| | 1ST REVIEW FBC-2017 RES FUEL GAS |
| | PERMIT #20040573 |
| | 5/4/2020 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| | EDITION 2017 |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) THE GENERATOR SHALL BE LOCATED A MINIMUM OF 10' FROM |
| | OPERABLE OPENINGS INTO THE BUILDING. REFER TO FIGURE |
| | 3-1 ATTACHED WITH THE GENERATOR SPECS- SECTION 107.2.1 |
| | WPB, AND SECTION R303.5.1 FBC RES. PLEASE CORRECT THE |
| | NOTES ON THE SURVEY. |
| | |
| | 2) PROVIDE CONSTRUCTION DETAILS FOR INSTALLATION OF THE |
| | GENERATOR MOUNTING PAD, AND SHOW HOW THE GENERATOR WILL |
| | BE ANCHORED TO THE PAD TO RESIST LATERAL AND UPLIFT |
| | WIND PRESSURES- SECTION G2404.6 FBC RES. |
| | |
| | 3) GAS RISER: |
| | A) SHOW THE TYPE AND SIZE OF PIPING FROM THE METER TO |
| | THE UNDERGROUND PE- TOTAL LENGTH OF THE RUN AND SIZING |
| | TABLE USED- G2413.3 FBC RES. |
| | B) SHOW THE TOTAL DEVELOPED LENGTH OF THE ENTIRE PIPING |
| | SYSTEM RUN FROM THE METER TO THE GENERATOR- G2413.4.1 & |
| | G2413.4.2 FBC RES. |
| | C) THE PVC COATED PIPE RISER IS NOT AN ALLOWABLE |
| | MATERIAL TO BE USED IN THE SYSTEM- SECTION G2414.6 FBC |
| | RES. |
| | D) SHOW THE REQUIRED LISTED SHUTOFF VALVE TO BE |
| | INSTALLED IMMEDIATELY AHEAD OF THE REGULATOR- SECTION |
| | G2420.4 FBC RES. PLEASE NOTE THAT IF THE PE IS |
| | CONNECTING TO RIGID PIPING AT THE REGULATOR, A UNION |
| | SHALL BE INSTALLED WITHIN ONE FOOT OF EITHER SIDE OF |
| | THE MP REGULATOR- SECTION G2421.2. |
| | E) PLEASE INDICATE THE MAKE AND MODEL NUMBER OF THE |
| | REGULATOR ON THE RISER- G2421.1 & G2421.2 FBC RES. |
| | INDICATE VENTED OR NON-VENTED TYPE- SECTION G2421.3. |
| | SHOW THE INLET AND OUTLET PRESSURE ON THE RISER |
| | F) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE FLEX |
| | HOSE- SECTION G2422.1.2 FBC RES. |
| | G) SHOW LOCATION OF SEDIMENT TRAP- SECTION G2419.3 |
| | H) INDICATE A TRACER WILL BE INSTALLED FOR THE |
| | UNDERGOUND PE- SECTION G2415.17.3 FBC RES. |
| | I) THE CONTRACTOR OR QUALIFIER WHO PREPARED THE RISER |
| | DRAWING SHALL PROVIDE HIS/HER SIGNATURE AND LICENSE |
| | NUMBER ON THE DRAWING- SECTION 107.2.1 WPB. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |