Plan Review Details - Permit 20040506
Plan Review Stops For Permit 20040506
Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2020-12-11 Cont ID  
Sent By pleduc Date 2020-12-11 Time   Rev Time 0.00
Received By pleduc Date 2020-12-11 Time 16:30 Sent To  
Notes
2020-12-11 16:37:28FIRE PROVISO:
  
 PROVIDE LISTED FIRE RATED WALL PENETRATION
 PROTECTION AS APPLICABLE
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2020-08-25 Time   Rev Time 0.00
Received By lmarchan Date 2020-08-24 Time 13:52 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2020-08-04 Time   Rev Time 0.00
Received By lmarchan Date 2020-07-27 Time 09:45 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2020-04-20 Time   Rev Time 0.00
Received By lmarchan Date 2020-04-16 Time 09:25 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2020-08-03 Cont ID  
Sent By medwards Date 2020-08-03 Time 07:51 Rev Time 0.00
Received By medwards Date 2020-08-03 Time 07:02 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2020-04-17 Cont ID  
Sent By medwards Date 2020-04-17 Time 08:57 Rev Time 0.00
Received By medwards Date 2020-04-17 Time 07:35 Sent To  
Notes
2020-04-17 08:58:091ST REVIEW FBC-2017 MECHANICAL
 PERMIT
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 PLEASE SUBMIT A COMPLETE PACKAGE FOR THIS REVIEW. THERE
 ARE NOTES ON SHEET P5.03 THAT REFERENCE THE MECHANICAL
 SHEETS AND ?REFER TO PLANS FOR SIZES ?ROUTE PIPING FULL
 SIZE, REDUCED AT EQUIPMENT CONNECTION? PROVIDE PIPE
 MATERIAL RATED FOR THE SYSTEM, INFORMATION ON APPROVED
 FITTINGS AND VALVES FOR THE FUEL TYPE, PIPING DETAIL
 DRAWING INCLUDING ALL SUPPORTS, FUEL OIL VALVES FOR THE
 GENERATOR. PLEASE PROVIDE EXHAUST AND VENTING DETAILS
 FOR THE GENERATOR AND GENERATOR ROOM. PLEASE REFER TO
 FBC M CHAPTER 13 FOR FUEL OIL PIPING. FBC FS 107.2.1
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2020-08-25 Cont ID  
Sent By ccole Date 2020-08-25 Time 17:31 Rev Time 0.00
Received By ccole Date 2020-08-25 Time 16:58 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2020-08-04 Cont ID  
Sent By ccole Date 2020-08-04 Time 10:14 Rev Time 0.00
Received By ccole Date 2020-08-04 Time 08:51 Sent To  
Notes
2020-08-04 10:15:52 
 2ND REVIEW FBC-2017 PLUMBING
 PERMIT #20040506
 4/20/2020
  
 CODES IN EFFECT:
  
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
 NFPA 30
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE REVISED SHEET P5.03 IS NOT ELECTRONICALLY SIGNED
 AND SEALED- FL. STATUTE 471.025 & SECTION 61G15-23.005
 FLORIDA ADMINISTRATION CODE.
  
 2) SHEETS P1.01 & P5.03: AS PREVIOUSLY REQUESTED SHOW
 THE VENT PIPING TERMINATION CLEARANCES PER SECTION
 1305.7 FBC M.
  
 LIQUID FUEL VENT PIPES SHALL TERMINATE OUTSIDE OF
 BUILDINGS AT A POINT NOT LESS THAN 2 FEET (610 MM)
 MEASURED VERTICALLY OR HORIZONTALLY FROM ANY BUILDING
 OPENING. OUTER ENDS OF VENT PIPES SHALL TERMINATE IN A
 WEATHERPROOF VENT CAP OR FITTING OR BE PROVIDED WITH A
 WEATHERPROOF HOOD. VENT CAPS SHALL HAVE A MINIMUM FREE
 OPEN AREA EQUAL TO THE CROSS-SECTIONAL AREA OF THE VENT
 PIPE AND SHALL NOT EMPLOY SCREENS FINER THAN NO. 4
 MESH. VENT PIPES SHALL TERMINATE SUFFICIENTLY ABOVE THE
 GROUND TO AVOID BEING OBSTRUCTED WITH SNOW OR ICE. VENT
 PIPES FROM TANKS CONTAINING HEATERS SHALL BE EXTENDED
 TO A LOCATION WHERE OIL VAPORS DISCHARGING FROM THE
 VENT WILL BE READILY DIFFUSED. IF THE STATIC HEAD WITH
 A VENT PIPE FILLED WITH OIL EXCEEDS 10 POUNDS PER
 SQUARE INCH (PSI) (69 KPA), THE TANK SHALL BE DESIGNED
 FOR THE MAXIMUM STATIC HEAD THAT WILL BE IMPOSED.
  
 2) THE FARMER & IRWIN FUEL PIPING SHOP DRAWING IS NOT
 SUITABLE FOR REVIEW BECAUSE IT IS CUT OFF AND NOT A
 FULL-SIZE DRAWING- SECTION 107.2.1 WPB. THE DRAWING
 MUST ALSO BEAR THE SHOP DRAWING APPROVAL STAMP OF TLC
 ENGINEERING- SECTION 107.1 WPB.
  
 3) THE FARMER & IRWIN FUEL OIL PIPING PRODUCT SUBMITTAL
 DOES NOT INCLUDE THE VENT PIPING AND THE TERMINATION
 CAPS- SECTION 107.2.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2020-04-20 Cont ID  
Sent By ccole Date 2020-04-20 Time 12:36 Rev Time 0.00
Received By ccole Date 2020-04-20 Time 10:42 Sent To  
Notes
2020-04-20 12:37:551ST REVIEW FBC-2017 PLUMBING
 PERMIT #20040506
 4/20/2020
  
 CODES IN EFFECT:
  
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
 NFPA 30
  
 1) SHEETS P1.01 SHOW THE LOCATIONS OF THE REMOTE FILL
 PIPE AND SMART PUMP, AND SHOW THE FILL PIPE RUN TO THE
 FUEL TANK- SECTION 1305.6 FBC M.
  
 2) P1.01: REFERENCE IS MADE TO SHEET P4.01A FOR VENT
 PIPING TERMINATION LOCATION. PLEASE UPLOAD THE MISSING
 PLAN SHEET- SECTION 1305.7 FBC M, AND SECTION 107.2.1
 WPB. THE PLANS SHALL SHOW THE NORMAL AND EMERGENCY
 RELIEF VENT PIPING TERMINATION LOCATIONS AT THE
 EXTERIOR OF THE BUILDING WITH REQUIRED CLEARANCES.
  
 3) PROVIDE A SUBMITTAL PACKAGE THAT INCLUDES PRODUCT
 SPECS FOR THE FUEL PIPING, FITTINGS AND VALVES,
 FLEXIBLE CONNECTORS AND HOSES, SMART PUMP, CONTROL
 DEVICES AND ALARMS- SEE SECTION 1302 FBC M, AND SECTION
 27.4 NFPA 30.
  
 4) PROVIDE PIPE ASSEMBLY AND INSTALLATION DETAILS AND
 SPECIFICATIONS- SECTION 1303 FBC M.
  
 PLAN REVIEW RESULTS: DENIED.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2020-10-14 Cont ID  
Sent By jgomez Date 2020-10-14 Time 17:33 Rev Time 0.00
Received By jgomez Date 2020-10-14 Time 17:33 Sent To  
Notes
2020-10-14 17:39:49DRAWING P5.03 WITH ENGINEER'S ORIGINAL SEAL/SIGNATURE
 MATCHES APPROVED ONE. JG.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status F Date 2020-08-25 Cont ID  
Sent By ccole Date 2020-08-25 Time 17:31 Rev Time 0.00
Received By ccole Date 2020-08-25 Time 17:31 Sent To  
Notes
2020-08-25 17:32:502ND REQUEST: THE REVISED SHEET P5.03 IS NOT
 ELECTRONICALLY SIGNED AND SEALED- FL. STATUTE 471.025 &
 SECTION 61G15-23.005 FLORIDA ADMINISTRATION CODE.
  
 IN LIEU OF AN ELECTRONICALLY SIGNED AND SEALED PLAN, A
 SIGNED AND SEALED PAPER PLAN MAY BE SUBMITTED PRIOR TO
 CALLING FOR 1ST INSPECTION.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2020-08-04 Cont ID  
Sent By medwards Date 2020-08-04 Time 07:53 Rev Time 0.00
Received By ccole Date 2020-08-03 Time 07:52 Sent To  
Notes
2020-08-04 10:17:04THE REVISED SHEET P5.03 IS NOT ELECTRONICALLY SIGNED
 AND SEALED- FL. STATUTE 471.025 & SECTION 61G15-23.005
 FLORIDA ADMINISTRATION CODE.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2020-04-17 Cont ID  
Sent By medwards Date 2020-04-17 Time 09:04 Rev Time 0.00
Received By medwards Date 2020-04-17 Time 09:04 Sent To  
Notes
***NONE***