Plan Review Details - Permit 20040509
Plan Review Stops For Permit 20040509
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2020-06-03 Cont ID  
Sent By jwitmer Date 2020-06-03 Time 10:15 Rev Time 0.00
Received By jwitmer Date 2020-06-03 Time 09:34 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-04-14 Cont ID  
Sent By jwitmer Date 2020-04-14 Time 16:58 Rev Time 0.00
Received By jwitmer Date 2020-04-14 Time 15:18 Sent To  
Notes
2020-04-14 16:45:092017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 20040509
 ADD: 1841 PALM BEACH LAKES BLVD.
 CONT: CORE STATES CONSTRUCTION SERVICES, INC.
 TEL: 561-206-0226
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION.
  
  
 1ST REVIEW
 DATE: TUES. APRIL 14TH/ 2020
 ACTION: DENIED
 1) THE PERMIT APPLICATION UNDER THE DESCRIPTION OF WORK
 STATES KIOSK CANOPY FOR EXTERIOR DRIVE THROUGH ATM. THE
 PERMIT DESCRIPTION STATES THE PERMIT IS FOR THE KIOSK
 CANOPY BUT NOT FOR THE ATM MACHINE. EITHER THE PERMIT
 WILL BE FOR BOTH OR 2 SEPARATE PERMITS WILL NEED TO BE
 APPLIED FOR BEFORE THIS PERMIT CAN BE ISSUED.
 2017 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATIVE CODE. 107.2.1.2
 ADDITIONAL INFORMATION IS REQUIRED.
  
 2) THE VALUE OF THE WORK IS EXTREMELY LOW FOR THIS
 PERMIT EVEN IF THIS PERMIT IS FOR THE ATM CANOPY.
 108.3* BUILDING PERMIT VALUATION.
 IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE
 CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE,
 ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS
 APPEARS TO BE UNDER ESTIMATED ON THE APPLICATION, THE
 PERMIT SHALL BE DENIED. FOR PERMITTING PURPOSES,
 VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL
 REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND
 SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE
 STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR
 FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR
 BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING
 COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC.) WITH REGIONAL ADJUSTMENTS
 FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE
 CONGRESS.
  
 3)NOTE! PLEASE ALSO NOTE THERE IS A SECOND PERMIT
 20010087 THAT IS APPLIED FOR, FOR THE ATM CANOPY
 SURROUND. TWO PERMITS CANNOT BE ISSUED FOR THE SAME
 WORK. AT THIS TIME PERMIT 20010087 HAS ONLY GONE
 THROUGH ONE ROUND OF COMMENTS.
  
  
 4) SHEET S5.2 DOES NOT INDICATE IN THE TITLEBLOCK WHO
 IT BELONGS TO. THE TITLEBLOCK HAS THE NAME ATLAS
 BRANDING THE WORLD. IF THIS IS FROM AN ARCHITECTURAL
 FIRM PLEASE SHOW COMPLIANCE FOR ARCHITECTS: FLORIDA
 ADMINISTRATIVE CODE 61G1-16.005. PROCEDURES FOR
 DIGITALLY SIGNING AND SEALING AND FOR ELECTRONICALLY
 TRANSMITTING PLANS, SPECIFICATIONS, REPORTS OR OTHER
 DOCUMENTS.
  
 5) THERE IS ALSO ISSUES WITH THE 7 SHEETS FROM ATLAS
 WITH THEODORE M MCANLIS P. E. ONLY THE TOP SHEET SHOWS
 AN ELECTRONIC SIGNATURE. THERE IS NO 2ND PERSON
 VERIFICATION TO THIS SIGNATURE. 61G15-23.003 PROCEDURES
 FOR SIGNING AND SEALING ELECTRONICALLY TRANSMITTED
 PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS.
  
 6) THE 7 SHEETS OF ENGINEERED DRAWINGS IT APPEARS AS
 STATED FOR FABRICATION ONLY, NOT TO BE USED FOR
 PERMITTING. THEY ALSO NOTE THAT THEY ARE FOR SIGNAGE,
 WHICH IS NOT COVERED UNDER THIS PERMIT. SEPARATE
 PERMITS ARE REQUIRED FOR SIGNAGE AND ELECTRICAL FOR THE
 SIGN. 105.1 PERMITS REQUIRED.
  
 7) SHEET 2 OF 7 SHOWS A STEEL POLE GOING THROUGH THE
 CENTER OF THE END WALL AND SECTION CUTS A AND B. PLEASE
 PROVIDE A STRUCTURAL SHEET SHOWING HOW THE MAIN WIND
 FORCE RESISTING SYSTEM WORKS AND HOW THE MWFRS IS TO BE
 ANCHORED TO THE FOUNDATION.
  
 8) A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN
 SINCE THERE WAS A GREAT DEFICIENCY IN PLANS AND
 REQUIRED DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE
 THERE MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW
 PLANS AND INFORMATION LACKING UNDER THE PRIOR REVIEW.
  
 9) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING , THE SHEET OR SPECIFICATION PAGE
 WHERE THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE
 YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 JAMES A. WITMER BN, PX, SFP & CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST
 PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2020-06-16 Cont ID  
Sent By jleahy Date 2020-06-16 Time 15:50 Rev Time 0.00
Received By jleahy Date 2020-06-16 Time 15:50 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2020-06-10 Cont ID  
Sent By jleahy Date 2020-06-10 Time 15:43 Rev Time 0.00
Received By jleahy Date 2020-06-10 Time 15:35 Sent To  
Notes
2020-06-10 15:50:57CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION,
 PART VIII ELECTRICAL
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 1) I SEE THE 20A CIRCUIT FEEDING THE ATM, BUT NOT THE
 POWER.
  
 WHERE MORE THAN ONE BRANCH CIRCUIT OR FEEDER FEEDS A
 STRUCTURE A PANEL SHALL BE INSTALLED AND THE BRANCH
 CIRCUITS SHALL BE FED OF SAID PANEL.
  
 225.30 NUMBER OF SUPPLIES A BUILDING OR O THER
 STRUCTURE THAT IS SERVED BY A BRANCH CIRCUIT OR FEEDER
 ON THE LOAD SIDE OF A SERVICE DISCONNECTING MEANS SHALL
 BE SUPPLIED BY ONLY ONE FEEDER OR BRANCH CIRCUIT UNLESS
 PERMITTED IN 225.30(A) THROUGH (E). FOR THE PURPOSE OF
 THIS SECTION, A MULTIWIRE BRANCH CIRCUIT SHALL BE
 CONSIDERED A SINGLE CIRCUIT.
  
 2) FOR SEPARATE STRUCTURE A GROUNDING ELECTRODE SYSTEM
 SHALL BE INSTALLED. 250.32
  
 250.32 BUILDINGS OR STRUCTURES SUPPLIED BY A FEEDER(S)
 OR BRANCH CIRCUIT(S) (A) GROUNDING ELECTRODE.
 BUILDING(S) OR STRUCTURE(S) SUPPLIED BY FEEDER(S) OR
 BRANCH CIRCUIT(S) SHALL HAVE A GROUNDING ELECTRODE OR
 GROUNDING ELECTRODE SYSTEM INSTALLED IN ACCORDANCE WI
 TH PART III OF ARTICLE 250. THE GROUNDING ELECTRODE
 CONDUCTOR(S) SHALL BE CON NECTED IN ACCORDANCE WITH
 250.32(B) OR (C). WHERE THERE IS NO EXISTING GROUNDING
 ELECTRODE, THE GROUNDING ELECTRODE(S) REQUIRED IN
 250.50 SHALL BE INSTALLED
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-04-27 Cont ID  
Sent By jleahy Date 2020-04-27 Time 14:12 Rev Time 0.00
Received By jleahy Date 2020-04-27 Time 14:00 Sent To  
Notes
2020-04-27 14:14:57ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 1) NO ELECTRIC SHOWN
  
 2) SHOW WHERE CIRCUIT COMES FROM AND SYSTEM GROUNDING
 AND DISCONNECT FOR SEPARATE STRUCTURE. 215.5, 225.30

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2020-07-06 Cont ID  
Sent By shill Date 2020-07-06 Time 14:40 Rev Time 0.00
Received By shill Date 2020-06-26 Time 08:30 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-06-23 Cont ID  
Sent By lmarchan Date 2020-06-23 Time 16:10 Rev Time 0.00
Received By lmarchan Date 2020-05-27 Time 11:35 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-05-15 Cont ID  
Sent By cthroop Date 2020-05-15 Time 09:36 Rev Time 0.00
Received By cthroop Date 2020-04-13 Time 15:35 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2020-07-14 Cont ID  
Sent By cthroop Date 2020-07-14 Time 16:36 Rev Time 0.00
Received By cthroop Date 2020-07-14 Time 16:36 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-05-15 Cont ID  
Sent By cthroop Date 2020-05-15 Time 09:35 Rev Time 0.00
Received By cthroop Date 2020-05-13 Time 15:45 Sent To  
Notes
2020-05-15 09:36:07SPOKE WITH ENGINEER. WILL UPLOAD DIGITAL PLANS WITH SIG
 AND SEAL UPON RE-SUBMITTAL. CT
2020-04-13 15:35:32**DIGITALLY SIGNED SHOP DRAWINGS MOVED TO SIGNATURES
 FOLDER**

Review Stop Z ZONING
Rev No 3 Status P Date 2020-07-01 Cont ID  
Sent By eschneid Date 2020-07-01 Time 09:00 Rev Time 0.25
Received By eschneid Date 2020-07-01 Time 08:58 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2020-06-23 Cont ID  
Sent By eschneid Date 2020-06-23 Time 15:55 Rev Time 0.25
Received By eschneid Date 2020-06-23 Time 15:55 Sent To  
Notes
2020-06-23 15:56:59FAILED
  
 1) PROVIDE TWO COPIES OF A SURVEY/SITE PLAN SHOWING THE
 LOCATION OF THE PROPOSED ATM SURROUND STRUCTURE.
  
 THIS COUNTS AS THE FIRST REVIEW OF PERMIT.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.
 [email protected]
  
  
  

Review Stop Z ZONING
Rev No 1 Status F Date 2020-04-15 Cont ID  
Sent By eschneid Date 2020-04-15 Time 11:21 Rev Time 0.25
Received By eschneid Date 2020-04-15 Time 10:38 Sent To  
Notes
2020-04-15 11:20:49FAILED
  
 1) THE PALM BEACH OUTLETS MANAGEMENT APPROVAL IS
 REQUIRED. THIS MAY EITHER BE PROVIDED AS STAMPS ON THE
 PLANS OR AS A SEPARATE LETTER THAT REFERENCES THE PLANS
 SUBMITTED WITH THE PERMIT.
  
 2) PLEASE CLARIFY THE DIFFERENCE BETWEEN THIS PERMIT
 AND PERMIT NO. 20010087 COM-MISC TO INSTALL ATM
 SURROUND SUBMITTED IN JANUARY, WHICH STILL HAS
 OUTSTANDING COMMENTS THAT NEED TO BE ADDRESSED. UNTIL
 THIS PERMIT OVERLAP(?) IS CORRECTED, ZONING STAFF WILL
 NOT REVIEW THIS PERMIT.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
 [email protected]