Plan Review Details - Permit 20040371
Plan Review Stops For Permit 20040371
Review Stop E ELECTRICAL
Rev No 3 Status P Date 2020-07-22 Cont ID  
Sent By jleahy Date 2020-07-22 Time 11:50 Rev Time 0.00
Received By jleahy Date 2020-07-22 Time 11:50 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2020-05-22 Cont ID  
Sent By jpearson Date 2020-05-22 Time 14:14 Rev Time 0.00
Received By jpearson Date 2020-05-22 Time 13:28 Sent To  
Notes
2020-05-22 13:58:31CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE ELECTRICAL PLAN FOR REVIEW, SIGNED (AND
 SEALED WHERE APPLICABLE) BY THE PERSON RESPONSIBLE FOR
 THE DESIGN. WPB FBC 107.2.1, 107.3.5; FS 471, 481
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, PROVIDE A RESPONSE LETTER ADDRESSING EACH
 ITEM ALONG WITH THE CITY RESUBMITTAL FORM.
 ADDITIONALLY, INSERT CORRECTED PAGES INTO THE ORIGINAL
 SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS.
 ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD
 REMAIN IN PACKAGE AND BE MARKED OLD SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-04-14 Cont ID  
Sent By jpearson Date 2020-04-14 Time 13:37 Rev Time 0.00
Received By jpearson Date 2020-04-14 Time 13:37 Sent To  
Notes
2020-04-14 13:37:12CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE ELECTRICAL PLAN FOR REVIEW, SIGNED (AND
 SEALED WHERE APPLICABLE) BY THE PERSON RESPONSIBLE FOR
 THE DESIGN. WPB FBC 107.2.1, 107.3.5; FS 471, 481
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, PROVIDE A RESPONSE LETTER ADDRESSING EACH
 ITEM ALONG WITH THE CITY RESUBMITTAL FORM.
 ADDITIONALLY, INSERT CORRECTED PAGES INTO THE ORIGINAL
 SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS.
 ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD
 REMAIN IN PACKAGE AND BE MARKED OLD SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2020-07-22 Cont ID  
Sent By ccarvaja Date 2020-07-22 Time 15:03 Rev Time 0.00
Received By ccarvaja Date 2020-07-22 Time 10:46 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2020-05-28 Time   Rev Time 0.00
Received By lmarchan Date 2020-05-14 Time 14:18 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2020-04-14 Time   Rev Time 0.00
Received By ccarvaja Date 2020-04-09 Time 08:33 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2020-05-28 Cont ID  
Sent By jpearson Date 2020-05-28 Time 15:51 Rev Time 0.00
Received By jpearson Date 2020-05-28 Time 14:59 Sent To  
Notes
2020-05-28 15:00:02REVIEWED BY JERRY SMITH.
 20040371 101 N CLEMATIS ST 509
  
  
 PLUMBING COMMENTS: APPROVED
 ALL WORK PER STATE AND CITY CODES SUBJECT TO FIELD
 INSPECTOR'S APPROVAL
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-246-0882 MOBILE
  
 20040371 101 N CLEMATIS ST 509
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2020-04-14 Cont ID  
Sent By jpearson Date 2020-04-14 Time 13:05 Rev Time 0.00
Received By jpearson Date 2020-04-14 Time 13:05 Sent To  
Notes
2020-04-14 13:04:54REVIEWED BY JERRY SMITH.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 20040371 101 N CLEMATIS ST 509
  
 1ST REVIEW
 PLUMBING COMMENTS: DENIED
 1. PER WPB FBC 107.2.1, REFERENCING APPLICATIONS ON THE
 SUBMITTED SPEC HOME ADVII, INDICATE THE TYPES AND
 QUANTITIES OF FIXTURES BEING SERVICED BY THE HA0118240
 UNIT. PROVIDE TOTAL DEMAND FOR UNIT AND INDICATE ON THE
 SUBMITTAL WHICH INSERT WILL BE INCORPORATED IN THE
 INSTALLATION.
 2. AS THE DOCUMENTS ARE NOT SIGNED AND SEALED BY A
 PROFESSIONAL ENGINEER OR ARCHITECT, THE SUBMITTED
 DOCUMENTS SHALL BEAR THE PRINTED NAME AND SIGNATURE OF
 THE DESIGNER PER WPB FBC 107.2.1.
 3. PER WPB FBC 107.2.1, CONFIRM THAT REPLACEMENT WATER
 HEATER IS TO BE INSTALLED IN SAME LOCATION AS THE
 REPLACED STORAGE WATER HEATER AND THAT IT IS ACCESSIBLE
 IN COMPLIANCE WITH FBC PL 501.4 OR PROVIDE PLAN SHOWING
 LOCATIONS IF NOT THE SAME.
 4. UNIT WATTAGE IS 18 KW; TYPICALLY, A STORAGE TYPE
 WATER HEATER IS NO MORE THAN 4.5 KW. PER WPB FBC
 107.2.1, AN ELECTRICAL PLAN AND PERMIT APPLICATION
 SHALL BE SUBMITTED.
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
 ALL PLANS TO BE SIGNED AND SEALED BY THE DESIGNER AS
 REQUIRED BY FAC AND FS.
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-246-0882 MOBILE
  
 20040371 101 N CLEMATIS ST 509
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2020-07-22 Cont ID  
Sent By jleahy Date 2020-07-22 Time 11:50 Rev Time 0.00
Received By jleahy Date 2020-07-22 Time 11:50 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2020-05-28 Cont ID  
Sent By jpearson Date 2020-05-28 Time 15:54 Rev Time 0.00
Received By jpearson Date 2020-05-28 Time 15:54 Sent To  
Notes
2020-05-28 15:54:10NO PLANS SUBMITTED. PER THE WPB AMENDMENTS TO THE FBC,
 EACH SHEET OF PLAN IS REQUIRED TO BE SIGNED AND SEALED
 BY THE PERSON RESPONSIBLE FOR THE DESIGN. A DIGITAL
 PLAN REQUIRES A DIGITAL SIGNATURE WITH THE PROPER THIRD
 PARTY VERIFICATION. PROVIDE CORRECTION. WPB FBC 107.1;
 FS 471/481

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-04-14 Cont ID  
Sent By jpearson Date 2020-04-14 Time 13:36 Rev Time 0.00
Received By jpearson Date 2020-04-14 Time 13:36 Sent To  
Notes
2020-04-14 13:35:57NO PLANS SUBMITTED. PER THE WPB AMENDMENTS TO THE FBC,
 EACH SHEET OF PLAN IS REQUIRED TO BE SIGNED AND SEALED
 BY THE PERSON RESPONSIBLE FOR THE DESIGN. A DIGITAL
 PLAN REQUIRES A DIGITAL SIGNATURE WITH THE PROPER THIRD
 PARTY VERIFICATION. PROVIDE CORRECTION. WPB FBC 107.1;
 FS 471/481