| Plan Review Stops For Permit 20040309 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
N |
Date |
2020-04-23 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2020-04-23 |
Time |
11:06 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2020-04-23 |
Time |
11:05 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2020-07-30 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2020-07-30 |
Time |
12:05 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2020-07-29 |
Time |
16:12 |
Sent To |
|
|
| Notes |
| 2020-07-30 12:11:10 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | FLORIDA BUILDING CODE 2017 6TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED | | | NFPA 70 2014 EDITION | | | | | | JAKE LEAHY BN, BU, PX | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | PER ZONING NOTES NO KITCHEN , BEDROOM ARE ALLOWED FOR | | | THIS STRUCTURE. | | | | | | AS NOTED IN MASTER PERMIT 19061015 (CONVERSION OF | | | GARAGE TO CABANA/HOBBY SPACE ONLY; NO KITCHEN | | | FACILITY), THE ACCESSORY STRUCTURE SHALL NOT BE UTLIZED | | | AS AN ACCESSORY DWELLING UNIT. ACESSORY DWELLING UNITS | | | ARE PROHIBITED IN THE SF7 ZONING DISTRICT. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2020-06-16 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2020-06-16 |
Time |
12:20 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2020-06-16 |
Time |
09:50 |
Sent To |
|
|
| Notes |
| 2020-06-16 11:43:41 | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 | | | 6TH ED, CHAPTER 1. | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 | | | 6TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | FAC = FLORIDA ADMINISTRATIVE CODE | | | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | 1. PROVIDE ACCURATE LOAD CALCULATION FOR SERVICE, | | | INCLUDE EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF | | | SERVICE IS ADEQUATE. EXISTING LOAD NOT INCLUDED | | | CURRENTLY, IT ONLY SHOWS PANEL C. NEC 215.2, 220, | | | 408.30; FBC RE E3602.2 | | | 2. PROVIDE MORE DETAIL FOR RISER DIAGRAM, SHOWING ALL | | | DETAILS OF SERVICE EQUIPMENT, UNDERGROUND OR OVERHEAD | | | SERVICE, WIRE AND BREAKER SIZES FOR SERVICE AND FEED TO | | | ANY SUB-PANEL(S). SHOW GEC SIZE AND SYSTEM, SHOW | | | INTERSYSTEM BONDING TERMINATION POINT. NEC 215.5, 230, | | | 250.50, 250.94, 408.30; FBC RE E3706.1, E3608.1, | | | E3609.3; WPB FBC 107.2.1 | | | 3. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR | | | SERVICE INCLUDING INFORMATION FROM THE POWER COMPANY | | | STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR | | | THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE | | | SERVICE EQUIPMENT IS ADEQUATE. NEC 110.9, 110.10; FBC | | | RE E3606.3 | | | | | | | | | | | | END OF COMMENTS. | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, PROVIDE A RESPONSE LETTER ADDRESSING EACH | | | ITEM ALONG WITH THE CITY RESUBMITTAL FORM. | | | ADDITIONALLY, INSERT CORRECTED PAGES INTO THE ORIGINAL | | | SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS. | | | ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD | | | REMAIN IN PACKAGE AND BE MARKED OLD SHEETS. | | | | | | SINCERELY, | | | | | | JOHN PEARSON | | | ELECTRICAL PLANS EXAMINER | | | 561-805-6746 | | | [email protected] | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2020-04-27 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2020-04-27 |
Time |
14:48 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2020-04-27 |
Time |
14:27 |
Sent To |
|
|
| Notes |
| 2020-04-27 14:39:52 | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 | | | 6TH ED, CHAPTER 1. | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 | | | 6TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | FAC = FLORIDA ADMINISTRATIVE CODE | | | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | 1. WHILE A SECOND METER MAY BE APPROVED IF ZONING | | | PERMITS, A SECOND SERVICE IS NOT PERMITTED. THE | | | ORIGINAL SERVICE ON THE STRUCTURE WOULD NEED TO BE | | | RE-BUILT TO ACCOMMODATE THE 2ND METER. PROVIDE | | | CORRECTION IF ZONING ISSUE CAN BE CORRECTED. NEC 230.2; | | | FBC RE E3601.2 | | | | | | END OF COMMENTS. | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, PROVIDE A RESPONSE LETTER ADDRESSING EACH | | | ITEM ALONG WITH THE CITY RESUBMITTAL FORM. | | | ADDITIONALLY, INSERT CORRECTED PAGES INTO THE ORIGINAL | | | SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS. | | | ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD | | | REMAIN IN PACKAGE AND BE MARKED OLD SHEETS. | | | | | | SINCERELY, | | | | | | JOHN PEARSON | | | ELECTRICAL PLANS EXAMINER | | | 561-805-6746 | | | [email protected] | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2020-07-30 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2020-07-30 |
Time |
12:12 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2020-07-13 |
Time |
09:43 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2020-06-19 |
|
|
Cont ID |
|
| Sent By |
lmarchan |
Date |
2020-06-19 |
Time |
16:11 |
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2020-06-04 |
Time |
13:33 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2020-04-27 |
Time |
|
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2020-04-14 |
Time |
10:33 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
3 |
Status |
P |
Date |
2020-07-30 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2020-07-30 |
Time |
12:12 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2020-07-30 |
Time |
12:12 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
P |
Date |
2020-06-29 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2020-06-29 |
Time |
14:21 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2020-06-29 |
Time |
14:21 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
P |
Date |
2020-04-27 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2020-04-27 |
Time |
14:33 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2020-04-27 |
Time |
14:33 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2020-06-19 |
|
|
Cont ID |
|
| Sent By |
llouie |
Date |
2020-06-19 |
Time |
|
Rev Time |
0.00 |
| Received By |
llouie |
Date |
2020-06-19 |
Time |
|
Sent To |
|
|
| Notes |
| 2020-06-19 15:47:22 | AS NOTED IN MASTER PERMIT 19061015 (CONVERSION OF | | | GARAGE TO CABANA/HOBBY SPACE ONLY; NO KITCHEN | | | FACILITY), THE ACCESSORY STRUCTURE SHALL NOT BE UTLIZED | | | AS AN ACCESSORY DWELLING UNIT. ACESSORY DWELLING UNITS | | | ARE PROHIBITED IN THE SF7 ZONING DISTRICT. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2020-04-16 |
|
|
Cont ID |
|
| Sent By |
llouie |
Date |
2020-04-16 |
Time |
|
Rev Time |
|
| Received By |
llouie |
Date |
2020-04-16 |
Time |
|
Sent To |
|
|
| Notes |
| 2020-04-16 16:02:03 | ** FAILED ** | | | | | | PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE | | | COMMENTS IN WRITING AND/OR ON THE PLANS WHERE | | | APPLICABLE: | | | | | | 1.) THE SF7 ZONING DISTRICT DOES NOT ALLOW FOR AN | | | ACCESSORY DWELLING UNIT. PLEASE PROVIDE JUSTIFICATION | | | FOR THE SEPARATE METER. | | | | | | 2.) SHOW INTERIOR PLAN LAYOUT. | | | | | | | | | NOTES: | | | | | | * ANY REVISIONS TO THE PLANS MAY RESULT IN ADDITIONAL | | | COMMENTS. | | | | | | * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE | | | QUESTIONS. | | | | | | * MASTER PERMIT: #19061015 (AS NOTED BY THE ARCHITECT, | | | THE SCOPE OF WORK IS FOR THE CONVERSION OF THE GARAGE | | | TO A HOBBY SPACE ONLY; NOT AN ACCESSORY DWELLING UNIT) | | | | | | * Z = SF7 | | | |
|
|