Plan Review Details - Permit 20040654
Plan Review Stops For Permit 20040654
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2021-04-16 Cont ID  
Sent By rmcphers Date 2021-04-16 Time 12:34 Rev Time 0.00
Received By rmcphers Date 2021-04-16 Time 12:34 Sent To  
Notes
2021-04-16 12:35:52UNABLE TO ADD APPROVAL STAMP AT THIS TIME

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2021-04-09 Cont ID  
Sent By rmcphers Date 2021-04-09 Time 14:22 Rev Time 0.00
Received By rmcphers Date 2021-04-09 Time 14:22 Sent To  
Notes
2021-04-09 14:30:09SFR REPAIRS/REMODEL
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) ALL DRAWINGS SEALED BY THE ARCHITECT NEED TO BE
 SIGNED BY THE ARCHITECT - SOME OF THE DRAWINGS ARE NOT
 SIGNED. FBC 107.1 - SS 481.221 (2)

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2021-03-29 Cont ID  
Sent By rmcphers Date 2021-03-29 Time 14:36 Rev Time 0.00
Received By rmcphers Date 2021-03-29 Time 14:35 Sent To  
Notes
2021-03-29 14:37:21SFR REMODEL
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 NO CHANGES SINCE THE LAST REVIEW
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) PLEASE PROVIDE A COMPLETE MIAMI DADE OR FLORIDA
 STATE PRODUCT APPROVAL FOR THE NEW EXTERIOR DOORS.
 2) BUILDING PERMIT APPLICATION SHOWS "REMOVE AND
 REPLACE FLOOR JOIST" - NEW DRAWINGS ADDED SHOW ALL
 INTERIOR WORK - PLEASE REVISE THE BUILDING PERMIT
 APPLICATION TO SHOW THE WORK DESCRIPTION AND THE JOB
 COST "VALUE" - SHOW THE TOTAL JOB COST ON THE BUILDING
 PERMIT APPLICATION. PROVIDE A SIGNED COPY OF THE
 CONTRACT TO VERIFY JOB COST.
 FBC WPB 109.3 BUILDING PERMIT VALUATIONS. IF, IN THE
 OPINION OF THE BUILDING OFFICIAL, THE CLAIMED VALUATION
 OF BUILDING, ALTERATION, STRUCTURE, ELECTRICAL, GAS,
 MECHANICAL OR PLUMBING SYSTEMS APPEARS TO BE
 UNDERESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE
 DENIED, UNLESS THE APPLICANT CAN SHOW
 DETAILED, QUANTITY ESTIMATES, AND/OR BONA FIDE SIGNED
 CONTRACTS (EXCLUDING LAND VALUE) TO MEET THE
 APPROVAL OF THE BUILDING OFFICIAL. FOR PERMITTING
 PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL
 BE TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL,
 ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH,
 RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES,
 MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING
 ONLY LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE
 LATEST PUBLISHED DATA OF NATIONAL
 CONSTRUCTION COST ANALYSIS SERVICES (MARSHALL-SWIFT,
 MEANS, ETC.), AS PUBLISHED BY INTERNATIONAL
 CODE CONGRESS. FINAL BUILDING PERMIT VALUATION SHALL BE
 SET BY THE BUILDING OFFICIAL.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2020-12-18 Cont ID  
Sent By mcphers Date 2020-12-18 Time 12:17 Rev Time 0.00
Received By rmcphers Date 2020-12-18 Time 12:17 Sent To  
Notes
2020-12-18 12:38:47NEW SFR
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) PLEASE PROVIDE A COMPLET MIAMI DADE OR FLORIDA STATE
 PRODUCT APPROVAL FOR THE NEW EXTERIOR DOORS.
 2) BUILDING PERMIT APPLICATION SHOWS "REMOVE AND
 REPALCE FLOOR JOIST" - NEW DRAWINGS ADDED SHOW ALL
 INTERIOR WORK - PLEASE REVISE THE BUILDING PERMIT
 APPLICATION TO SHOW THE WORK DESCRIPTION AND THE JOB
 COST "VALUE" - SHOW THE TOTAL JOB COST ON THE BUILDING
 PERMIT APPLICATION. PROVIDE A SIGNED COPY OF THE
 CONTRACT TO VERIFY JOB COST.
 FBC WPB 109.3 BUILDING PERMIT VALUATIONS. IF, IN THE
 OPINION OF THE BUILDING OFFICIAL, THE CLAIMED VALUATION
 OF BUILDING, ALTERATION, STRUCTURE, ELECTRICAL, GAS,
 MECHANICAL OR PLUMBING SYSTEMS APPEARS TO BE
 UNDERESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE
 DENIED, UNLESS THE APPLICANT CAN SHOW
 DETAILED, QUANTITY ESTIMATES, AND/OR BONA FIDE SIGNED
 CONTRACTS (EXCLUDING LAND VALUE) TO MEET THE
 APPROVAL OF THE BUILDING OFFICIAL. FOR PERMITTING
 PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL
 BE TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL,
 ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH,
 RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES,
 MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING
 ONLY LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE
 LATEST PUBLISHED DATA OF NATIONAL
 CONSTRUCTION COST ANALYSIS SERVICES (MARSHALL-SWIFT,
 MEANS, ETC.), AS PUBLISHED BY INTERNATIONAL
 CODE CONGRESS. FINAL BUILDING PERMIT VALUATION SHALL BE
 SET BY THE BUILDING OFFICIAL.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-04-21 Cont ID  
Sent By rmcphers Date 2020-04-21 Time 16:51 Rev Time 0.00
Received By rmcphers Date 2020-04-21 Time 15:44 Sent To  
Notes
2020-04-21 16:50:58SFR FLOOR JOIST
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) PLEASE SHOW THE ATTACHMENT (STRAPPING ETC.) OF THE
 FLOOR JOIST TO THE FOUNDATION. FBC EXISTING BUILDING
 807.4 - FBC R301.1
 2) PLEASE SHOW ALL ATTACHMENT AND STRAPPING REQUIREMENT
 DETAILS - JOIST TO FOUNDATION, FLOOR SHEATHING TO
 JOIST, BEARING WALLS TO JOIST ETC.
 3) PLEASE PROVIDE A FLOOR PLAN FOR THE RECONFIGURATION
 OF THE ROOMS (BEDROOMS, BATHROOM, KITCHEN) ALONG WITH
 WALL DETAILS, ROOM DIMENSIONS ETC.
 4) PLEASE SHOW BUILDING DIMENSIONS.
  

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2021-05-06 Cont ID  
Sent By jleahy Date 2021-05-06 Time 15:25 Rev Time 0.00
Received By jleahy Date 2021-05-06 Time 15:15 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 5 Status F Date 2021-04-22 Cont ID  
Sent By jleahy Date 2021-04-22 Time 13:37 Rev Time 0.00
Received By jleahy Date 2021-04-22 Time 13:35 Sent To  
Notes
2021-04-22 13:45:58ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 1) OUTLETS REQUIRED AT THR FRONT AND REAR OF UNIT
 210.52(E)(1)
  
 FOR A ONE-FAMILY DWELLING AND EACH UNIT OF A TWO-FAMILY
 DWELLING THAT IS AT GRADE LEVEL, AT LEAST ONE
 RECEPTACLE OUTLET READILY ACCESSIBLE FROM GRADE AND NOT
 MORE THAN 2.0 M (6 1?2 FT) ABOVE GRADE LEVEL SHALL BE
 INSTALLED AT THE FRONT AND BACK OF THE DWELLING
  
 2) SMOKE ALARMS TO BE AT LEAST 6' AWAY FROM COOKING
 APPLIANCES R314 FBC
  
 3) OUTLET SPACING DOES NOT MEET CODE 210.52(A)(1)
  
 SPACING. RECEPTACLES SHALL BE INSTALLED SUCH THAT NO
 POINT MEASURED HORIZONTALLY ALONG THE FLOOR LINE OF ANY
 WALL SPACE IS MORE THAN 1.8 M (6 FT) FROM A RECEPTACLE
 OUTLET.
 ANY SPACE 600 MM (2 FT) OR MORE IN WIDTH (INCLUDING
 SPACE MEASURED AROUND CORNERS) AND UNBROKEN ALONG THE
 FLOOR LINE BY DOORWAYS AND SIMILAR OPENINGS,
 FIREPLACES, AND FIXED CABINETS THAT DO NO
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2021-04-09 Cont ID  
Sent By jleahy Date 2021-04-09 Time 11:24 Rev Time 0.00
Received By jleahy Date 2021-04-09 Time 08:16 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2021-03-18 Cont ID  
Sent By jleahy Date 2021-03-18 Time 13:28 Rev Time 0.00
Received By jleahy Date 2021-03-18 Time 11:15 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2020-12-23 Cont ID  
Sent By jleahy Date 2020-12-23 Time 14:18 Rev Time 0.00
Received By jleahy Date 2020-12-23 Time 13:52 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-04-21 Cont ID  
Sent By jleahy Date 2020-04-21 Time 09:46 Rev Time 0.00
Received By jleahy Date 2020-04-21 Time 09:40 Sent To  
Notes
2020-04-21 09:47:18FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 NO ELECTRICAL WORK SHOWN??????

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2021-05-06 Cont ID  
Sent By jleahy Date 2021-05-06 Time 15:25 Rev Time 0.00
Received By jleahy Date 2021-05-04 Time 16:06 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2021-04-22 Cont ID  
Sent By jleahy Date 2021-04-22 Time 13:46 Rev Time 0.00
Received By jleahy Date 2021-04-14 Time 16:24 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date   Cont ID  
Sent By   Date 2021-04-13 Time   Rev Time 0.00
Received By aoliver Date 2021-04-08 Time 16:12 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2021-03-29 Cont ID  
Sent By rmcphers Date 2021-03-29 Time 14:39 Rev Time 0.00
Received By rmcphers Date 2021-03-15 Time 14:55 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-12-23 Cont ID  
Sent By jleahy Date 2020-12-23 Time 14:18 Rev Time 0.00
Received By jleahy Date 2020-12-16 Time 09:34 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-06-29 Cont ID  
Sent By shill Date 2020-06-29 Time 14:26 Rev Time 0.00
Received By shill Date 2020-04-15 Time 10:07 Sent To  
Notes
2020-04-20 10:07:17CONVERTED TO DIGITAL. JG.

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2021-04-16 Cont ID  
Sent By medwards Date 2021-04-16 Time 12:09 Rev Time 0.00
Received By medwards Date 2021-04-16 Time 12:09 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status F Date 2021-04-12 Cont ID  
Sent By medwards Date 2021-04-12 Time 13:40 Rev Time 0.00
Received By medwards Date 2021-04-12 Time 13:40 Sent To  
Notes
2021-04-12 13:41:36PLEASE ADDRESS PREVIOUS COMMENTS.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2021-03-24 Cont ID  
Sent By medwards Date 2021-03-24 Time 16:32 Rev Time 0.00
Received By medwards Date 2021-03-24 Time 16:32 Sent To  
Notes
2021-03-24 16:38:56IT APPEARS THAT THE MECHANICAL SYSTEM IS A NEW SYSTEM.
 THE MECHANICAL CONTRACTOR MUST OBTAIN A PERMIT, SUBMIT
 THE MECHANICAL EQUIPMENT SIZING CALCULATIONS AND A
 MECHANICAL DRAWING OF THE PROJECT OR A MECHANICAL
 ENGINEER MAY SUBMIT THE DOCUMENTS MENTIONED EARLIER. FS
 471.003 (H) THE ENERGY CALCULATIONS FOR THIS PROJECT
 MUST ALSO BE SUBMITTED. FBC EC 101.5.1.1.2
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2020-04-30 Cont ID  
Sent By ccole Date 2020-04-30 Time 15:18 Rev Time 0.00
Received By ccole Date 2020-04-30 Time 15:18 Sent To  
Notes
2020-04-30 15:23:55 
 1ST REVIEW FBC-2017 MECHANICAL
 PERMIT #20040654
 4/30/2020
  
 CODES IN EFFECT:
  
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET D1.01: PROVIDE A SCOPE OF WORK FOR MECHANICAL.
 SHOW THE LOCATION OF THE AC AIR HANDLER ON THE PLANS
 AND INDICATE IF IT WILL BE REMOVED AND REINSTALLED OR
 REPLACED. PLEASE INCLUDE ANY WORK INVOLVING THE
 DUCTWORK, REFRIGERANT LINES AND CONDENSATE PIPING-
 SECTION 107.2.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2020-04-21 Cont ID  
Sent By medwards Date 2020-04-21 Time 07:43 Rev Time 0.00
Received By medwards Date 2020-04-21 Time 07:32 Sent To  
Notes
2020-04-21 07:44:151ST REVIEW FBC-2017 MECHANICAL
 PERMIT-20040654
  
 CODES IN EFFECT:
  
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 SHEET D1.01 DOES NOT MENTION ANY MECHANICAL WORK IN
 THIS PROJECT. IF ANY MECHANICAL WORK IS TO BE DONE ON
 THIS PROJECT YOU WILL BE REQUIRED TO OBTAIN THE PROPER
 PERMITS BEFORE ANY WORK IS DONE. FBC FS 105.1
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 5 Status P Date 2021-04-20 Cont ID  
Sent By ccole Date 2021-04-20 Time 16:44 Rev Time 0.00
Received By ccole Date 2021-04-20 Time 16:15 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 4 Status F Date 2021-04-13 Cont ID  
Sent By ccole Date 2021-04-13 Time 10:09 Rev Time 0.00
Received By ccole Date 2021-04-13 Time 09:53 Sent To  
Notes
2021-04-13 10:13:074TH REVIEW FBC-2017 PLUMBING
 PERMIT #20040654
 4/13/2021
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET P1.01: THE PLANS DO NOT MATCH THE SCOPE OF
 WORK IN THE CONTRACT WHICH INCDICATES ALL NEW SANITARY
 DRAINAGE AND WATER DISTRIBUTION PIPING. PLEASE CORRECT
 THE PLAN- SECTION 107.2.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 3 Status F Date 2021-03-22 Cont ID  
Sent By ccole Date 2021-03-22 Time 17:09 Rev Time 0.00
Received By ccole Date 2021-03-22 Time 15:34 Sent To  
Notes
2021-03-22 17:13:242ND REVIEW FBC-2017 PLUMBING
 PERMIT #20040654
 3/22/2021
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET P1.01: PROVIDE A SANITARY RISER DRAWING-
 SECTION 107.3.5.3 WPB.
  
 2) P1.01: SHOW THE LOCATION OF THE WATER HEATER, DRAIN
 PAN LINE RUN, AND DISCHARGE LOCATION- SECTION P2801.6
 FBC RES.
  
 3) P1.01: PROVIDE A THERMAL EXPANSION TANK FOR THE
 WATER HEATER AND SHOW THE LOCATION OF THE THE TANK IN
 THE DETAIL- SECTION P2903.4 FBC RES.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2020-12-18 Cont ID  
Sent By ccole Date 2020-12-18 Time 07:53 Rev Time 0.00
Received By lcrespo Date 2020-12-18 Time 07:41 Sent To  
Notes
2020-12-18 07:53:4212/18/20 REVIEWED FOR CODE COMPLIANCE (PLUMBING)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS, OR THEIR REPRESENTATIVES
 FROM THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL,
 STATE, AND NATIONAL CODES AND STANDARDS IN EFFECT AT
 THE TIME OF PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK
 OF EVERY ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2020-04-30 Cont ID  
Sent By ccole Date 2020-04-30 Time 14:58 Rev Time 0.00
Received By ccole Date 2020-04-20 Time 16:46 Sent To  
Notes
2020-04-30 15:17:51 
 1ST REVIEW FBC-2017 PLUMBING
 PERMIT #20040654
 4/30/2020
  
 CODES IN EFFECT:
  
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET D1.01, NOTE 9: PLEASE PROVIDE A COMPLETE SCOPE
 OF WORK FOR PLUMBING WITH NOTES AND DETAILS. REMOVAL OF
 THE ENTIRE FLOOR IN THE RESIDENCE WILL REQUIRE REMOVAL
 AND REPLACEMENT OR REINSTALLATION OF THE KITCHEN AND
 BATH PLUMBING FIXTURES, APPLIANCES, WATER HEATER, AND
 MOST LIKELY RESULT IN THE CUTTING BACK OF WATER SUPPLY
 LINES AND SANITARY DRAINS. REVISE BOTH THE DEMO PLAN
 AND THE NEW WORK PLAN- SECTION 107.2.1 WPB. PLEASE NOTE
 THAT A SEPARATE PERMIT IS REQUIRED FOR REMOVAL AND
 REPLACEMENT OF ANY GAS APPLIANCES AND PIPING,
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 6 Status P Date 2021-05-05 Cont ID  
Sent By equinone Date 2021-05-05 Time 10:14 Rev Time 0.00
Received By equinone Date 2021-05-05 Time 10:14 Sent To  
Notes
2021-05-05 10:14:39ORIGINAL PAPER DRAWINGS WITH ORIGINAL SEAL AND
 SIGNATURE SUBMITTED. ROUTED TO STORAGE. EQ

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 5 Status P Date 2021-04-15 Cont ID  
Sent By equinone Date 2021-04-15 Time 10:01 Rev Time 0.00
Received By equinone Date 2021-04-15 Time 10:01 Sent To  
Notes
2021-04-15 10:02:00SIGNED AND SEALED PAPER DRAWINGS ROUTED TO STORAGE. EQ

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status F Date 2021-04-09 Cont ID  
Sent By equinone Date 2021-04-09 Time 10:42 Rev Time 0.00
Received By equinone Date 2021-04-09 Time 10:42 Sent To  
Notes
2021-04-09 11:15:44CODES IN EFFECT:
  
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2020
 7TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
  
 REVIEW STATUS: FAILED. PLEASE SEE COMMENTS BELOW:
  
 PAPER DRAWINGS SUBMITTED ARE MISSING THE ARCHITECT'S
 SIGNATURE. SEE BELOW PLEASE.
  
  
 FS471, FS481, DOCUMENTS PREPARED BY AN ARCHITECT OR
 ENGINEER AND SUBMITTED FOR PUBLIC RECORD ARE TO BE
 SIGNED, SEALED, DATED ORIGINALS. A SCAN OF A DIGITALLY
 SIGNED PLAN IS NOT CONSIDERED AN ORIGINAL, PDF MUST
 HAVE THE INTEGRATED DIGITAL SIGNATURE.
  
 EITHER SUBMIT A DIGITALLY OR ELECTRONICALLY SIGNED
 PLAN, OR YOU CAN DROP OFF PAPER ORIGINALS WITH A WET
 SEAL AND ORIGINAL SIGNATURES.
  
 ENRIQUE QUINONEZ P.E.
 ELECTRICAL PLANS EXAMINER
 DEVELOPMENT SERVICES
 CITY OF WEST PAM BEACH
 401 CLEMATIS STREET, 1ST FLOOR
 WEST PALM BEACH, FL 33401
  
 FEEL FREE TO CONTACT ME IF YOU WISH TO DISCUSS,
 561-805-6746.
  
 ROUTED TO STORAGE
  
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2021-03-24 Cont ID  
Sent By medwards Date 2021-03-24 Time 16:40 Rev Time 0.00
Received By medwards Date 2021-03-16 Time 05:45 Sent To  
Notes
2021-03-16 05:45:54ORIGINAL SIGNED AND SEALED PAPER DRAWINGS ROUTED TO
 STORAGE.ME

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status N Date 2020-12-16 Cont ID  
Sent By medwards Date 2020-12-16 Time 09:40 Rev Time 0.00
Received By medwards Date 2020-12-16 Time 09:40 Sent To  
Notes
2020-12-16 09:40:45ORIGINAL SIGNED AND SEALED PAPER PLANS ROUTED TO
 STORAGE.ME

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-04-17 Cont ID  
Sent By jgomez Date 2020-04-17 Time 12:13 Rev Time 0.00
Received By jgomez Date 2020-04-17 Time 12:13 Sent To  
Notes
2020-04-17 12:15:59CONVERTED TO DIGITAL.
 DRAWINGS/CALCULATIONS WITH ENGINEER'S ORIGINAL
 SEAL/SIGNATURE ON CITY'S FILE. JG
  
 NOTE;
 FUTURE SUBMITTALS REQUIRE ORIGINAL SIGNATURES.
 PREFERABLY DIGITAL SIGNATURE SINCE THIS PROJECT GOT
 CONVERTED TO DIGITAL AND BASED ON PLANS SUBMITTED, IT
 LOOKS LIKE ADDITIONAL INFORMATION WILL BE REQUIRED. JG.
  

Review Stop Z ZONING
Rev No 1 Status N Date 2020-06-23 Cont ID  
Sent By awooten Date 2020-06-23 Time   Rev Time  
Received By awooten Date 2020-06-23 Time   Sent To  
Notes
***NONE***