| Plan Review Stops For Permit 20040654 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
5 |
Status |
P |
Date |
2021-04-16 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2021-04-16 |
Time |
12:34 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2021-04-16 |
Time |
12:34 |
Sent To |
|
|
| Notes |
| 2021-04-16 12:35:52 | UNABLE TO ADD APPROVAL STAMP AT THIS TIME |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
F |
Date |
2021-04-09 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2021-04-09 |
Time |
14:22 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2021-04-09 |
Time |
14:22 |
Sent To |
|
|
| Notes |
| 2021-04-09 14:30:09 | SFR REPAIRS/REMODEL | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1 | | | AMENDMENTS | | | | | | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 | | | 1) ALL DRAWINGS SEALED BY THE ARCHITECT NEED TO BE | | | SIGNED BY THE ARCHITECT - SOME OF THE DRAWINGS ARE NOT | | | SIGNED. FBC 107.1 - SS 481.221 (2) |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2021-03-29 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2021-03-29 |
Time |
14:36 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2021-03-29 |
Time |
14:35 |
Sent To |
|
|
| Notes |
| 2021-03-29 14:37:21 | SFR REMODEL | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected]. | | | CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1 | | | AMENDMENTS | | | | | | NO CHANGES SINCE THE LAST REVIEW | | | | | | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 | | | 1) PLEASE PROVIDE A COMPLETE MIAMI DADE OR FLORIDA | | | STATE PRODUCT APPROVAL FOR THE NEW EXTERIOR DOORS. | | | 2) BUILDING PERMIT APPLICATION SHOWS "REMOVE AND | | | REPLACE FLOOR JOIST" - NEW DRAWINGS ADDED SHOW ALL | | | INTERIOR WORK - PLEASE REVISE THE BUILDING PERMIT | | | APPLICATION TO SHOW THE WORK DESCRIPTION AND THE JOB | | | COST "VALUE" - SHOW THE TOTAL JOB COST ON THE BUILDING | | | PERMIT APPLICATION. PROVIDE A SIGNED COPY OF THE | | | CONTRACT TO VERIFY JOB COST. | | | FBC WPB 109.3 BUILDING PERMIT VALUATIONS. IF, IN THE | | | OPINION OF THE BUILDING OFFICIAL, THE CLAIMED VALUATION | | | OF BUILDING, ALTERATION, STRUCTURE, ELECTRICAL, GAS, | | | MECHANICAL OR PLUMBING SYSTEMS APPEARS TO BE | | | UNDERESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE | | | DENIED, UNLESS THE APPLICANT CAN SHOW | | | DETAILED, QUANTITY ESTIMATES, AND/OR BONA FIDE SIGNED | | | CONTRACTS (EXCLUDING LAND VALUE) TO MEET THE | | | APPROVAL OF THE BUILDING OFFICIAL. FOR PERMITTING | | | PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL | | | BE TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL, | | | ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH, | | | RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES, | | | MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING | | | ONLY LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE | | | LATEST PUBLISHED DATA OF NATIONAL | | | CONSTRUCTION COST ANALYSIS SERVICES (MARSHALL-SWIFT, | | | MEANS, ETC.), AS PUBLISHED BY INTERNATIONAL | | | CODE CONGRESS. FINAL BUILDING PERMIT VALUATION SHALL BE | | | SET BY THE BUILDING OFFICIAL. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2020-12-18 |
|
|
Cont ID |
|
| Sent By |
mcphers |
Date |
2020-12-18 |
Time |
12:17 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2020-12-18 |
Time |
12:17 |
Sent To |
|
|
| Notes |
| 2020-12-18 12:38:47 | NEW SFR | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected]. | | | CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1 | | | AMENDMENTS | | | | | | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 | | | 1) PLEASE PROVIDE A COMPLET MIAMI DADE OR FLORIDA STATE | | | PRODUCT APPROVAL FOR THE NEW EXTERIOR DOORS. | | | 2) BUILDING PERMIT APPLICATION SHOWS "REMOVE AND | | | REPALCE FLOOR JOIST" - NEW DRAWINGS ADDED SHOW ALL | | | INTERIOR WORK - PLEASE REVISE THE BUILDING PERMIT | | | APPLICATION TO SHOW THE WORK DESCRIPTION AND THE JOB | | | COST "VALUE" - SHOW THE TOTAL JOB COST ON THE BUILDING | | | PERMIT APPLICATION. PROVIDE A SIGNED COPY OF THE | | | CONTRACT TO VERIFY JOB COST. | | | FBC WPB 109.3 BUILDING PERMIT VALUATIONS. IF, IN THE | | | OPINION OF THE BUILDING OFFICIAL, THE CLAIMED VALUATION | | | OF BUILDING, ALTERATION, STRUCTURE, ELECTRICAL, GAS, | | | MECHANICAL OR PLUMBING SYSTEMS APPEARS TO BE | | | UNDERESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE | | | DENIED, UNLESS THE APPLICANT CAN SHOW | | | DETAILED, QUANTITY ESTIMATES, AND/OR BONA FIDE SIGNED | | | CONTRACTS (EXCLUDING LAND VALUE) TO MEET THE | | | APPROVAL OF THE BUILDING OFFICIAL. FOR PERMITTING | | | PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL | | | BE TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL, | | | ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH, | | | RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES, | | | MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING | | | ONLY LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE | | | LATEST PUBLISHED DATA OF NATIONAL | | | CONSTRUCTION COST ANALYSIS SERVICES (MARSHALL-SWIFT, | | | MEANS, ETC.), AS PUBLISHED BY INTERNATIONAL | | | CODE CONGRESS. FINAL BUILDING PERMIT VALUATION SHALL BE | | | SET BY THE BUILDING OFFICIAL. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2020-04-21 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2020-04-21 |
Time |
16:51 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2020-04-21 |
Time |
15:44 |
Sent To |
|
|
| Notes |
| 2020-04-21 16:50:58 | SFR FLOOR JOIST | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected]. | | | | | | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 | | | 1) PLEASE SHOW THE ATTACHMENT (STRAPPING ETC.) OF THE | | | FLOOR JOIST TO THE FOUNDATION. FBC EXISTING BUILDING | | | 807.4 - FBC R301.1 | | | 2) PLEASE SHOW ALL ATTACHMENT AND STRAPPING REQUIREMENT | | | DETAILS - JOIST TO FOUNDATION, FLOOR SHEATHING TO | | | JOIST, BEARING WALLS TO JOIST ETC. | | | 3) PLEASE PROVIDE A FLOOR PLAN FOR THE RECONFIGURATION | | | OF THE ROOMS (BEDROOMS, BATHROOM, KITCHEN) ALONG WITH | | | WALL DETAILS, ROOM DIMENSIONS ETC. | | | 4) PLEASE SHOW BUILDING DIMENSIONS. | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
6 |
Status |
P |
Date |
2021-05-06 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2021-05-06 |
Time |
15:25 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2021-05-06 |
Time |
15:15 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
5 |
Status |
F |
Date |
2021-04-22 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2021-04-22 |
Time |
13:37 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2021-04-22 |
Time |
13:35 |
Sent To |
|
|
| Notes |
| 2021-04-22 13:45:58 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | FLORIDA BUILDING CODE 2017 6TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED | | | NFPA 70 2014 EDITION | | | | | | JAKE LEAHY BN, BU, PX | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | 1) OUTLETS REQUIRED AT THR FRONT AND REAR OF UNIT | | | 210.52(E)(1) | | | | | | FOR A ONE-FAMILY DWELLING AND EACH UNIT OF A TWO-FAMILY | | | DWELLING THAT IS AT GRADE LEVEL, AT LEAST ONE | | | RECEPTACLE OUTLET READILY ACCESSIBLE FROM GRADE AND NOT | | | MORE THAN 2.0 M (6 1?2 FT) ABOVE GRADE LEVEL SHALL BE | | | INSTALLED AT THE FRONT AND BACK OF THE DWELLING | | | | | | 2) SMOKE ALARMS TO BE AT LEAST 6' AWAY FROM COOKING | | | APPLIANCES R314 FBC | | | | | | 3) OUTLET SPACING DOES NOT MEET CODE 210.52(A)(1) | | | | | | SPACING. RECEPTACLES SHALL BE INSTALLED SUCH THAT NO | | | POINT MEASURED HORIZONTALLY ALONG THE FLOOR LINE OF ANY | | | WALL SPACE IS MORE THAN 1.8 M (6 FT) FROM A RECEPTACLE | | | OUTLET. | | | ANY SPACE 600 MM (2 FT) OR MORE IN WIDTH (INCLUDING | | | SPACE MEASURED AROUND CORNERS) AND UNBROKEN ALONG THE | | | FLOOR LINE BY DOORWAYS AND SIMILAR OPENINGS, | | | FIREPLACES, AND FIXED CABINETS THAT DO NO | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
P |
Date |
2021-04-09 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2021-04-09 |
Time |
11:24 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2021-04-09 |
Time |
08:16 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2021-03-18 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2021-03-18 |
Time |
13:28 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2021-03-18 |
Time |
11:15 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2020-12-23 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2020-12-23 |
Time |
14:18 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2020-12-23 |
Time |
13:52 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2020-04-21 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2020-04-21 |
Time |
09:46 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2020-04-21 |
Time |
09:40 |
Sent To |
|
|
| Notes |
| 2020-04-21 09:47:18 | FLORIDA BUILDING CODE 2017 6TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED | | | NFPA 70 2014 EDITION | | | | | | JAKE LEAHY BN, BU, PX | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | NO ELECTRICAL WORK SHOWN?????? |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
6 |
Status |
N |
Date |
2021-05-06 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2021-05-06 |
Time |
15:25 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2021-05-04 |
Time |
16:06 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2021-04-22 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2021-04-22 |
Time |
13:46 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2021-04-14 |
Time |
16:24 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2021-04-13 |
Time |
|
Rev Time |
0.00 |
| Received By |
aoliver |
Date |
2021-04-08 |
Time |
16:12 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2021-03-29 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2021-03-29 |
Time |
14:39 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2021-03-15 |
Time |
14:55 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2020-12-23 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2020-12-23 |
Time |
14:18 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2020-12-16 |
Time |
09:34 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2020-06-29 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2020-06-29 |
Time |
14:26 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2020-04-15 |
Time |
10:07 |
Sent To |
|
|
| Notes |
| 2020-04-20 10:07:17 | CONVERTED TO DIGITAL. JG. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
5 |
Status |
P |
Date |
2021-04-16 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2021-04-16 |
Time |
12:09 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2021-04-16 |
Time |
12:09 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
4 |
Status |
F |
Date |
2021-04-12 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2021-04-12 |
Time |
13:40 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2021-04-12 |
Time |
13:40 |
Sent To |
|
|
| Notes |
| 2021-04-12 13:41:36 | PLEASE ADDRESS PREVIOUS COMMENTS. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
F |
Date |
2021-03-24 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2021-03-24 |
Time |
16:32 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2021-03-24 |
Time |
16:32 |
Sent To |
|
|
| Notes |
| 2021-03-24 16:38:56 | IT APPEARS THAT THE MECHANICAL SYSTEM IS A NEW SYSTEM. | | | THE MECHANICAL CONTRACTOR MUST OBTAIN A PERMIT, SUBMIT | | | THE MECHANICAL EQUIPMENT SIZING CALCULATIONS AND A | | | MECHANICAL DRAWING OF THE PROJECT OR A MECHANICAL | | | ENGINEER MAY SUBMIT THE DOCUMENTS MENTIONED EARLIER. FS | | | 471.003 (H) THE ENERGY CALCULATIONS FOR THIS PROJECT | | | MUST ALSO BE SUBMITTED. FBC EC 101.5.1.1.2 | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2020-04-30 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2020-04-30 |
Time |
15:18 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2020-04-30 |
Time |
15:18 |
Sent To |
|
|
| Notes |
| 2020-04-30 15:23:55 | | | | 1ST REVIEW FBC-2017 MECHANICAL | | | PERMIT #20040654 | | | 4/30/2020 | | | | | | CODES IN EFFECT: | | | | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH | | | EDITION 2017 | | | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 | | | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION | | | 2017 | | | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 | | | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION | | | 2017 | | | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH | | | EDITION 2017 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SHEET D1.01: PROVIDE A SCOPE OF WORK FOR MECHANICAL. | | | SHOW THE LOCATION OF THE AC AIR HANDLER ON THE PLANS | | | AND INDICATE IF IT WILL BE REMOVED AND REINSTALLED OR | | | REPLACED. PLEASE INCLUDE ANY WORK INVOLVING THE | | | DUCTWORK, REFRIGERANT LINES AND CONDENSATE PIPING- | | | SECTION 107.2.1 WPB. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
N |
Date |
2020-04-21 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2020-04-21 |
Time |
07:43 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2020-04-21 |
Time |
07:32 |
Sent To |
|
|
| Notes |
| 2020-04-21 07:44:15 | 1ST REVIEW FBC-2017 MECHANICAL | | | PERMIT-20040654 | | | | | | CODES IN EFFECT: | | | | | | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION | | | 2017 | | | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION | | | 2017 | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH | | | EDITION 2017 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH | | | EDITION 2017 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | SHEET D1.01 DOES NOT MENTION ANY MECHANICAL WORK IN | | | THIS PROJECT. IF ANY MECHANICAL WORK IS TO BE DONE ON | | | THIS PROJECT YOU WILL BE REQUIRED TO OBTAIN THE PROPER | | | PERMITS BEFORE ANY WORK IS DONE. FBC FS 105.1 | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD | | | SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER | | | SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN | | | THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS | | | PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS | | | PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR | | | UPDATED. | | | | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
5 |
Status |
P |
Date |
2021-04-20 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2021-04-20 |
Time |
16:44 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2021-04-20 |
Time |
16:15 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
F |
Date |
2021-04-13 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2021-04-13 |
Time |
10:09 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2021-04-13 |
Time |
09:53 |
Sent To |
|
|
| Notes |
| 2021-04-13 10:13:07 | 4TH REVIEW FBC-2017 PLUMBING | | | PERMIT #20040654 | | | 4/13/2021 | | | | | | CODES IN EFFECT: | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH | | | EDITION 2017 | | | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 | | | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION | | | 2017 | | | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 | | | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION | | | 2017 | | | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH | | | EDITION 2017 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SHEET P1.01: THE PLANS DO NOT MATCH THE SCOPE OF | | | WORK IN THE CONTRACT WHICH INCDICATES ALL NEW SANITARY | | | DRAINAGE AND WATER DISTRIBUTION PIPING. PLEASE CORRECT | | | THE PLAN- SECTION 107.2.1 WPB. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
F |
Date |
2021-03-22 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2021-03-22 |
Time |
17:09 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2021-03-22 |
Time |
15:34 |
Sent To |
|
|
| Notes |
| 2021-03-22 17:13:24 | 2ND REVIEW FBC-2017 PLUMBING | | | PERMIT #20040654 | | | 3/22/2021 | | | | | | CODES IN EFFECT: | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH | | | EDITION 2017 | | | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 | | | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION | | | 2017 | | | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 | | | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION | | | 2017 | | | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH | | | EDITION 2017 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SHEET P1.01: PROVIDE A SANITARY RISER DRAWING- | | | SECTION 107.3.5.3 WPB. | | | | | | 2) P1.01: SHOW THE LOCATION OF THE WATER HEATER, DRAIN | | | PAN LINE RUN, AND DISCHARGE LOCATION- SECTION P2801.6 | | | FBC RES. | | | | | | 3) P1.01: PROVIDE A THERMAL EXPANSION TANK FOR THE | | | WATER HEATER AND SHOW THE LOCATION OF THE THE TANK IN | | | THE DETAIL- SECTION P2903.4 FBC RES. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2020-12-18 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2020-12-18 |
Time |
07:53 |
Rev Time |
0.00 |
| Received By |
lcrespo |
Date |
2020-12-18 |
Time |
07:41 |
Sent To |
|
|
| Notes |
| 2020-12-18 07:53:42 | 12/18/20 REVIEWED FOR CODE COMPLIANCE (PLUMBING) | | | | | | BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE | | | COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN | | | PROFESSIONAL, CONTRACTORS, OR THEIR REPRESENTATIVES | | | FROM THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, | | | STATE, AND NATIONAL CODES AND STANDARDS IN EFFECT AT | | | THE TIME OF PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK | | | OF EVERY ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM | | | REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES | | | / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO | | | AVOID VOIDING OF THE PERMIT. | | | | | | LUIS A. CRESPO | | | PLUMBING PLAN EXAMINER / INSPECTOR | | | EMAIL: [email protected] OFFICE: 561 805-6720 | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2020-04-30 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2020-04-30 |
Time |
14:58 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2020-04-20 |
Time |
16:46 |
Sent To |
|
|
| Notes |
| 2020-04-30 15:17:51 | | | | 1ST REVIEW FBC-2017 PLUMBING | | | PERMIT #20040654 | | | 4/30/2020 | | | | | | CODES IN EFFECT: | | | | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH | | | EDITION 2017 | | | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 | | | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION | | | 2017 | | | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 | | | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION | | | 2017 | | | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH | | | EDITION 2017 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SHEET D1.01, NOTE 9: PLEASE PROVIDE A COMPLETE SCOPE | | | OF WORK FOR PLUMBING WITH NOTES AND DETAILS. REMOVAL OF | | | THE ENTIRE FLOOR IN THE RESIDENCE WILL REQUIRE REMOVAL | | | AND REPLACEMENT OR REINSTALLATION OF THE KITCHEN AND | | | BATH PLUMBING FIXTURES, APPLIANCES, WATER HEATER, AND | | | MOST LIKELY RESULT IN THE CUTTING BACK OF WATER SUPPLY | | | LINES AND SANITARY DRAINS. REVISE BOTH THE DEMO PLAN | | | AND THE NEW WORK PLAN- SECTION 107.2.1 WPB. PLEASE NOTE | | | THAT A SEPARATE PERMIT IS REQUIRED FOR REMOVAL AND | | | REPLACEMENT OF ANY GAS APPLIANCES AND PIPING, | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
6 |
Status |
P |
Date |
2021-05-05 |
|
|
Cont ID |
|
| Sent By |
equinone |
Date |
2021-05-05 |
Time |
10:14 |
Rev Time |
0.00 |
| Received By |
equinone |
Date |
2021-05-05 |
Time |
10:14 |
Sent To |
|
|
| Notes |
| 2021-05-05 10:14:39 | ORIGINAL PAPER DRAWINGS WITH ORIGINAL SEAL AND | | | SIGNATURE SUBMITTED. ROUTED TO STORAGE. EQ |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
5 |
Status |
P |
Date |
2021-04-15 |
|
|
Cont ID |
|
| Sent By |
equinone |
Date |
2021-04-15 |
Time |
10:01 |
Rev Time |
0.00 |
| Received By |
equinone |
Date |
2021-04-15 |
Time |
10:01 |
Sent To |
|
|
| Notes |
| 2021-04-15 10:02:00 | SIGNED AND SEALED PAPER DRAWINGS ROUTED TO STORAGE. EQ |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
4 |
Status |
F |
Date |
2021-04-09 |
|
|
Cont ID |
|
| Sent By |
equinone |
Date |
2021-04-09 |
Time |
10:42 |
Rev Time |
0.00 |
| Received By |
equinone |
Date |
2021-04-09 |
Time |
10:42 |
Sent To |
|
|
| Notes |
| 2021-04-09 11:15:44 | CODES IN EFFECT: | | | | | | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2020 | | | 7TH ED, CHAPTER 1. | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 | | | 7TH EDITION | | | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2020 | | | 7TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION | | | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | FAC = FLORIDA ADMINISTRATIVE CODE | | | | | | | | | REVIEW STATUS: FAILED. PLEASE SEE COMMENTS BELOW: | | | | | | PAPER DRAWINGS SUBMITTED ARE MISSING THE ARCHITECT'S | | | SIGNATURE. SEE BELOW PLEASE. | | | | | | | | | FS471, FS481, DOCUMENTS PREPARED BY AN ARCHITECT OR | | | ENGINEER AND SUBMITTED FOR PUBLIC RECORD ARE TO BE | | | SIGNED, SEALED, DATED ORIGINALS. A SCAN OF A DIGITALLY | | | SIGNED PLAN IS NOT CONSIDERED AN ORIGINAL, PDF MUST | | | HAVE THE INTEGRATED DIGITAL SIGNATURE. | | | | | | EITHER SUBMIT A DIGITALLY OR ELECTRONICALLY SIGNED | | | PLAN, OR YOU CAN DROP OFF PAPER ORIGINALS WITH A WET | | | SEAL AND ORIGINAL SIGNATURES. | | | | | | ENRIQUE QUINONEZ P.E. | | | ELECTRICAL PLANS EXAMINER | | | DEVELOPMENT SERVICES | | | CITY OF WEST PAM BEACH | | | 401 CLEMATIS STREET, 1ST FLOOR | | | WEST PALM BEACH, FL 33401 | | | | | | FEEL FREE TO CONTACT ME IF YOU WISH TO DISCUSS, | | | 561-805-6746. | | | | | | ROUTED TO STORAGE | | | | | | | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
3 |
Status |
P |
Date |
2021-03-24 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2021-03-24 |
Time |
16:40 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2021-03-16 |
Time |
05:45 |
Sent To |
|
|
| Notes |
| 2021-03-16 05:45:54 | ORIGINAL SIGNED AND SEALED PAPER DRAWINGS ROUTED TO | | | STORAGE.ME |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
N |
Date |
2020-12-16 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2020-12-16 |
Time |
09:40 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2020-12-16 |
Time |
09:40 |
Sent To |
|
|
| Notes |
| 2020-12-16 09:40:45 | ORIGINAL SIGNED AND SEALED PAPER PLANS ROUTED TO | | | STORAGE.ME |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
F |
Date |
2020-04-17 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2020-04-17 |
Time |
12:13 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2020-04-17 |
Time |
12:13 |
Sent To |
|
|
| Notes |
| 2020-04-17 12:15:59 | CONVERTED TO DIGITAL. | | | DRAWINGS/CALCULATIONS WITH ENGINEER'S ORIGINAL | | | SEAL/SIGNATURE ON CITY'S FILE. JG | | | | | | NOTE; | | | FUTURE SUBMITTALS REQUIRE ORIGINAL SIGNATURES. | | | PREFERABLY DIGITAL SIGNATURE SINCE THIS PROJECT GOT | | | CONVERTED TO DIGITAL AND BASED ON PLANS SUBMITTED, IT | | | LOOKS LIKE ADDITIONAL INFORMATION WILL BE REQUIRED. JG. | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
N |
Date |
2020-06-23 |
|
|
Cont ID |
|
| Sent By |
awooten |
Date |
2020-06-23 |
Time |
|
Rev Time |
|
| Received By |
awooten |
Date |
2020-06-23 |
Time |
|
Sent To |
|
|
| Notes |
|
|