| 2020-04-20 14:01:43 | 2017 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 20040307 / EXPIRED: 06071240 |
| | ADD: 14205 GLENMOORE DR. / CONDOMINIUM |
| | CONT: TNT BUILDERS OF SOUTH FLORIDA |
| | TEL: 772-344-9400 |
| | E-MAIL: [email protected] |
| | |
| | 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION. |
| | |
| | PERMIT: 06071240 WAS NEVER ISSUED. THERE WAS ONLY ONE |
| | ROUND OF COMMENTS AND NO RE-SUBMITTAL. NOTE IN THE |
| | COMPUTER FROM ASSISTANT BUILDING OFFICIAL S. KENNEDY, |
| | EVALUATE REVOCATION OF EXPIRED PERMIT APPLICATION PART |
| | OF THE WORK WAS COMPLETED IN THAT ERA. |
| | |
| | CREATION OR EXTENSION OF NONCONFORMITY. |
| | 2017 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. CREATION OR EXTENSION |
| | OF NONCONFORMITY. ALL NEW WORK, RE-CONFIGURATION SHALL |
| | NOT CREATE OR EXTEND ANY NONCONFORMITY IN THE EXISTING |
| | BUILDING TO WHICH THE RE-CONFIGURATION OF SPACE IS |
| | BEING MADE WITH REGARD TO ACCESSIBILITY, STRUCTURAL |
| | STRENGTH, FIRE SAFETY, MEANS OF EGRESS, OR THE CAPACITY |
| | OF MECHANICAL, PLUMBING, OR ELECTRICAL SYSTEMS. |
| | |
| | 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | THE ORIGINAL PERMIT WAS FOR ENCLOSING A EXTERIOR DINING |
| | ROOM, REMOVE THE PATIO DOORS, AND INSTALLATION OF NEW |
| | WINDOWS. SINCE THE ORIGINAL PERMIT WAS NEVER ISSUED, |
| | THERE ARE NO DOCUMENTS TO REFERENCE. A COMPLETE SET OF |
| | DOCUMENTS WILL BE NEEDED TO ENSURE CODE COMPLIANCE. |
| | SINCE THE PERMIT WAS NEVER ISSUED, THERE WAS NEVER |
| | INSPECTIONS TO VERIFY CODE COMPLIANCE. THIS REVIEW WILL |
| | PROVIDE A LIST OF DEFICIENT DOCUMENTS NEEDED TO DO A |
| | THOROUGH REVIEW. |
| | |
| | |
| | 1ST REVIEW |
| | DATE: MON.APRIL20/2020 |
| | ACTION: DENIED |
| | |
| | 1) PLEASE PROVIDE A LETTER FROM THE CONDOMINIUM |
| | ASSOCIATION THAT THE ENCLOSING OF THE EXTERIOR PORCH IS |
| | IN ACCORDANCE WITH THE CONDOMINIUM BYLAWS. |
| | CREATION OR EXTENSION OF NONCONFORMITY. 2017 EXISTING |
| | BUILDING CODE LEVEL II 701.3 COMPLIANCE. THE ENCLOSING |
| | OF THE EXTERIOR PORCH IS CONSIDERED AN ADDITION TO THE |
| | AIR CONDITIONED SPACE. ON THE ORIGINAL PERMIT THE |
| | SLIDING GLASS DOORS WERE GOING TO BE REMOVED CREATING |
| | NEW AIR CONDITIONED SPACE. |
| | |
| | 2) PLEASE SUBMIT 2 COPIES OF THE ENERGY CALCULATION?S |
| | THAT ARE SIGNED BY THE OWNER & AGENT. 2017 EXIST. |
| | BUILD. CODE 1106.1. |
| | |
| | 3) PLEASE SUBMIT 2 SETS OF PLANS FOR PAPER PLANS. 2017 |
| | WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| | CODE, CHAPTER 1, ADMINISTRATIVE CODE |
| | 107.3.5.1. COMMERCIAL BUILDINGS- CONDOMINIUMS ARE |
| | CONSIDERED MULTI-FAMILY R-2 RESIDENCE, COMMERCIAL |
| | BUILDINGS REVIEWED UNDER THE 2017 FBC-B. |
| | 107.3.5.1.1. BUILDING. REVIEW/ R-2 OCCUPANCY/ |
| | CONDOMINIUM. |
| | FLOOR PLAN |
| | OCCUPANCY |
| | BUILDING CONSTRUCTION TYPE |
| | ELEVATION OF AREA TO BE ENCLOSED |
| | WALL CONSTRUCTION, PROVIDE TYPE OF MATERIALS, CBS BLOCK |
| | & REINFORCING, WOOD FRAME, STEEL FRAME, AND TYPE OF |
| | FINISHES INTERIOR & EXTERIOR |
| | BUCK ATTACHMENT TO SUBSTRATE BY DESIGN PROFESSIONAL |
| | WIND DESIGN CRITERIA |
| | |
| | 4) 2017 FBC-B 1603.1.4 WIND DESIGN DATA. |
| | THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL |
| | BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE |
| | DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE |
| | STRUCTURE: |
| | |
| | 4.1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST), |
| | MILES PER HOUR AND NOMINAL DESIGN WIND SPEED, VASD, AS |
| | DETERMINED IN ACCORDANCE WITH SECTION 1609.3.1. |
| | |
| | 4.2. RISK CATEGORY. |
| | |
| | 4.3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE |
| | THAN ONE WIND EXPOSURE IS UTILIZED. TABLE 1609.7.2. |
| | HEIGHT AND EXPOSURE. |
| | |
| | 4.4. APPLICABLE INTERNAL PRESSURE COEFFICIENT. |
| | |
| | 4.5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR |
| | COMPONENTS AND CLADDING MATERIALS NOT SPECIFICALLY |
| | DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL |
| | RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE, PSF. |
| | |
| | 4.6 TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT & |
| | EXPOSURE (CONSIDERED ( C ) EXPOSURE). PROVIDE THE MEAN |
| | ROOF HEIGHT FOR THE BUILDING. 1609.3.1 WIND SPEED |
| | CONVERSION VULT TO VASD. |
| | |
| | 5) COMPONENTS & CLADDING.2017 FBC-B 1609.1.2 PROTECTION |
| | OF OPENINGS, 1609.6.4.4.1 COMPONENTS & CLADDING. |
| | FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS, ADMINISTRATIVE |
| | CODE 61G20-3.005, RULE 9N-3 NOV. 01/ 2010 (31) |
| | SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT |
| | WILL REQUIRE PRODUCT APPROVALS: |
| | (31)(B) WINDOWS & MULLIONS |
| | (C) EFIS SYSTEMS, |
| | (E) SHUTTERS |
| | |
| | 6) IDENTIFY GLAZING/ MULLIONS. THE SUBMITTED PRODUCT |
| | APPROVALS THE ELEMENTS LISTED BELOW ARE NOT IDENTIFIED. |
| | PLEASE IDENTIFY ON THE PRODUCT APPROVAL BEFORE |
| | SUBMITTING TO DESIGNER OF RECORD AND BEFORE SUBMISSION |
| | TO THE BUILDING DEPARTMENT. FOR ALL PRODUCTS WITH |
| | GLAZING, PLEASE IDENTIFY THE OPENING WIDTH & HEIGHT, |
| | TYPE OF GLAZING, MULLION SIZE, LENGTH IF UNREINFORCED |
| | OR REINFORCED INFORMATION IF REQUIRED, ATTACHMENTS AND |
| | ASSOCIATE PRESSURES FOR EACH OPENING SIZE. 2017 FBC-B |
| | 1405.13.1 INSTALLATION. WINDOWS AND DOORS SHALL BE |
| | INSTALLED IN ACCORDANCE WITH APPROVED MANUFACTURER?S |
| | INSTRUCTIONS. FASTENER SIZE AND SPACING SHALL BE |
| | PROVIDED IN SUCH INSTRUCTIONS AND SHALL BE CALCULATED |
| | BASED ON MAXIMUM LOADS AND SPACING USED IN THE TESTS. |
| | |
| | 7) THE DESIGN PROFESSIONAL SHALL ASCERTAIN WHAT TYPE OF |
| | MWFRS MAIN WIND FORCE RESISTING SYSTEM (CONCRETE BLOCK, |
| | FILLED OR UNFILLED, CONCRETE, WOOD FRAMING, STEEL |
| | FRAMING) THAT THE WINDOW BUCKS ARE GOING TO BE ATTACHED |
| | TO, TYPE OF ANCHORS, SIZE OF ANCHORS AND MINIMUM |
| | SPACING OF ANCHORS FOR THE POSITIVE & NEGATIVE |
| | PRESSURES THAT ARE GOING TO BE APPLIED TO THE WOOD |
| | BUCKS. 707.4 EXIST. BUILD. CODE & CHAPTER 16 OF THE |
| | 2017 FBC-B. |
| | |
| | 8) W. P. B. 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS |
| | WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| | SHOP DRAWINGS ETC.. |
| | |
| | 9) IF THE PROPOSED WINDOWS BEING INSTALLED DO NOT HAVE |
| | LARGE MISSILE IMPACT RESISTANT TESTING THEN STORM |
| | SHUTTERS WILL BE REQUIRED ON THIS NEW OPENING. |
| | STORM SHUTTERS. PROVIDE STORM PANEL INFORMATION WITH |
| | INSTALLATION SCHEDULE AND KEY PLAN WITH SPECIFIC |
| | ANCHORS AND MOUNTING TO BE USED FOR ALL NON-IMPACT |
| | GLAZING. FBC 1609.1.2. |
| | FL BLD CODE 2017 SECTION 107.2.5.,1609.1.2, 1715.8 & |
| | EXIST BUILD CODE 706.4 PROCEDURES: A COMPLETE |
| | INSTALLATION SCHEDULE SUMMARIZING & IDENTIFYING OPENING |
| | SIZES, STORY HEIGHTS, UNIT MARK NUMBERS, UNIT |
| | SPANS/WIDTHS, UNIT STORM BAR REINFORCING REQUIREMENTS, |
| | WALL PRESSURE ZONES, SLAT TYPES, ETC. |
| | |
| | 10) THE PLAN ALSO INDICATED THE INSTALATION OF A |
| | GUARDRAIL TO BEINSTALLED TO WALL AND FLOOR. THERE IS NO |
| | DETAIL OF THE RAILING SHOWING IF THIS RAILING IS TO BE |
| | DESIGNED AS A GUARD RAILING INACCORDANCE WITH CHAPTER |
| | 15 OF THE FBC-B. |
| | 1503 HEIGTH. |
| | 1504. OPENING LIMITATIONS. |
| | 1607.8.1 GUARDRAILS. |
| | 1607.8.1.1 CONCENTRATED LOADS PROVIDE ENGINEERED |
| | ANALYSIS WHAT ANCHORS TO BE INSTALLED TO ENSURE CODE |
| | COMPLIANCE WITH THESE REQUIREMENTS. |
| | 1607.8.1.2 INTERMEDIATE RAILS |
| | |
| | 2017 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| | CODE, CHAPTER 1, ADMINISTRATION 107.2.1. W.P.B. |
| | ADMINISTRATIVE CODE/2017 DRAWINGS & SPECIFICATIONS |
| | SHALL CONTAIN INFORMATION, IN THE FORM OF NOTES OR |
| | OTHERWISE, AS TO THE QUALITY OF MATERIALS, WHERE |
| | QUALITY IS ESSENTIAL TO CONFORMITY WITH THE TECHNICAL |
| | CODES. SUCH INFORMATION SHALL BE SPECIFIC TO THE |
| | TECHNICAL CODES "SHALL NOT BE CITED AS A WHOLE OR IN |
| | PART, NOR THE TERM "LEGAL" OR ITS EQUIVALENT BE USED AS |
| | A SUBSTITUTE FOR SPECIFIC INFORMATION". CONSTRUCTION |
| | DOCUMENTS SHALL BE SUFFICIENT CLARITY TO INDICATE THE |
| | LOCATION, NATURE AND EXTENT OF THE WORK PROPOSED AND |
| | SHOW IN DETAIL THAT IT WILL CONFORM TO THE PROVISIONS |
| | OF THIS CODE AND RELEVANT LAWS, ORDINANCES, RULES AND |
| | REGULATIONS, AS DETERMINED BY THE BUILDING OFFICIAL. |
| | |
| | 11) IMPACT FEES/ IMPACT FEES - DIGITAL SUBMITTALS: |
| | PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE |
| | DIGITALLY VIA PROJECT DOX UPON NOTIFICATION BY THIS |
| | OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST |
| | FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE |
| | OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL |
| | IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME |
| | THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM |
| | CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS |
| | TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON |
| | APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE RECEIPT TO |
| | YOUR PROJECT OR EMAIL IT TO [email protected] . |
| | PALM BEACH COUNTY IMPACT FEE OFFICE IS LOCATED AT 2300 |
| | N. JOG RD. ROOM?S 2W01-2W14 WEST PALM BEACH, FL. |
| | |
| | IMPACT FEES- PAPER SUBMITTALS. |
| | PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE OFFICE. CALL |
| | (561) 233-5025. UPON APPROVAL, YOU MAY CHECK OUT ONE |
| | PLAN SET AND TAKE TO THAT OFFICE FOR REVIEW. PLEASE |
| | RETURNED STAMPED AND WITH A COPY OF THE RECEIPT AS |
| | APPLICABLE. PLEASE PROVIDE THE MUNICIPAL IMPACT FEE |
| | QUESTIONNAIRE FORM TO THE PBC IMPACT FEE OFFICE. THE |
| | FORM CAN BE FOUND AT: |
| | HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINISTRATION/PDF/IMPAC |
| | TFEES/FORMS/QUESTIONNAIRE.PDF |
| | |
| | 12) WHEN RESUBMITTING PLANS PLEASE INDICATE THE |
| | REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES |
| | AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE |
| | THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED |
| | DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE |
| | MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS |
| | AND INFORMATION LACKING UNDER THE PRIOR REVIEW. |
| | JAMES A. WITMER BN, PX, SFP & CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT |
| | 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 |
| | TEL: 561-805-6717 / FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| 2020-04-08 11:30:02 | EVALUATE REVOCATION OF EXPIRE PERMIT APPLICATIONS. PART |
| | OF THE WORK WAS COMPLETED IN THIS ERA. |