Plan Review Details - Permit 20040614
Plan Review Stops For Permit 20040614
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status N Date 2020-04-20 Cont ID  
Sent By jwitmer Date 2020-04-20 Time 08:33 Rev Time 0.00
Received By jwitmer Date 2020-04-20 Time 08:32 Sent To  
Notes
2020-04-20 08:33:00NEW HIGH RISE- NO ASBESTOS. JW

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2020-07-16 Cont ID  
Sent By jwitmer Date 2020-07-16 Time 15:15 Rev Time 0.00
Received By jwitmer Date 2020-07-16 Time 14:45 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2020-07-08 Cont ID  
Sent By jwitmer Date 2020-07-07 Time 08:15 Rev Time 0.00
Received By jwitmer Date 2020-07-07 Time 08:03 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2020-06-21 Cont ID  
Sent By jwitmer Date 2020-06-21 Time 13:18 Rev Time 0.00
Received By jwitmer Date 2020-06-21 Time 12:57 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-04-20 Cont ID  
Sent By jwitmer Date 2020-04-20 Time 09:28 Rev Time 0.00
Received By jwitmer Date 2020-04-20 Time 08:32 Sent To  
Notes
2020-04-20 09:28:272017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 20040614
 ADD: 255 EVERNIA ST. SUITE: 804
 CONT: MAJESTIC DESIGN & CONSTRUCTION CORP.
 TEL: 561-777-3875
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION.
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MONDAY APRIL 20/2020
 ACTION: DENIED
  
 1) THERE IS A PROPOSED DEMO PLAN, AN EXISTING FLOOR
 PLAN AND A PROPOSED MEP FLOOR PLAN. THERE IS NO
 PROPOSED FLOOR PLAN FOR BUILDING SHOWING THE LOCATION
 OF BATHROOM LAVS, WATERCLOSET?S. ALSO MISSING IS THE
 NEW KITCHEN CABINET CONFIGURATION, IT IS UNKNOWN IF
 THERE IS AN ISLAND CABINET AND THE DIMENSIONS BETWEEN
 ISLAND AND SURROUNDING CABINETS AND APPLIANCES. PLEASE
 NOTE THIS BUILDING WAS CONFIGURED AFTER THE FAIR
 HOUSING REQUIREMENTS TOOK PLACE. ADDITIONAL INFORMATION
 IS REQUIRED TO BE ABLE TO DETERMINE CODE COMPLIANCE.
 107.3.5.1. MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS.
 107.3.5.1.1 COMMERCIAL BUILDINGS/ BUILDING REVIEW
 BUILDING FLOOR PLAN
 FAIR HOUSING REQUIREMENTS.
  
 2) FAIR HOUSING GUIDELINES. 2014 FLORIDA ACCESSIBILITY
 CODE/ FAIR HOUSING ACCESSIBILITY GUIDELINES. SECTION 3.
 FAIR HOUSING ACT DESIGN AND CONSTRUCTION REQUIREMENTS.
 FOR PURPOSES OF THIS SECTION, A COVERED MULTIFAMILY
 DWELLING SHALL BE DEEMED TO BE DESIGNED AND CONSTRUCTED
 FOR FIRST OCCUPANCY ON OR BEFORE MARCH 13, 1991, IF
 THEY ARE OCCUPIED BY THAT DATE OR IF THE LAST BUILDING
 PERMIT OR RENEWAL THEREOF FOR THE COVERED MULTIFAMILY
 DWELLINGS IS ISSUED BY A STATE, COUNTY OR LOCAL
 GOVERNMENT ON OR BEFORE JANUARY 13, 1990.
  
 3) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE
 THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED
 DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE
 MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS
 AND INFORMATION LACKING UNDER THE PRIOR REVIEW.
  
  
 JAMES A. WITMER BN, PX, SFP & CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2020-07-01 Cont ID  
Sent By jleahy Date 2020-07-01 Time 10:11 Rev Time 0.00
Received By jleahy Date 2020-07-01 Time 08:42 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-04-30 Cont ID  
Sent By jpearson Date 2020-04-30 Time 13:33 Rev Time 0.00
Received By jpearson Date 2020-04-30 Time 09:42 Sent To  
Notes
2020-04-30 13:21:11CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE ELECTRICAL PLAN FOR REVIEW THAT IS DESIGNED
 BY AND SIGNED AND SEALED BY A LICENSED DESIGN
 PROFESSIONAL OR DESIGNED BY AND SIGNED BY THE
 ELECTRICAL CONTRACTOR QUALIFIER. FS 471.003(2)(H);
 471.025; WPB FBC 107.2.1, 107.3.5
 2. ALL BRANCH CIRCUITS THAT SUPPLY 120-VOLT,
 SINGLE-PHASE, 15- AND 20-AMPERE OUTLETS INSTALLED IN
 KITCHENS, FAMILY ROOMS, DINING ROOMS, LIVING ROOMS,
 PARLORS, LIBRARIES, DENS, BEDROOMS, SUN-ROOMS,
 RECREATIONS ROOMS, CLOSETS, HALLWAYS, LAUNDRY AREAS AND
 SIMILAR ROOMS OR AREAS SHALL BE AFCI PROTECTED. THIS
 INCLUDES LIGHTING AND POWER OUTLETS AND RECEPTACLES.
 SOME AREAS REQUIRE BOTH AFCI AND GFCI PROTECTION.
 PROVIDE CORRECTION. NEC 210.8, 210.12; FBC EX 607.1.1
 OR 801.1, 801.2, OR 901.2 AS APPLICABLE.
 3. PROVIDE GFCI PROTECTION FOR DISHWASHER. NEC 210.8(D)
 4. CONFIRM IF ANY LOAD IS BEING ADDED. IF LOAD IS BEING
 ADDED, PROVIDE ACCURATE LOAD CALCULATION FOR SERVICE,
 INCLUDE EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF
 SERVICE IS ADEQUATE. NEC 215.2, 220, 408.30
 5. PROVIDE RISER DIAGRAM OF EXISTING SERVICE TO CONFIRM
 CAPACITY. NEC 215.5; WPB FBC 107.2.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, PROVIDE A RESPONSE LETTER ADDRESSING EACH
 ITEM ALONG WITH THE CITY RESUBMITTAL FORM.
 ADDITIONALLY, INSERT CORRECTED PAGES INTO THE ORIGINAL
 SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS.
 ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD
 REMAIN IN PACKAGE AND BE MARKED OLD SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2020-07-14 Cont ID  
Sent By pleduc Date 2020-07-14 Time   Rev Time 0.00
Received By pleduc Date 2020-07-14 Time 11:36 Sent To  
Notes
2020-07-14 11:36:53THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
 1) ANY REMOVAL AND/OR CONSTRUCTION OF WALLS AND /OR
 CEILINGS REQUIRE AN EVALUATION OF THE FIRE ALARM AND/OR
 FIRE SPRINKLER SYSTEMS BY APPLICABLE LICENSED
 CONTRACTORS FOR CODE COVERAGE COMPLIANCE.
  
 2) ANY AND ALL WORK ON THE FIRE ALARM AND/OR FIRE
 SPRINKLER SYSTEMS SHALL BE DONE UNDER SEPARATE PERMITS
 AND SHOP DRAWINGS.
  
 3) THE EXISTING LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR
 FIRE SPRINKLER SHALL BE MAINTAINED AND REMAIN ACTIVE
 THROUGHOUT THE CONSTRUCTION PERIOD.
  
 PETER LEDUC
 FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 561-804-4709
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2020-06-17 Cont ID  
Sent By pleduc Date 2020-06-17 Time   Rev Time 0.00
Received By pleduc Date 2020-06-17 Time 12:51 Sent To  
Notes
2020-06-17 12:53:20THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
 1) ANY REMOVAL AND/OR CONSTRUCTION OF WALLS AND /OR
 CEILINGS REQUIRE AN EVALUATION OF THE FIRE ALARM AND/OR
 FIRE SPRINKLER SYSTEMS BY APPLICABLE LICENSED
 CONTRACTORS FOR CODE COVERAGE COMPLIANCE.
  
 2) ANY AND ALL WORK ON THE FIRE ALARM AND/OR FIRE
 SPRINKLER SYSTEMS SHALL BE DONE UNDER SEPARATE PERMITS
 AND SHOP DRAWINGS.
  
 3) THE EXISTING LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR
 FIRE SPRINKLER SHALL BE MAINTAINED AND REMAIN ACTIVE
 THROUGHOUT THE CONSTRUCTION PERIOD.
  
 PETER LEDUC
 FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 561-804-4709
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2020-04-16 Cont ID  
Sent By pleduc Date 2020-04-16 Time   Rev Time 0.00
Received By pleduc Date 2020-04-16 Time 11:58 Sent To  
Notes
2020-04-16 12:26:03THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
 1) ANY REMOVAL AND/OR CONSTRUCTION OF WALLS AND /OR
 CEILINGS REQUIRE AN EVALUATION OF THE FIRE ALARM AND/OR
 FIRE SPRINKLER SYSTEMS BY APPLICABLE LICENSED
 CONTRACTORS FOR CODE COVERAGE COMPLIANCE.
  
 2) ANY AND ALL WORK ON THE FIRE ALARM AND/OR FIRE
 SPRINKLER SYSTEMS SHALL BE DONE UNDER SEPARATE PERMITS
 AND SHOP DRAWINGS.
  
 3) THE EXISTING LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR
 FIRE SPRINKLER SHALL BE MAINTAINED AND REMAIN ACTIVE
 THROUGHOUT THE CONSTRUCTION PERIOD.
  
 PETER LEDUC
 FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2020-07-16 Cont ID  
Sent By jwitmer Date 2020-07-16 Time 15:17 Rev Time 0.00
Received By jwitmer Date 2020-07-13 Time 11:30 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2020-07-08 Time   Rev Time 0.00
Received By lmarchan Date 2020-07-06 Time 08:06 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-07-01 Cont ID  
Sent By jleahy Date 2020-07-01 Time 10:23 Rev Time 0.00
Received By jleahy Date 2020-06-16 Time 16:31 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2020-04-30 Time   Rev Time 0.00
Received By lmarchan Date 2020-04-15 Time 11:36 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 4 Status P Date 2020-07-15 Cont ID  
Sent By ccole Date 2020-07-15 Time 08:36 Rev Time 0.00
Received By ccole Date 2020-07-15 Time 08:21 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2020-07-08 Cont ID  
Sent By ccole Date 2020-07-08 Time 15:01 Rev Time 0.00
Received By ccole Date 2020-07-08 Time 14:00 Sent To  
Notes
2020-07-08 15:02:403RD REVIEW FBC-2017 PLUMBING
 PERMIT #20040614
 7/8/2020
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
 PLAN REVIEW RESULTS: DENIED.
  
 1) P1: PLEASE PROVIDE THE SCOPE OF WORK FOR THE WATER
 HEATER- LABEL IT AS EITHER NEW, EXISTING, RELOCATED-
 SECTION 107.2.1 WPB. AN EQUIPMENT SCHEDULE IS REQUIRED
 FOR NEW WATER HEATERS. THE SCHEDULE SHALL INDICATE MAKE
 AND MODEL NUMBER, GALLON SIZE, AND EFFICIENCY RATING-
 SEE TABLE C404.2 FBC EC. THE DETAIL SHOWS THE PAN DRAIN
 LINE TO DISCHARGE INTO THE NEAREST SANITARY DRAIN WHICH
 IS NOT AN APPROVED LOCATION. THIS MAY BE A TYPO AND
 THERE IS ACCESS TO THE BUILDING STORM DRAIN RISER IN
 THE CLOSET- SECTION 504.7.2 FBC P.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2020-06-22 Cont ID  
Sent By ccole Date 2020-06-22 Time 15:31 Rev Time 0.00
Received By ccole Date 2020-06-22 Time 14:14 Sent To  
Notes
2020-06-22 15:38:122ND REVIEW FBC-2017 PLUMBING
 PERMIT #20040614
 6/22//2020
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEETS A0, A1, & P1: THE REVISED PLANS SHOW BATHTUB
 TO SHOWER CONVERSIONS IN THE BATHROOMS. COMPLIANCE WITH
 THE FAIR HOUSING ACCESSIBILITY GUIDELINES IS REQUIRED.
 BECAUSE THE BUILDING WAS CONSTRUCTED IN ACCORDANCE WITH
 THE ACCESSIBILITY REQUIREMENTS OF THE FAIR HOUSING ACT
 AND THE DESIGN GUIDELINES FOR USABLE BATHROOMS IN
 DWELLING UNITS, THE ALTERATIONS THAT ARE PROPOSED IN
 THE BATHROOMS SHALL ALSO BE IN COMPLIANCE WITH THE FAIR
 HOUSING ACT. THE FAIR HOUSING ACCESSIBILITY GUIDELINES
 ARE INCLUDED IN THE FLORIDA ACCESSIBILITY CODE- 2017
 SIXTH EDITION. COMPLIANCE WITH THE GUIDELINES REQUIRES
 THAT CLEAR FLOOR SPACES FOR WHEELCHAIR APPROACHES TO
 BATH FIXTURES SHALL EITHER BE MAINTAINED AS ORIGINALLY
 DESIGNED OR PROVIDED WHERE NEW FIXTURES ARE BEING
 INSTALLED. BASED ON THE DRAWINGS IT IS NOT CLEAR IF
 USUABLE BATHROOM TYPE A OR B WAS CHOSEN AS THE ORIGINAL
 DESIGN. THE DESIGNER OF RECORD MUST INDICATE WHCH TYPE
 DESIGN WAS USED ON THE PLAN, AND THEN PROVIDE ENLARGED
 DIMENSIONED DRAWINGS OF THE BATHROOMS WITH CLEAR FLOOR
 SPACE DIAGRAMS CONFIGURED FOR THE SHOWERS. PLEASE SEE
 REQUIREMENT 7 CONTAINED IN THE GUIDELINES AND FIGURE 5,
 AND FIGURES 7A, 7C, & 7D FOR GUIDANCE. REINFORCEMENTS
 FOR FUTURE GRAB BAR AND WALL HUNG BENCH SEAT
 INSTALLATIONS ARE ALSO REQUIRED. PROVIDE DIMENSIONED
 ELEVATION VIEWS AND DETAILS SHOWING THE LOCATIONS OF
 THE WALL REINFORCEMENTS.
  
 1A) AS AN ALTERNATIVE TO MEETING THE GUIDELINES FOR THE
 BATH ALTERATIONS, THE OWNER AND DESIGNER OF RECORD FOR
 THE PROPOSED PROJECT MAY PROVIDE A SIGNED AND NOTARIZED
 AFFIDAVIT WHICH WOULD INDICATE ACKNOWLEDGEMENT THAT THE
 PROPOSED DESIGN DOES NOT MEET THE REQUIREMENTS OF THE
 FAIR HOUSING ACCESSIBILITY GUIDELINES, BUT WILL ALSO
 REQUIRE THE OWNER TO AGREE TO REVERT THE UNIT BACK TO
 COMPLIANCE AT TIME OF SALE IF SO REQUESTED BY THE
 BUYER. IF THIS OPTION IS CHOSEN, PLEASE SEND AN EMAIL
 TO [email protected] AND I WILL SEND A COPY OF THE FAIR
 HOUSING AFFIDAVIT. IF CHOOSING THIS OPTION IT WOULD BE
 ADVISABLE AT A MINIMUM TO INSTALL THE SHOWER WALL
 REINFORCEMENTS.
  
 2) SHEET P1: CONCERNING THE SHOWER DRAIN OUTLETS, SHOW
 COMPLIANCE WITH ITEMS A, B, & C LISTED BELOW.
  
 A) REFER TO SECTION 1002.1 FBC P: THE HORIZONTAL
 DISTANCE FROM THE CENTERLINE OF THE NEW SHOWER DRAIN
 OUTLET TO THE CENTERLINE OF THE INLET OF THE EXISTING
 TRAPS SHALL NOT EXCEED 30". PLEASE PLACE A NOTE ON THE
 PLAN INDICATING COMPLIANCE.
 B) RELOCATING THE SHOWER DRAIN OUTLETS WILL REQUIRE THE
 FLOOR TO BE X-RAYED TO IN ORDER TO LOCATE REINFORCING
 STEEL OR POST STRESSED FLOOR TENDONS. PLEASE PLACE A
 NOTE ON THE PLANS TO VERIFY COMPLIANCE WILL BE MET-
 SECTION 1-07.2.1 WPB.
 C) NEW DRAIN PIPE PENETRATIONS OF THE EXISTING SLAB
 WILL REQUIRE FIRESTOPPING TO SEAL THE ANNULAR SPACE
 AROUND THE PIPING. PROVIDE A UL TESTED AND APPROVED
 FIRESTOPPING ASSEMBLY DETAIL ON THE PLAN- SECTION
 714.4.1.2 FBC B.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2020-04-30 Cont ID  
Sent By ccole Date 2020-04-30 Time 14:19 Rev Time 0.00
Received By ccole Date 2020-04-30 Time 14:12 Sent To  
Notes
2020-04-30 14:39:35 
 1ST REVIEW FBC-2017 PLUMBING
 PERMIT #20040614
 4/30/2020
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE A SANITARY ISOMETRIC DRAWING FOR THE
 RELOCATED KITCHEN SINK AND DISHWASHING MACHINE- SECTION
 107.3.5.1.3 WPB AMENDMENTS TO THE FBC-17.
  
 2) PROVIDE A WATER RISER DRAWING FOR THE RELOCATED SINK
 AND DISHWASHING MACHINE- SECTION 107.3.5.1.3 WPB
 AMENDMENTS TO THE FBC-17. PLEASE NOTE THAT A WATER
 HAMMER ARRESTOR IS REQUIRED FOR THE WATER SUPPLY LINE
 TO THE DISHWASHER- SECTION 604.9 FBC P; AND THE SUPPLY
 LINE SHALL BE PROTECTED AGAINST BACKFLOW BY EITHER AN
 AIR GAP OR A BACKFLOW PREVENTER- SECTION 409.2 FBC P.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 5 Status P Date 2020-07-16 Cont ID  
Sent By jwitmer Date 2020-07-16 Time 15:17 Rev Time 0.00
Received By jwitmer Date 2020-07-16 Time 15:00 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status F Date 2020-07-15 Cont ID  
Sent By ccole Date 2020-07-15 Time 11:53 Rev Time 0.00
Received By ccole Date 2020-07-15 Time 11:53 Sent To  
Notes
2020-07-15 11:53:44THE PLANS ARE NOT ELECTRONICALLY SIGNED AND SEALED BY
 THE ARCHITECT OF RECORD- FL STATUTE 481.221 AND SECTION
 61G1-16.005 FLORIDA ADMINISTRATIVE CODE.
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status F Date 2020-07-08 Cont ID  
Sent By ccole Date 2020-07-08 Time 15:02 Rev Time 0.00
Received By ccole Date 2020-07-08 Time 15:02 Sent To  
Notes
2020-07-08 15:05:48THE PLANS ARE NOT ELECTRONICALLY SIGNED AND SEALED BY
 THE ARCHITECT OF RECORD- FL STATUTE 481.221 AND SECTION
 61G1-16.005 FLORIDA ADMINISTRATIVE CODE.
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2020-07-01 Cont ID  
Sent By jleahy Date 2020-07-01 Time 10:17 Rev Time 0.00
Received By jleahy Date 2020-07-01 Time 10:17 Sent To  
Notes
2020-07-01 10:23:06CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION,
 PART VIII ELECTRICAL
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 PAGES DOWNLOADED ON 6/16 ARE NOT DIGITALLY SIGNED.
  
 PLAN IS NOT DIGITALLY SIGNED BY THE DESIGNER OF RECORD
  
 PLAN IS REQUIRED TO BE SIGNED AND SEALED BY A DESIGN
 PROFESSIONAL OR THE ELECTRICAL CONTRACTOR QUALIFIER. FS
 471.003(2)(H); 471.025; FBC 107.2.
  
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-04-30 Cont ID  
Sent By jpearson Date 2020-04-30 Time 13:28 Rev Time 0.00
Received By jpearson Date 2020-04-30 Time 13:28 Sent To  
Notes
2020-04-30 13:24:09ELECTRICAL PLAN MUST BE DESIGNED BY AND SIGNED AND
 SEALED BY A LICENSED DESIGN PROFESSIONAL OR DESIGNED BY
 AND SIGNED BY THE ELECTRICAL CONTRACTOR QUALIFIER. THE
 GENERAL CONTRACTOR IS NOT PERMITTED TO DESIGN
 ELECTRICAL DOCUMENTS. DIGITAL PLAN REQUIRES A DIGTAL
 SIGNATURE. PROVIDE CORRECTION. FS 471.003(2)(H);
 471.025; WPB FBC 107.2.1, 107.3.5, 105.1