CHAPTER 10 OF THE 2017
 FBC-B.
  
 3D) SHOW THE MEZZANINE LEVEL AND AMOUNT OF OPENNESS OF
 THE MEZZANINE LEVEL AND COMPLIANCE WITH:
 2017 FBC-B 505.2.3 OPENNESS.
  
 3E) MEZANINE LIVE LOAD FLOOR LOADS SHALL BE DESIGNED IF
 STORAGE FOR 125 PSF LIGHT AND 250 PSF HEAVY, SEE TABLE
 1607.1
 OF THE 2017 FBC-B .
  
 3F) SHEET A-1 THE JOIST LOADING INDICATES 50 PSF LIVE
 LOADS. 2017 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATIVE CODE SECTIONS:
 106.1 LIVE LOADS POSTED. WHERE THE LIVE LOADS FOR WHICH
 EACH FLOOR OR PORTION THEREOF OF A COMMERCIAL OR
 INDUSTRIAL BUILDING IS OR HAS BEEN DESIGNED TO EXCEED
 50 PSF, SUCH DESIGN LIVE LOADS SHALL BE CONSPICUOUSLY
 POSTED BY THE OWNER IN THAT PART OF EACH STORY IN WHICH
 THEY APPLY, USING DURABLE SIGNS. IT SHALL BE UNLAWFUL
 TO REMOVE OR DEFACE SUCH NOTICES?
  
 3G)106.2 ISSUANCE OF CERTIFICATE OF OCCUPANCY. A
 CERTIFICATE OF OCCUPANCY REQUIRED BY SECTION 111 SHALL
 NOT BE ISSUED UNTIL THE FLOOR LOAD SIGNS, REQUIRED BY
 SECTION 106.1, HAVE BEEN INSTALLED.
  
 3H) 106.3 RESTRICTIONS ON LOADING. IT SHALL BE UNLAWFUL
 TO PLACE, OR CAUSE OR PERMIT TO BE PLACED, ON ANY FLOOR
 OR ROOF OF A BUILDING, STRUCTURE OR PORTION THEREOF, A
 LOAD GREATER THAN IS PERMITTED BY THIS CODE.
  
 4) SHEET A1 INDICATES THE MAIN FLOOR AS LIGHT
 MANUFACTURING SPACE. THE DESIGN DATA PROVIDED DOES NOT
 INDICATE THE USAGE NOR THE OCCUPANCY CLASSIFICATION.
 PLEASE REVIEW THE 2017 FBC-B SECTIONS:
 306.2 GROUP F-1 MODERATE HAZARD FACTORY INDUSTRIAL
 306.3 GROUP F-2 LOW-HAZARD FACTORY INDUSTRIAL
  
 5) SHEET A1 DOES NOT PROVIDE THE OCCUPANT LOAD FOR THE
 MAIN FLOOR NOR FOR THE PROPOSED MEZZANINE LEVEL NOR THE
 PROPOSED USE OF THE MEZZANINE. 2017 FBC-B TABLE
 1004.1.2.
  
 6) PLEASE PROVIDE THE SQUARE FOOTAGE OF THE BUSINESS
 USE AND THE STORAGE 1ST FLOOR , AND MANUFACTURING AREA
 ON THE 1ST FLOOR TO SEE IF THE BUSINESS AREA IS OVER
 10% OF THE FLOOR AREA. THE OTHER ISSUE UNKNOWN IS THE
 OCCUPANCY TYPE TABLE 508.4 DETERMINES IF SEPARATION
 BETWEEN OCCUPANCIES IS REQUIRED, ADDITIONAL INFORMATION
 IS REQUIRED TO DETERMINE IF OCCUPANCY SEPARATION IS
 REQUIRED. IF SO THEN THE WALL, WINDOW & DOOR TO THE
 OFFICE AREA WILL NEED TO BE FIRE RATED. F2 / BUSINESS
 WOULD REQUIRE A 2 HOUR FIRE RATED WALL AND 1 ? HOUR
 PROTECTIVES, IF REQUIRED.
  
 7) PLEASE SHOW A LIFE SAFETY PLAN FOR THE MAIN FLOOR
 INCLUDING THE MEZZANINE LEVEL. 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATIVE CODE SECTION 107.3.5 MINIMUM PLAN REVIEW
 CRITERIA FOR BUILDINGS.
 107.3.5.1.1 COMMERCIAL BUILDINGS-BUILDINGS
 OCCUPANT LOADS AND EGRESS REQUIREMENTS
 OCCUPANT LOADS
 GROSS
 NET
 MEANS OF EGRESS
 STAIR CONSTRUCTION/ GEOMETRY HANDRAILS & GUARDRAILS
 CONSTRUCTION REQUIREMENTS FOR STAIRS, HANDRAILS &
 GUARDRAILS
 EMERGENCY LIGHTING AND EXIT LIGHTS.
  
 8) ADDITIONAL SQUARE FOOTAGE (MEZZANINE LEVEL) REQUIRES
 REVIEW BY PALM BEACH COUNTY IMPACT FEE OFFICE. PLANS
 WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE DIGITALLY
 VIA PROJECT DOX UPON NOTIFICATION BY THIS OFFICE.
 NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST FINAL
 FORM. YOU MAY COORDINATE WITH THE IMPACT FEE OFFICE AT
 (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL IMPACT
 FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME THE
 FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM CAN
 BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON
 APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE RECEIPT TO
 YOUR PROJECT OR EMAIL IT TO [email protected] .
 PALM BEACH COUNTY IMPACT FEE OFFICE IS LOCATED AT 2300
 N. JOG RD. ROOM?S 2W01-2W14 WEST PALM BEACH, FL.
  
 9) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE
 THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED
 DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE
 MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS
 AND INFORMATION LACKING UNDER THE PRIOR REVIEW.
  
 JAMES A. WITMER BN, PX, SFP & CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-04-29 Cont ID  
Sent By jleahy Date 2020-04-29 Time 14:23 Rev Time 0.00
Received By jleahy Date 2020-04-29 Time 14:23 Sent To  
Notes
2020-04-29 14:24:49ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
  
 NO ELECTRIC SHOWN

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2020-04-17 Cont ID  
Sent By pleduc Date 2020-04-17 Time   Rev Time 0.00
Received By pleduc Date 2020-04-17 Time 12:23 Sent To  
Notes
2020-04-17 12:44:56THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 THE PROPOSED PROJECT SHALL COMPLY WITH THE REQUIREMENTS
 OF NFPA 101 CH 40 INDUSTRIAL OCCUPANCIES40.1 GENERAL
 REQUIREMENTS.
  
 40.1.1 APPLICATION.
 40.1.1.1 THE REQUIREMENTS OF THIS CHAPTER SHALL APPLY
 TO BOTH NEW
 AND EXISTING INDUSTRIAL OCCUPANCIES.
 40.1.1.2 ADMINISTRATION. THE PROVISIONS OF CHAPTER 1,
 ADMINISTRATION, SHALL APPLY.
 40.1.1.3 GENERAL. THE PROVISIONS OF CHAPTER 4, GENERAL,
 SHALL
 APPLY.
 40.1.1.4 INDUSTRIAL OCCUPANCIES SHALL INCLUDE FACTORIES
 MAKING
 PRODUCTS OF ALL KINDS AND PROPERTIES USED FOR
 OPERATIONS SUCH AS
 PROCESSING, ASSEMBLING, MIXING, PACKAGING, FINISHING OR
 DECORATING, REPAIRING, AND SIMILAR OPERATIONS.
  
  
 1) THERE ARE NO INDICATIONS OF ILLUMINATION OF THE
 MEANS OF EGRESS
  
 40.2.8 ILLUMINATION OF MEANS OF EGRESS. MEANS OF EGRESS
 SHALL
 BE ILLUMINATED IN ACCORDANCE WITH SECTION 7.8 OR WITH
 NATURAL
 LIGHTING THAT PROVIDES THE REQUIRED LEVEL OF
 ILLUMINATION IN
 STRUCTURES OCCUPIED ONLY DURING DAYLIGHT HOURS.
  
 7.8 ILLUMINATION OF MEANS OF EGRESS.
 7.8.1 GENERAL.
 7.8.1.1* ILLUMINATION OF MEANS OF EGRESS SHALL BE
 PROVIDED IN
 ACCORDANCE WITH SECTION 7.8 FOR EVERY BUILDING AND
 STRUCTURE WHERE
 REQUIRED IN CHAPTERS 11 THROUGH 43. FOR THE PURPOSES OF
 THIS
 REQUIREMENT, EXIT ACCESS SHALL INCLUDE ONLY DESIGNATED
 STAIRS, AISLES,
 CORRIDORS, RAMPS, ESCALATORS, AND PASSAGEWAYS LEADING
 TO AN EXIT. FOR THE
 PURPOSES OF THIS REQUIREMENT, EXIT DISCHARGE SHALL
 INCLUDE ONLY
 DESIGNATED STAIRS, AISLES, CORRIDORS, RAMPS,
 ESCALATORS, WALKWAYS, AND EXIT
 PASSAGEWAYS LEADING TO A PUBLIC WAY.
 7.8.1.2 ILLUMINATION OF MEANS OF EGRESS SHALL BE
 CONTINUOUS DURING THE
 TIME THAT THE CONDITIONS OF OCCUPANCY REQUIRE THAT THE
 MEANS OF EGRESS
 BE AVAILABLE FOR USE, UNLESS OTHERWISE PROVIDED IN
 7.8.1.2.2.
 7.8.1.2.1 ARTIFICIAL LIGHTING SHALL BE EMPLOYED AT SUCH
 LOCATIONS AND FOR
 SUCH PERIODS OF TIME AS ARE NECESSARY TO MAINTAIN THE
 ILLUMINATION TO THE
 MINIMUM CRITERIA VALUES HEREIN SPECIFIED.
  
 PLEASE REVIEW AND PROVIDE
  
  
  
 2) THERE ARE NO INDICATIONS OF EMERGENCY LIGHTING.
  
 40.2.9 EMERGENCY LIGHTING
 40.2.9.1 EMERGENCY LIGHTING SHALL BE IN ACCORDANCE WITH
 SECTION 7.9
 40.2.9.2 EMERGENCY LIGHTING SHALL NOT BE REQUIRED FOR
 ANY OF THE
 FOLLOWING:
 (1) SPECIAL-PURPOSE INDUSTRIAL OCCUPANCIES WITHOUT
 ROUTINE
 HUMAN HABITATION
 (2) STRUCTURES OCCUPIED ONLY DURING DAYLIGHT HOURS,
 WITH
 SKYLIGHTS OR WINDOWS ARRANGED TO PROVIDE THE REQUIRED
 LEVEL
 OF ILLUMINATION ON ALL PORTIONS OF THE MEANS OF EGRESS
 DURING
 SUCH HOURS
  
 7.9 EMERGENCY LIGHTING.
 7.9.1 GENERAL.
 7.9.1.1* EMERGENCY LIGHTING FACILITIES FOR MEANS OF
 EGRESS SHALL BE
 PROVIDED IN ACCORDANCE WITH SECTION 7.9 FOR THE
 FOLLOWING:
 (1) BUILDINGS OR STRUCTURES WHERE REQUIRED IN CHAPTERS
 11 THROUGH 43
 (2) UNDERGROUND AND LIMITED ACCESS STRUCTURES AS
 ADDRESSED IN SECTION
 11.7
 (3) HIGH-RISE BUILDINGS AS REQUIRED BY OTHER SECTIONS
 OF THIS CODE
 (4) DOORS EQUIPPED WITH DELAYED-EGRESS LOCKS
 (5) STAIR SHAFTS AND VESTIBULES OF SMOKEPROOF
 ENCLOSURES, FOR WHICH THE
 FOLLOWING ALSO APPLY:
 (A) THE STAIR SHAFT AND VESTIBULE SHALL BE PERMITTED TO
 INCLUDE A
 STANDBY GENERATOR THAT IS INSTALLED FOR THE SMOKEPROOF
 ENCLOSURE MECHANICAL VENTILATION EQUIPMENT.
 (B) THE STANDBY GENERATOR SHALL BE PERMITTED TO BE USED
 FOR THE
 STAIR SHAFT AND VESTIBULE EMERGENCY LIGHTING POWER
 SUPPLY.
 (6) NEW ACCESS-CONTROLLED EGRESS DOORS IN ACCORDANCE
 WITH 7.2.1.6.2
  
 7.9.2 PERFORMANCE OF SYSTEM.
 7.9.2.1 EMERGENCY ILLUMINATION SHALL BE PROVIDED FOR A
 MINIMUM OF 1?
 HOURS IN THE EVENT OF FAILURE OF NORMAL LIGHTING.
 7.9.2.1.1 EMERGENCY LIGHTING FACILITIES SHALL BE
 ARRANGED TO PROVIDE
 INITIAL ILLUMINATION THAT IS NOT LESS THAN AN AVERAGE
 OF 1 FT-CANDLE (10.8
 LUX) AND, AT ANY POINT, NOT LESS THAN 0.1 FT-CANDLE
 (1.1 LUX) , MEASURED
 ALONG THE PATH OF EGRESS AT FLOOR LEVEL.
 7.9.2.1.2 ILLUMINATION LEVELS SHALL BE PERMITTED TO
 DECLINE TO NOT
 LESS THAN AN AVERAGE OF 0.6 FT-CANDLE (6.5 LUX) AND, AT
 ANY POINT,
 NOT LESS THAN 0.06 FT-CANDLE (0.65 LUX) AT THE END OF
 1? HOURS.
  
 7.9.2.3* THE EMERGENCY LIGHTING SYSTEM SHALL BE
 ARRANGED TO
 PROVIDE THE REQUIRED ILLUMINATION AUTOMATICALLY IN THE
 EVENT OF ANY
 INTERRUPTION OF NORMAL LIGHTING DUE TO ANY OF THE
 FOLLOWING:
 (1) FAILURE OF A PUBLIC UTILITY OR OTHER OUTSIDE
 ELECTRICAL POWER
 SUPPLY
 (2) OPENING OF A CIRCUIT BREAKER OR FUSE
 (3) MANUAL ACT(S), INCLUDING ACCIDENTAL OPENING OF A
 SWITCH
 CONTROLLING NORMAL LIGHTING FACILITIES
  
 7.9.2.6 EXISTING BATTERY-OPERATED EMERGENCY LIGHTS
 SHALL USE ONLY
 RELIABLE TYPES OF RECHARGEABLE BATTERIES PROVIDED WITH
 SUITABLE
 FACILITIES FOR MAINTAINING THEM IN PROPERLY CHARGED
 CONDITION.
 BATTERIES USED IN SUCH LIGHTS OR UNITS SHALL BE
 APPROVED FOR THEIR
 INTENDED USE AND SHALL COMPLY WITH NFPA 70, NATIONAL
 ELECTRICAL
 CODE.
 7.9.2.7 THE EMERGENCY LIGHTING SYSTEM SHALL BE EITHER
 CONTINUOUSLY
 IN OPERATION OR SHALL BE CAPABLE OF REPEATED AUTOMATIC
 OPERATION
 WITHOUT MANUAL INTERVENTION.
  
 PLEASE REVIEW AND PROVIDE.
  
  
  
 3) THERE IS NO INDICATION OF AN EXIT SIGN IN THE NEWLY
 CREATED SPACE AND WHEN A PERSON WOULD EXIT FROM THE NEW
 SPACE.
  
 40.2.10 MARKING OF MEANS OF EGRESS. MEANS OF EGRESS
 SHALL
 HAVE SIGNS IN ACCORDANCE WITH SECTION 7.10.
  
 7.10.1.2 EXITS.
 7.10.1.2.1* EXITS, OTHER THAN MAIN EXTERIOR EXIT DOORS
 THAT OBVIOUSLY
 AND CLEARLY ARE IDENTIFIABLE AS EXITS, SHALL BE MARKED
 BY AN APPROVED
 SIGN THAT IS READILY VISIBLE FROM ANY DIRECTION OF EXIT
 ACCESS.
 7.10.1.2.2* HORIZONTAL COMPONENTS OF THE EGRESS PATH
 WITHIN AN EXIT
 ENCLOSURE SHALL BE MARKED BY APPROVED EXIT OR
 DIRECTIONAL EXIT SIGNS
 WHERE THE CONTINUATION OF THE EGRESS PATH IS NOT
 OBVIOUS.
  
 7.10.1.5 EXIT ACCESS.
 7.10.1.5.1 ACCESS TO EXITS SHALL BE MARKED BY APPROVED,
 READILY
 VISIBLE SIGNS IN ALL CASES WHERE THE EXIT OR WAY TO
 REACH THE EXIT IS
 NOT READILY APPARENT TO THE OCCUPANTS.
 7.10.1.5.2* NEW SIGN PLACEMENT SHALL BE SUCH THAT NO
 POINT IN AN
 EXIT ACCESS CORRIDOR IS IN EXCESS OF THE RATED VIEWING
 DISTANCE OR
 100 FT (30 M), WHICHEVER IS LESS, FROM THE NEAREST
 SIGN.
  
  
  
 4) THE TITLE HEADER INDICATES AN ADDRESS OF 935 35TH
 CT.
  
 IT SHOULD READ 25TH CT.
  
 PLEASE REVIEW AND CORRECT.
  
  
  
 5) THERE APPEARS TO BE A WINDOW WITHIN THE NEW WALL.
  
 THERE IS NO WINDOW SCHEDULE, SIZE, TYPE.
  
 PLEASE REVIEW AND PROVIDE WINDOW DETAILS.
  
  
  
 6) THERE IS NO INDICATIONS OF A DOOR SCHEDULE FOR THE
 NEW DOOR.
  
 THERE IS NO INDICATION OF THE SIZE, TYPE, AND HARDWARE
 FOR THE DOOR.
  
 40.2.2.2 DOORS.
 40.2.2.2.1 DOORS COMPLYING WITH 7.2.1 SHALL BE
 PERMITTED.
  
 40.2.2.2.4 LOCKS IN ACCORDANCE WITH 7.2.1.6.3 SHALL BE
 PERMITTED
  
 7.2.1.5 LOCKS, LATCHES, AND ALARM DEVICES.
 7.2.1.5.1 DOOR LEAVES SHALL BE ARRANGED TO BE OPENED
 READILY FROM
 THE EGRESS SIDE WHENEVER THE BUILDING IS OCCUPIED.
  
 7.2.1.5.3 LOCKS, IF PROVIDED, SHALL NOT REQUIRE THE USE
 OF A KEY, A
 TOOL, OR SPECIAL KNOWLEDGE OR EFFORT FOR OPERATION FROM
 THE EGRESS
 SIDE.
  
 7.2.1.5.10* A LATCH OR OTHER FASTENING DEVICE ON A DOOR
 LEAF SHALL
 BE PROVIDED WITH A RELEASING DEVICE THAT HAS AN OBVIOUS
 METHOD OF
 OPERATION AND THAT IS READILY OPERATED UNDER ALL
 LIGHTING CONDITIONS.
 7.2.1.5.10.1 THE RELEASING MECHANISM FOR ANY LATCH
 SHALL BE
 LOCATED AS FOLLOWS:
 (1) NOT LESS THAN 34 IN. (865 MM) ABOVE THE FINISHED
 FLOOR FOR
 OTHER THAN EXISTING INSTALLATIONS
 (2) NOT MORE THAN 48 IN. (1220 MM) ABOVE THE FINISHED
 FLOOR
 7.2.1.5.10.2 THE RELEASING MECHANISM SHALL OPEN THE
 DOOR LEAF
 WITH NOT MORE THAN ONE RELEASING OPERATION, UNLESS
 OTHERWISE
 SPECIFIED IN 7.2.1.5.10.3, 7.2.1.5.10.4, OR
 7.2.1.5.10.6.
  
 PLEASE REVIEW AND PROVIDE DOOR AND HARDWARE DETAILS
 THAT COMPLY WITH NFPA 101 CH 7 MEANS OF EGRESS.
  
  
  
  
 7) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 8) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-05-18 Cont ID  
Sent By lmarchan Date 2020-05-18 Time 08:24 Rev Time 0.00
Received By lmarchan Date 2020-04-15 Time 15:29 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2020-04-20 Cont ID  
Sent By jwitmer Date 2020-04-20 Time 08:25 Rev Time 0.00
Received By jwitmer Date 2020-04-20 Time   Sent To  
Notes
2020-04-20 08:20:44IMPACT FEES - DIGITAL SUBMITTALS:
 PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECT DOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON
 APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE RECEIPT TO
 YOUR PROJECT OR EMAIL IT TO [email protected] .
 PALM BEACH COUNTY IMPACT FEE OFFICE IS LOCATED AT 2300
 N. JOG RD. ROOM?S 2W01-2W14 WEST PALM BEACH, FL.
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-06-29 Cont ID  
Sent By shill Date 2020-06-29 Time 14:23 Rev Time 0.00
Received By shill Date 2020-06-29 Time 14:23 Sent To  
Notes
2020-06-29 14:23:48SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FS471, DOCUMENTS PREPARED BY AN ENGINEER AND SUBMITTED
 FOR PUBLIC RECORD ARE TO BE SIGNED, SEALED, DATED
 ORIGINALS. A SCAN OF A SIGNED PLAN IS NOT CONSIDERED AN
 ORIGINAL.
  
 EITHER EMAIL A DIGITALLY OR ELECTRONICALLY SIGNED PLAN
 TO ME, OR YOU CAN MAIL ONE ORIGINAL SIGNED AND SEALED
 PAPER ORIGINAL WITH A WET SIGNATURE TO:
  
 SAMANTHA M. HILL
 CHIEF PLANS EXAMINER
 BUILDING DIVISION
 CITY OF WEST PALM BEACH
 401 CLEMATIS STREET, 1ST FLOOR
 WEST PALM BEACH, FL 33401
  
 FEEL FREE TO CONTACT ME IF YOU WISH TO DISCUSS,
 561-805-6724.