Plan Review Details - Permit 20040595
Plan Review Stops For Permit 20040595
Review Stop E ELECTRICAL
Rev No 3 Status P Date 2020-05-29 Cont ID  
Sent By jpearson Date 2020-05-29 Time 08:50 Rev Time 0.00
Received By jpearson Date 2020-05-29 Time 08:46 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2020-05-13 Cont ID  
Sent By jpearson Date 2020-05-13 Time 12:27 Rev Time 0.00
Received By jpearson Date 2020-05-13 Time 09:42 Sent To  
Notes
2020-05-13 12:27:08CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. CONTRACTOR NOT LICENSED FOR THIS TYPE OF WORK. PER
 FAC 61G6-7.001 SPECIALTY ELECTRICAL CONTRACTORS, THE
 FOLLOWING IS REQUIRED: (6) TWO-WAY RADIO COMMUNICATIONS
 ENHANCEMENT SYSTEMS SPECIALTY. THE SCOPE OF
 CERTIFICATION OF A TWO-WAY RADIO COMMUNICATIONS
 ENHANCEMENT SYSTEM SPECIALTY CONTRACTOR INCLUDES THE
 INSTALLATION, REPAIR, ALTERATION, ADDITION TO, TESTING,
 REPLACEMENT AND DESIGN OF ELECTRICAL WIRING, FIXTURES,
 ANTENNAE, AMPLIFIERS, APPLIANCES, APPARATUS, RACEWAYS,
 CONDUIT, OR ANY PART THEREOF, FOR TWO-WAY RADIO
 COMMUNICATIONS ENHANCEMENT SYSTEMS IN ALL STRUCTURES.
 THE SCOPE OF THIS LICENSE DOES NOT INCLUDE THE
 CONNECTION OF A SYSTEM TO A FIRE ALARM PANEL. THE SCOPE
 OF WORK OF THIS LICENSE MAY ALSO BE PERFORMED BY THE
 FOLLOWING LICENSE CATEGORIES: CERTIFIED UNLIMITED
 ELECTRICAL CONTRACTOR; CERTIFIED ALARM SYSTEM
 CONTRACTOR I; AND REGISTERED ALARM SYSTEM CONTRACTOR I.
 CONTRACTOR THAT APPLIES FOR THIS PERMIT MUST BE
 LICENSED IN ONE OF THESE CATEGORIES. FAC 61G6-7.001
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, PROVIDE A RESPONSE LETTER ADDRESSING EACH
 ITEM ALONG WITH THE CITY RESUBMITTAL FORM.
 ADDITIONALLY, INSERT CORRECTED PAGES INTO THE ORIGINAL
 SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS.
 ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD
 REMAIN IN PACKAGE AND BE MARKED OLD SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-04-17 Cont ID  
Sent By jpearson Date 2020-04-16 Time 15:28 Rev Time 0.00
Received By jpearson Date 2020-04-16 Time 13:48 Sent To  
Notes
2020-04-17 07:57:29CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. CONTRACTOR NOT LICENSED FOR THIS TYPE OF WORK. PER
 FAC 61G6-7.001 SPECIALTY ELECTRICAL CONTRACTORS, THE
 FOLLOWING IS REQUIRED: (6) TWO-WAY RADIO COMMUNICATIONS
 ENHANCEMENT SYSTEMS SPECIALTY. THE SCOPE OF
 CERTIFICATION OF A TWO-WAY RADIO COMMUNICATIONS
 ENHANCEMENT SYSTEM SPECIALTY CONTRACTOR INCLUDES THE
 INSTALLATION, REPAIR, ALTERATION, ADDITION TO, TESTING,
 REPLACEMENT AND DESIGN OF ELECTRICAL WIRING, FIXTURES,
 ANTENNAE, AMPLIFIERS, APPLIANCES, APPARATUS, RACEWAYS,
 CONDUIT, OR ANY PART THEREOF, FOR TWO-WAY RADIO
 COMMUNICATIONS ENHANCEMENT SYSTEMS IN ALL STRUCTURES.
 THE SCOPE OF THIS LICENSE DOES NOT INCLUDE THE
 CONNECTION OF A SYSTEM TO A FIRE ALARM PANEL. THE SCOPE
 OF WORK OF THIS LICENSE MAY ALSO BE PERFORMED BY THE
 FOLLOWING LICENSE CATEGORIES: CERTIFIED UNLIMITED
 ELECTRICAL CONTRACTOR; CERTIFIED ALARM SYSTEM
 CONTRACTOR I; AND REGISTERED ALARM SYSTEM CONTRACTOR I.
 CONTRACTOR THAT APPLIES FOR THIS PERMIT MUST BE
 LICENSED IN ONE OF THESE CATEGORIES. FAC 61G6-7.001
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, PROVIDE A RESPONSE LETTER ADDRESSING EACH
 ITEM ALONG WITH THE CITY RESUBMITTAL FORM.
 ADDITIONALLY, INSERT CORRECTED PAGES INTO THE ORIGINAL
 SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS.
 ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD
 REMAIN IN PACKAGE AND BE MARKED OLD SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2020-05-11 Cont ID  
Sent By pleduc Date 2020-05-11 Time   Rev Time 0.00
Received By pleduc Date 2020-05-11 Time 16:27 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2020-04-16 Cont ID  
Sent By pleduc Date 2020-04-16 Time   Rev Time 0.00
Received By pleduc Date 2020-04-16 Time 10:16 Sent To  
Notes
2020-04-16 10:28:51THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) SHEET D 2 - UNDER GENERAL NOTES # 1 THERE IS AN
 INDICATION OF THIS IS A 3 STORY ALF.
  
 PLEASE CORRECT.
  
  
  
 2) SHEET D 2 - UNDER GENERAL NOTES # 2 & ALL TITLE
 HEADERS THERE ARE INDICATIONS OF THE ADDRESS OF 360
 PEMBROKE PLACE
  
 THE ADDRESS APPEARS TO BE 351 PEMBROKE.
  
 PLEASE REVIEW AND PROVIDE THE CORRECT ADDRESS IN ALL
 PLACES.
  
  
  
 3) SHEET D 2 - UNDER GENERAL NOTES # 8 THERE IS AN
 INDICATION OF A RISER AS 2-HR SURVIVALBILTIY.
  
 HOW IS THIS PROVIDED/CONSTRUCTED AND WHERE WILL THE
 VERTICAL CABLEING BE LOCATED.
  
 PLEASE REVIEW AND PROVIDE DETAILS.
  
  
  
 4) FOR TESTING AND COMPLIANCE PURPOSES WITH PALM BEACH
 COUNTY EMERGENCY COMMUNICATIONS YOU SHALL MAKE CONTACT
 AND
 COORDINATE WITH MARK FILLA, PALM BEACH COUNTY, PUBLIC
 SAFETY RADIO SYSTEMS MANAGER, FOR ALL RADIO SIGNAL
 DETAILS, OUTBOUND
 SIGNAL STRENGTH, ANTENNA DIRECTION AND TESTING BEFORE
 THE SYSTEM GOES LIVE, AS OUR RADIOS OPERATE ON THAT
 SYSTEM.
  
 [email protected] 561-233-0837
  
 PLEASE PROVIDE A NOTE OF ACKNOWLEDGEMENT.
  
  
  
 5) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2020-05-29 Time   Rev Time 0.00
Received By lmarchan Date 2020-05-21 Time 11:22 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2020-05-13 Time   Rev Time 0.00
Received By lmarchan Date 2020-05-08 Time 09:27 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2020-04-16 Time   Rev Time 0.00
Received By lmarchan Date 2020-04-15 Time 14:49 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2020-05-13 Cont ID  
Sent By jpearson Date 2020-05-13 Time 12:26 Rev Time 0.00
Received By jpearson Date 2020-05-13 Time 12:26 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-04-16 Cont ID  
Sent By jpearson Date 2020-04-16 Time 14:15 Rev Time 0.00
Received By jpearson Date 2020-04-16 Time 14:15 Sent To  
Notes
2020-04-16 14:15:16PER THE WPB AMENDMENTS TO THE FBC, EACH SHEET OF PLAN
 IS REQUIRED TO BE SIGNED AND SEALED BY THE PERSON
 RESPONSIBLE FOR THE DESIGN. THE ENGINEER OF RECORD,
 REGINA BOBO-JACKSON, IS THE RESPONSIBLE PERSON FOR THE
 DIGITAL SIGNATURE. A DIGITAL PLAN REQUIRES A DIGITAL
 SIGNATURE WITH THE PROPER THIRD PARTY VERIFICATION.
 PROVIDE CORRECTION. WPB FBC 107.1; FS 471/481