| 2020-05-06 14:17:06 | 1) BACKFLOW PREVENTION DEVICES ARE REQUIRED ON ALL |
| | DISHWASHERS AND ICE MAKER/WATER DISPENSER LINES ON |
| | REFRIGERATORS PER FBC-PLUMBING SEC.608.2. |
| | 2) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE NEW |
| | WATER HEATERS. WATER HEATERS SHALL HAVE AN EF RATING OF |
| | .95 PER DOE STARDANDS AS OF APRIL 15, 2015. |
| | 3) JOB SPECIFICATIONS - DIVISION 33 - UTILITIES NOTES |
| | THAT A VIDEO WILL BE DONE ON THE EXISTING SANITARY AND |
| | STORM LINES.A COPY OF THE VIDEO(S) WILL BE SUBMITTED TO |
| | THE PLUMBING INSPECTOR FOR REVIEW BY THE CHIEF PLUMBING |
| | INSPECTOR ALONG WITH A REPORT OF THE FINDINGS. WPB |
| | AMEND. TO FBC SEC. |
| | 4) INDICATE THE LEVEL OF ALTERATION ON THE PLANS PER |
| | THE FBC-EXISTING BUILDING SED. 501.1. |
| | 5) THE GROUND FLOOR UNITS WERE ORIGINALLY DESIGNED |
| | UNDER THE FEDERAL FAIR HOUSING ACCESSIBILITY GUIDELINES |
| | BUT THE ACCESSIBILITY DETAILS ON SHT. G102 APPEAR TO BE |
| | OUT OF THE FLORIDA ACCESSIBILITY CODE. THE FAIR HOUSING |
| | ACCESSIBILITY GUIDELINES TAKE PRECEDENCE IN THESE |
| | ALTERATIONS.THE DETAILS APPEAR TO APPLY TO THE DWELLING |
| | UNITS.CLARIFY.IF THESE ACCESSIBILITY DETAILS DO NOT |
| | APPLY, REMOVE THESE DETAILS FROM THE PLANS. |
| | 6) INDICATE THE DESIGN OPTION ( "A" OR "B") OF THE FHA |
| | ACCESSIBILITY GUIDELINES THESE UNITS WERE ORIGINALLY |
| | DESIGNED UNDER. WPN AMEND. TO FBC SEC. 107.2.1. |
| | 6) THERE ARE NUMEROUS DISCREPANCIES WITH THE |
| | ACCESSIBILITY DETAILS ON SHT. G102 AND THE FLORIDA |
| | ACCESSIBILITY CODE BUT THEY ARE NOT GOING TO BE NOTED |
| | IF THE DETAILS ARE GOING TO BE REMOVED FROM THE PLANS. |
| | CLARIFY. |
| | 7) SHOW THE WIDTH OF THE SHOWER IN THE ONE BED |
| | ACCESSIBLE UNIT.(SHT. A 203) .WPB AMEND. TO FBC SEC. |
| | 107.2.1. |
| | 8) A CLEAR FLOOR SPACE MEASURING 30 INCHES WIDE BY 48 |
| | INCHES DEEP FLUSH WITH THE CONTROL WALL SHALL BE |
| | PROVIDED ADJACENT TO THE NEW SHOWERS PER FIGURE 7 (A) |
| | OF THE FAIR HOUSING ACCESSIBILITY GUIDELINES. |
| | 9) THE CABINET FOR THE LAVATORY NEXT TO THE SHOWER |
| | SHALL BE A REMOVABLE CABINET. FHA ACCESSIBILITY |
| | GUIDELINES REQ. #7. |
| | 10) THE SCOPE OF WORK ON THE PLANS STATES THE THE |
| | TOILETS WILL BE REPLACED BUT THE TOILETS AND LAVATORIES |
| | ARE BEING FLIPPED IN THEIR LOCATIONS IN THE ACCESSIBLE |
| | UNITS, THE KITCHEN SINKS ARE BEING RELOCATED IN THE TWO |
| | AND THREE BED ACCESSIBLE UNITS, AND THE WASHER IS BEING |
| | RELOCATED IN THE TWO BED ACCESSIBLE UNIT. THESE CHANGES |
| | NEED TO BE NOTED ON THE PLANS.WPB AMEND. TO FBC SEC. |
| | 107.2.1. |
| | 11) THE DRAIN FOR THE RELOCATED WASHER IN THE TWO BED |
| | ACCESSIBLE UNIT SHALL BE A MINIMUM OF 3 INCHES PER |
| | FBC-PLUMBING SEC.406.2. |
| | 12) SUBMIT SANITARY AND WATER RISER DIAGRAMS FOR THE |
| | RELOCATED FIXTURES. WPB AMEND TO FBC SEC.107.3.5.1.3. |
| | 13) SHT. G102 - TRANSFER SHOWER - THE HEIGHT OF THE |
| | SHOWER CONTROLS SHALL BE LOCATED IN ACCORDANCE WITH |
| | FBC-ACCESS. SEC.608.5.1.CONTROLS SHALL BE 38-48 INCHES |
| | MAXIMUM ABOVE THE SHOWER FLOOR AND SHALL BE LOCATED ON |
| | THE CONTROL WALL 15 INCHES MAXIMUM FROM THE CENTERLINE |
| | OF THE SEAT TWARD THE SHOWER OPENING.THE DETAIL APPEARS |
| | TO SHOW 18 INCHES. CLARIFY. |
| | 14) SHT. G 102 - GRAB BARS SHALL BE INSTALLED IN A |
| | HORIZONTAL POSITION, 33 INCHES (840 MM) MINIMUM AND 36 |
| | INCHES (915 MM) MAXIMUM ABOVE THE FINISH FLOOR MEASURED |
| | TO THE TOP OF THE GRIPPING SURFACE PER FBC-ACCESS. SEC. |
| | 609.4. THE ACCESSIBILITY DETAILS APPEAR TO SHOW ALL THE |
| | GRAB BARS MEASURED TO THE CENTERLINE OF THE GRAB BARS. |
| | SEE ALSO A 203, A 204. CLARIFY. |
| | 15) G102 - THE PLANS SHOW GRAB BARS INSTALLED IN A |
| | VERTICAL POSITION. FBC-ACCESS. SEC. 609.4 REQUIRES GRAB |
| | BARS TO BE INSTALLED IN A HORIZONTAL POSITION. THERE IS |
| | NO EXCEPTION IN THE ACCESSIBILITY CODE FOR VERTICAL |
| | GRAB BARS.SEE SHT. A 203, DETAIL#9 AND SHT.A 204, |
| | DETAIL #6 ALSO.CLARIFY.CHECK ALL APPLICABLE PLANS AND |
| | DETAILS. |
| | 16) G102 - THE TRANSFER SHOWER DETAIL SHOWS A |
| | MEASUREMENT OF 3-6 INCHES. WHAT DOES THIS MEASUREMENT |
| | APPLY TO? WHAT CODE STANDARD IS THE 16 INCHES MINIMUM |
| | COMING FROM? CLARIFY ON THE PLANS. |
| | 17) G102 - TYPE "A" & "B" BATHTUB PLANS - THE LOCATION |
| | OF THE GRAB BARS SHALL COMPLY WITH FBC-ACCESS. |
| | SEC.607.4.2 OR THE FHA ACCESSIBILITY GUIDELINES, |
| | WHICHEVER IS APPLICABLE. |
| | 18) G102 - TYPE "A" & "B" BATHTUB PLANS - THE CONTROL |
| | AREA SHALL COMPLY WITH FBC-ACCESS. SEC.607.5 OR THE FHA |
| | GUIDELINES, WHICHEVER IS APPLICABLE.WHAT IS THE 3-6 |
| | INCHES MEASUREMENT FOR? CLARIFY. |
| | 19) G102 - TYPE "A" & "B" BATHTUB PLANS - BATHTUB WITH |
| | BENCH DETAIL - A GRAB BAR 24 INCHES (610 MM) LONG |
| | MINIMUM SHALL BE INSTALLED ON THE CONTROL END WALL AT |
| | THE FRONT EDGE OF THE BATHTUB.FBC -ACCESS. |
| | SEC.607.4.1.2 OR COMPLY WITH FHA GUIDELINES, WHICHEVER |
| | IS APPLICABLE. |
| | 20) G102 - SINK APPROACHES & STANDARDS DETAILS - WHAT |
| | STANDARD IS THE 29 INCHES MINIMUM HEIGHT AT THE SINK |
| | FROM? B) WHERE IS THE 19 INCHES MAXIMUM FOR THE CLEAR |
| | FLOOE SPACE UNDER THE SINK COMING FROM? THIS IS NOT IN |
| | THE FBC-ACCESS. CODE OR THE FHA GUIDELINES. CLARIFY. |
| | 21) G 102 - TOILET & APPROACHES - TYPE "B" AND PUBLIC |
| | RESTROOM DETAILS - WHERE ARE THESE DIMENSIONS AND |
| | FIGURES COMING FROM? THEY ARE NOT IN THE FBC-ACCESS. |
| | NOR DO THEY COMPLY WITH THE FIGURES IN THE FHA |
| | GUIDELINES. CLARIFY. |
| | 22) SHT. A 105 - DETAIL #5 - WHERE IS THE 3 INCH |
| | MINIMUM TOE CLEARANCE MEASUREMENT COMING FROM? THIS IS |
| | NOT IN THE FBC-ACCESS. OR FHA GUIDELINES. CLARIFY. |
| | 23) SHT. A 203 & A 205 - SHOW THE REQUIRED 30 INCHES BY |
| | 48 INCHES MINIMUM CLEAR FLOOR SPACE ADJACENT TO THE |
| | SHOWER ON THE PLANS. FHA GUIDELINES AND FBC-ACESS. SEC. |
| | 24) SUBMIT CALCULATIONS FOR THE GUTTER SIZING. GUTTERS |
| | SHALL COMPLY WITH TABLE 1106.6. THE FLOW RATE IN |
| | HORIZONTAL GUTTERS SHALL NOT EXCEED THAT SPECIFIED IN |
| | TABLE 1106.6. |
| | |
| | TIM LARGE |
| | CHIEF PLUMBING INSPECTOR |
| | PLUMBING PLAN REVIEW |