| Plan Review Stops For Permit 20040487 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2020-06-04 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2020-06-04 |
Time |
10:47 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2020-06-04 |
Time |
10:47 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2020-05-26 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2020-05-26 |
Time |
08:59 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2020-05-26 |
Time |
08:59 |
Sent To |
|
|
| Notes |
| 2020-05-26 09:00:19 | PLAN | | | REVIEW COMMENTS | | | | | | 2ND REVIEW: FBC SIXTH EDITION (2017) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) COMMENT WAS NOT ADDRESSED. THE VALUATION OF $3500.00 | | | IS LOW FOR THIS PROJECT. FOR THE PURPOSES OF PERMIT | | | COST, THE VALUE OF THE SIGNS, MATERIALS, LABOR, | | | ENGINEERING, OVERHEAD & PROFIT IS ALL INCLUDED IN THE | | | PERMIT VALUE. FBC 109.3 BUILDING PERMIT VALUATION. FOR | | | PERMITTING PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS | | | SHALL BE TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL, | | | ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH, | | | RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES, | | | MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY | | | LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST | | | PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS | | | SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY | | | INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT | | | VALUATION SHALL BE SET BY THE BUILDING OFFICIAL. | | | | | | 2) COMMENT WAS NOT ADDRESSED. DRAWING SHEETS 10 AND 11 | | | ARE STILL MISSING. THERE APPEARS TO BE SOME SHEETS | | | MISSING FROM THE 11 PAGES OF DESIGN DOCUMENTS. SUBMIT | | | ALL SHEETS FBC 107.2.1 | | | | | | 3) COMPLIED. | | | | | | 4) COMPLIED. | | | | | | 5) COMPLIED. | | | | | | 6) WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A | | | RESPONSE LETTER ADDRESSING EACH ITEM ALONG WITH THE | | | CITY RE-SUBMITTAL FORM. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2020-04-16 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2020-04-16 |
Time |
14:55 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2020-04-16 |
Time |
14:55 |
Sent To |
|
|
| Notes |
| 2020-04-16 15:07:35 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC SIXTH EDITION (2017) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) THE VALUATION OF $3500.00 IS LOW FOR THIS PROJECT. | | | FOR THE PURPOSES OF PERMIT COST, THE VALUE OF THE | | | SIGNS, MATERIALS, LABOR, ENGINEERING, OVERHEAD & PROFIT | | | IS ALL INCLUDED IN THE PERMIT VALUE. FBC 109.3 BUILDING | | | PERMIT VALUATION. FOR PERMITTING PURPOSES, VALUATION OF | | | BUILDINGS AND SYSTEMS SHALL BE TOTAL REPLACEMENT VALUE | | | TO INCLUDE STRUCTURAL, ELECTRIC, PLUMBING, MECHANICAL, | | | INTERIOR FINISH, RELATIVE SITE WORK, ARCHITECTURAL AND | | | DESIGN FEES, MARKETING COSTS, OVERHEAD AND PROFIT; | | | EXCLUDING ONLY LAND VALUE. VALUATION REFERENCES MAY | | | INCLUDE THE LATEST PUBLISHED DATA OF NATIONAL | | | CONSTRUCTION COST ANALYSIS SERVICES (MARSHALL-SWIFT, | | | MEANS, ETC.), AS PUBLISHED BY INTERNATIONAL CODE | | | CONGRESS. FINAL BUILDING PERMIT VALUATION SHALL BE SET | | | BY THE BUILDING OFFICIAL. | | | | | | 2) THERE APPEARS TO BE SOME SHEETS MISSING FROM THE 11 | | | PAGES OF DESIGN DOCUMENTS. SUBMIT ALL SHEETS FBC | | | 107.2.1 | | | | | | 3) PROVIDE A DIAGRAM THAT SHOWS THE LOCATION OF THE | | | FASTENERS FOR EACH OF THE CHANNEL LETTERS FOR THE WALL | | | MOUNT SIGN. FBC 107.2.1.2 | | | | | | 4) PROVIDE ENGINEERED WINDLOAD CALCULATIONS FOR THE | | | BLADE SIGN. FBC 107.2.1.2 | | | | | | 5) PROVIDE A DETAIL THAT SHOWS THE TYPE, NUMBER AND | | | LOCATION OF THE ANCHORS FOR THE BLADE SIGN. FBC 107.2.1 | | | | | | 6) WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A | | | RESPONSE LETTER ADDRESSING EACH ITEM ALONG WITH THE | | | CITY RE-SUBMITTAL FORM. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2020-06-05 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2020-06-05 |
Time |
17:43 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2020-06-05 |
Time |
17:42 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2020-05-27 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2020-05-27 |
Time |
13:27 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2020-05-27 |
Time |
13:27 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2020-04-29 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2020-04-29 |
Time |
08:58 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2020-04-29 |
Time |
07:56 |
Sent To |
|
|
| Notes |
| 2020-04-29 08:58:29 | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 | | | 6TH ED, CHAPTER 1. | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 | | | 6TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | FAC = FLORIDA ADMINISTRATIVE CODE | | | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | 1. PROVIDE ELECTRICAL PLAN FOR REVIEW, SIGNED (AND | | | SEALED WHERE APPLICABLE) BY THE PERSON RESPONSIBLE FOR | | | THE DESIGN. WPB FBC 107.2.1, 107.3.5; FS 471, 481 | | | | | | END OF COMMENTS. | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, PROVIDE A RESPONSE LETTER ADDRESSING EACH | | | ITEM ALONG WITH THE CITY RESUBMITTAL FORM. | | | ADDITIONALLY, INSERT CORRECTED PAGES INTO THE ORIGINAL | | | SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS. | | | ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD | | | REMAIN IN PACKAGE AND BE MARKED OLD SHEETS. | | | | | | SINCERELY, | | | | | | JOHN PEARSON | | | ELECTRICAL PLANS EXAMINER | | | 561-805-6746 | | | [email protected] | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2020-06-09 |
|
|
Cont ID |
|
| Sent By |
ccarvaja |
Date |
2020-06-09 |
Time |
16:23 |
Rev Time |
0.00 |
| Received By |
ccarvaja |
Date |
2020-06-02 |
Time |
15:01 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2020-05-29 |
|
|
Cont ID |
|
| Sent By |
ajones |
Date |
2020-05-29 |
Time |
09:22 |
Rev Time |
0.00 |
| Received By |
ajones |
Date |
2020-05-13 |
Time |
14:45 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2020-05-08 |
|
|
Cont ID |
|
| Sent By |
ajones |
Date |
2020-05-08 |
Time |
15:14 |
Rev Time |
0.00 |
| Received By |
ajones |
Date |
2020-04-13 |
Time |
13:34 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
3 |
Status |
P |
Date |
2020-06-04 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2020-06-04 |
Time |
10:47 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2020-06-04 |
Time |
10:47 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
P |
Date |
2020-05-26 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2020-05-26 |
Time |
09:09 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2020-05-26 |
Time |
09:09 |
Sent To |
|
|
| Notes |
| 2020-05-26 09:11:00 | THE MISSING SHEETS WILL NEED TO HAVE DIGITAL | | | SIGNATURES. THE ONES THAT WERE SUBMITTED ARE OKAY. |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
F |
Date |
2020-04-16 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2020-04-16 |
Time |
14:55 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2020-04-16 |
Time |
14:55 |
Sent To |
|
|
| Notes |
| 2020-04-16 14:56:25 | DRAWINGS ARE NOT DIGITALLY SIGNED. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
P |
Date |
2020-06-09 |
|
|
Cont ID |
|
| Sent By |
ajones |
Date |
2020-06-09 |
Time |
16:22 |
Rev Time |
0.00 |
| Received By |
ajones |
Date |
2020-06-09 |
Time |
16:22 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
F |
Date |
2020-05-29 |
|
|
Cont ID |
|
| Sent By |
ajones |
Date |
2020-05-29 |
Time |
09:21 |
Rev Time |
0.00 |
| Received By |
ajones |
Date |
2020-05-29 |
Time |
09:21 |
Sent To |
|
|
| Notes |
| 2020-05-29 09:22:32 | 5/29/2020- REPEAT COMMENTFAILED. PALM BEACH OUTLETS | | | MANAGEMENT APPROVAL MUST BE PROVIDED EITHER IN A STAMP | | | OR SEPERATE LETTER. | | | | | | ANGELLA VANN | | | [email protected] | | | 561-822-1441 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2020-05-08 |
|
|
Cont ID |
|
| Sent By |
rfalcone |
Date |
2020-05-08 |
Time |
15:11 |
Rev Time |
0.00 |
| Received By |
ajones |
Date |
2020-05-08 |
Time |
15:11 |
Sent To |
|
|
| Notes |
| 2020-05-08 15:14:18 | 5/8/2020- FAILED. PALM BEACH OUTLETS MANAGEMENT | | | APPROVAL MUST BE PROVIDED EITHER IN A STAMP OR SEPERATE | | | LETTER. | | | | | | ANGELLA VANN | | | [email protected] | | | 561-822-1441 |
|
|