Plan Review Details - Permit 20040309
Plan Review Stops For Permit 20040309
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status N Date 2020-04-23 Cont ID  
Sent By pvalenti Date 2020-04-23 Time 11:06 Rev Time 0.00
Received By rmcdouga Date 2020-04-23 Time 11:05 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2020-07-30 Cont ID  
Sent By jleahy Date 2020-07-30 Time 12:05 Rev Time 0.00
Received By jleahy Date 2020-07-29 Time 16:12 Sent To  
Notes
2020-07-30 12:11:10ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 PER ZONING NOTES NO KITCHEN , BEDROOM ARE ALLOWED FOR
 THIS STRUCTURE.
  
 AS NOTED IN MASTER PERMIT 19061015 (CONVERSION OF
 GARAGE TO CABANA/HOBBY SPACE ONLY; NO KITCHEN
 FACILITY), THE ACCESSORY STRUCTURE SHALL NOT BE UTLIZED
 AS AN ACCESSORY DWELLING UNIT. ACESSORY DWELLING UNITS
 ARE PROHIBITED IN THE SF7 ZONING DISTRICT.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2020-06-16 Cont ID  
Sent By jpearson Date 2020-06-16 Time 12:20 Rev Time 0.00
Received By jpearson Date 2020-06-16 Time 09:50 Sent To  
Notes
2020-06-16 11:43:41CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE ACCURATE LOAD CALCULATION FOR SERVICE,
 INCLUDE EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF
 SERVICE IS ADEQUATE. EXISTING LOAD NOT INCLUDED
 CURRENTLY, IT ONLY SHOWS PANEL C. NEC 215.2, 220,
 408.30; FBC RE E3602.2
 2. PROVIDE MORE DETAIL FOR RISER DIAGRAM, SHOWING ALL
 DETAILS OF SERVICE EQUIPMENT, UNDERGROUND OR OVERHEAD
 SERVICE, WIRE AND BREAKER SIZES FOR SERVICE AND FEED TO
 ANY SUB-PANEL(S). SHOW GEC SIZE AND SYSTEM, SHOW
 INTERSYSTEM BONDING TERMINATION POINT. NEC 215.5, 230,
 250.50, 250.94, 408.30; FBC RE E3706.1, E3608.1,
 E3609.3; WPB FBC 107.2.1
 3. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR
 SERVICE INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR
 THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE
 SERVICE EQUIPMENT IS ADEQUATE. NEC 110.9, 110.10; FBC
 RE E3606.3
  
  
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, PROVIDE A RESPONSE LETTER ADDRESSING EACH
 ITEM ALONG WITH THE CITY RESUBMITTAL FORM.
 ADDITIONALLY, INSERT CORRECTED PAGES INTO THE ORIGINAL
 SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS.
 ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD
 REMAIN IN PACKAGE AND BE MARKED OLD SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-04-27 Cont ID  
Sent By jpearson Date 2020-04-27 Time 14:48 Rev Time 0.00
Received By jpearson Date 2020-04-27 Time 14:27 Sent To  
Notes
2020-04-27 14:39:52CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. WHILE A SECOND METER MAY BE APPROVED IF ZONING
 PERMITS, A SECOND SERVICE IS NOT PERMITTED. THE
 ORIGINAL SERVICE ON THE STRUCTURE WOULD NEED TO BE
 RE-BUILT TO ACCOMMODATE THE 2ND METER. PROVIDE
 CORRECTION IF ZONING ISSUE CAN BE CORRECTED. NEC 230.2;
 FBC RE E3601.2
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, PROVIDE A RESPONSE LETTER ADDRESSING EACH
 ITEM ALONG WITH THE CITY RESUBMITTAL FORM.
 ADDITIONALLY, INSERT CORRECTED PAGES INTO THE ORIGINAL
 SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS.
 ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD
 REMAIN IN PACKAGE AND BE MARKED OLD SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2020-07-30 Cont ID  
Sent By jleahy Date 2020-07-30 Time 12:12 Rev Time 0.00
Received By jleahy Date 2020-07-13 Time 09:43 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-06-19 Cont ID  
Sent By lmarchan Date 2020-06-19 Time 16:11 Rev Time 0.00
Received By lmarchan Date 2020-06-04 Time 13:33 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2020-04-27 Time   Rev Time 0.00
Received By lmarchan Date 2020-04-14 Time 10:33 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2020-07-30 Cont ID  
Sent By jleahy Date 2020-07-30 Time 12:12 Rev Time 0.00
Received By jleahy Date 2020-07-30 Time 12:12 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2020-06-29 Cont ID  
Sent By shill Date 2020-06-29 Time 14:21 Rev Time 0.00
Received By shill Date 2020-06-29 Time 14:21 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2020-04-27 Cont ID  
Sent By jpearson Date 2020-04-27 Time 14:33 Rev Time 0.00
Received By jpearson Date 2020-04-27 Time 14:33 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2020-06-19 Cont ID  
Sent By llouie Date 2020-06-19 Time   Rev Time 0.00
Received By llouie Date 2020-06-19 Time   Sent To  
Notes
2020-06-19 15:47:22AS NOTED IN MASTER PERMIT 19061015 (CONVERSION OF
 GARAGE TO CABANA/HOBBY SPACE ONLY; NO KITCHEN
 FACILITY), THE ACCESSORY STRUCTURE SHALL NOT BE UTLIZED
 AS AN ACCESSORY DWELLING UNIT. ACESSORY DWELLING UNITS
 ARE PROHIBITED IN THE SF7 ZONING DISTRICT.

Review Stop Z ZONING
Rev No 1 Status F Date 2020-04-16 Cont ID  
Sent By llouie Date 2020-04-16 Time   Rev Time  
Received By llouie Date 2020-04-16 Time   Sent To  
Notes
2020-04-16 16:02:03** FAILED **
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE
 COMMENTS IN WRITING AND/OR ON THE PLANS WHERE
 APPLICABLE:
  
 1.) THE SF7 ZONING DISTRICT DOES NOT ALLOW FOR AN
 ACCESSORY DWELLING UNIT. PLEASE PROVIDE JUSTIFICATION
 FOR THE SEPARATE METER.
  
 2.) SHOW INTERIOR PLAN LAYOUT.
  
  
 NOTES:
  
 * ANY REVISIONS TO THE PLANS MAY RESULT IN ADDITIONAL
 COMMENTS.
  
 * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE
 QUESTIONS.
  
 * MASTER PERMIT: #19061015 (AS NOTED BY THE ARCHITECT,
 THE SCOPE OF WORK IS FOR THE CONVERSION OF THE GARAGE
 TO A HOBBY SPACE ONLY; NOT AN ACCESSORY DWELLING UNIT)
  
 * Z = SF7
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved