Plan Review Details - Permit 20040307
Plan Review Stops For Permit 20040307
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2020-05-05 Cont ID  
Sent By skennedy Date 2020-05-05 Time 13:27 Rev Time 0.00
Received By skennedy Date 2020-05-05 Time 13:27 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-04-20 Cont ID  
Sent By jwitmer Date 2020-04-20 Time 14:01 Rev Time 0.00
Received By jwitmer Date 2020-04-20 Time 11:01 Sent To  
Notes
2020-04-20 14:01:432017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 20040307 / EXPIRED: 06071240
 ADD: 14205 GLENMOORE DR. / CONDOMINIUM
 CONT: TNT BUILDERS OF SOUTH FLORIDA
 TEL: 772-344-9400
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION.
  
 PERMIT: 06071240 WAS NEVER ISSUED. THERE WAS ONLY ONE
 ROUND OF COMMENTS AND NO RE-SUBMITTAL. NOTE IN THE
 COMPUTER FROM ASSISTANT BUILDING OFFICIAL S. KENNEDY,
 EVALUATE REVOCATION OF EXPIRED PERMIT APPLICATION PART
 OF THE WORK WAS COMPLETED IN THAT ERA.
  
 CREATION OR EXTENSION OF NONCONFORMITY.
 2017 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING. CREATION OR EXTENSION
 OF NONCONFORMITY. ALL NEW WORK, RE-CONFIGURATION SHALL
 NOT CREATE OR EXTEND ANY NONCONFORMITY IN THE EXISTING
 BUILDING TO WHICH THE RE-CONFIGURATION OF SPACE IS
 BEING MADE WITH REGARD TO ACCESSIBILITY, STRUCTURAL
 STRENGTH, FIRE SAFETY, MEANS OF EGRESS, OR THE CAPACITY
 OF MECHANICAL, PLUMBING, OR ELECTRICAL SYSTEMS.
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 THE ORIGINAL PERMIT WAS FOR ENCLOSING A EXTERIOR DINING
 ROOM, REMOVE THE PATIO DOORS, AND INSTALLATION OF NEW
 WINDOWS. SINCE THE ORIGINAL PERMIT WAS NEVER ISSUED,
 THERE ARE NO DOCUMENTS TO REFERENCE. A COMPLETE SET OF
 DOCUMENTS WILL BE NEEDED TO ENSURE CODE COMPLIANCE.
 SINCE THE PERMIT WAS NEVER ISSUED, THERE WAS NEVER
 INSPECTIONS TO VERIFY CODE COMPLIANCE. THIS REVIEW WILL
 PROVIDE A LIST OF DEFICIENT DOCUMENTS NEEDED TO DO A
 THOROUGH REVIEW.
  
  
 1ST REVIEW
 DATE: MON.APRIL20/2020
 ACTION: DENIED
  
 1) PLEASE PROVIDE A LETTER FROM THE CONDOMINIUM
 ASSOCIATION THAT THE ENCLOSING OF THE EXTERIOR PORCH IS
 IN ACCORDANCE WITH THE CONDOMINIUM BYLAWS.
 CREATION OR EXTENSION OF NONCONFORMITY. 2017 EXISTING
 BUILDING CODE LEVEL II 701.3 COMPLIANCE. THE ENCLOSING
 OF THE EXTERIOR PORCH IS CONSIDERED AN ADDITION TO THE
 AIR CONDITIONED SPACE. ON THE ORIGINAL PERMIT THE
 SLIDING GLASS DOORS WERE GOING TO BE REMOVED CREATING
 NEW AIR CONDITIONED SPACE.
  
 2) PLEASE SUBMIT 2 COPIES OF THE ENERGY CALCULATION?S
 THAT ARE SIGNED BY THE OWNER & AGENT. 2017 EXIST.
 BUILD. CODE 1106.1.
  
 3) PLEASE SUBMIT 2 SETS OF PLANS FOR PAPER PLANS. 2017
 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATIVE CODE
 107.3.5.1. COMMERCIAL BUILDINGS- CONDOMINIUMS ARE
 CONSIDERED MULTI-FAMILY R-2 RESIDENCE, COMMERCIAL
 BUILDINGS REVIEWED UNDER THE 2017 FBC-B.
 107.3.5.1.1. BUILDING. REVIEW/ R-2 OCCUPANCY/
 CONDOMINIUM.
 FLOOR PLAN
 OCCUPANCY
 BUILDING CONSTRUCTION TYPE
 ELEVATION OF AREA TO BE ENCLOSED
 WALL CONSTRUCTION, PROVIDE TYPE OF MATERIALS, CBS BLOCK
 & REINFORCING, WOOD FRAME, STEEL FRAME, AND TYPE OF
 FINISHES INTERIOR & EXTERIOR
 BUCK ATTACHMENT TO SUBSTRATE BY DESIGN PROFESSIONAL
 WIND DESIGN CRITERIA
  
 4) 2017 FBC-B 1603.1.4 WIND DESIGN DATA.
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE
 STRUCTURE:
  
 4.1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST),
 MILES PER HOUR AND NOMINAL DESIGN WIND SPEED, VASD, AS
 DETERMINED IN ACCORDANCE WITH SECTION 1609.3.1.
  
 4.2. RISK CATEGORY.
  
 4.3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE
 THAN ONE WIND EXPOSURE IS UTILIZED. TABLE 1609.7.2.
 HEIGHT AND EXPOSURE.
  
 4.4. APPLICABLE INTERNAL PRESSURE COEFFICIENT.
  
 4.5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR
 COMPONENTS AND CLADDING MATERIALS NOT SPECIFICALLY
 DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL
 RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE, PSF.
  
 4.6 TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT &
 EXPOSURE (CONSIDERED ( C ) EXPOSURE). PROVIDE THE MEAN
 ROOF HEIGHT FOR THE BUILDING. 1609.3.1 WIND SPEED
 CONVERSION VULT TO VASD.
  
 5) COMPONENTS & CLADDING.2017 FBC-B 1609.1.2 PROTECTION
 OF OPENINGS, 1609.6.4.4.1 COMPONENTS & CLADDING.
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS, ADMINISTRATIVE
 CODE 61G20-3.005, RULE 9N-3 NOV. 01/ 2010 (31)
 SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT
 WILL REQUIRE PRODUCT APPROVALS:
 (31)(B) WINDOWS & MULLIONS
 (C) EFIS SYSTEMS,
 (E) SHUTTERS
  
 6) IDENTIFY GLAZING/ MULLIONS. THE SUBMITTED PRODUCT
 APPROVALS THE ELEMENTS LISTED BELOW ARE NOT IDENTIFIED.
 PLEASE IDENTIFY ON THE PRODUCT APPROVAL BEFORE
 SUBMITTING TO DESIGNER OF RECORD AND BEFORE SUBMISSION
 TO THE BUILDING DEPARTMENT. FOR ALL PRODUCTS WITH
 GLAZING, PLEASE IDENTIFY THE OPENING WIDTH & HEIGHT,
 TYPE OF GLAZING, MULLION SIZE, LENGTH IF UNREINFORCED
 OR REINFORCED INFORMATION IF REQUIRED, ATTACHMENTS AND
 ASSOCIATE PRESSURES FOR EACH OPENING SIZE. 2017 FBC-B
 1405.13.1 INSTALLATION. WINDOWS AND DOORS SHALL BE
 INSTALLED IN ACCORDANCE WITH APPROVED MANUFACTURER?S
 INSTRUCTIONS. FASTENER SIZE AND SPACING SHALL BE
 PROVIDED IN SUCH INSTRUCTIONS AND SHALL BE CALCULATED
 BASED ON MAXIMUM LOADS AND SPACING USED IN THE TESTS.
  
 7) THE DESIGN PROFESSIONAL SHALL ASCERTAIN WHAT TYPE OF
 MWFRS MAIN WIND FORCE RESISTING SYSTEM (CONCRETE BLOCK,
 FILLED OR UNFILLED, CONCRETE, WOOD FRAMING, STEEL
 FRAMING) THAT THE WINDOW BUCKS ARE GOING TO BE ATTACHED
 TO, TYPE OF ANCHORS, SIZE OF ANCHORS AND MINIMUM
 SPACING OF ANCHORS FOR THE POSITIVE & NEGATIVE
 PRESSURES THAT ARE GOING TO BE APPLIED TO THE WOOD
 BUCKS. 707.4 EXIST. BUILD. CODE & CHAPTER 16 OF THE
 2017 FBC-B.
  
 8) W. P. B. 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 9) IF THE PROPOSED WINDOWS BEING INSTALLED DO NOT HAVE
 LARGE MISSILE IMPACT RESISTANT TESTING THEN STORM
 SHUTTERS WILL BE REQUIRED ON THIS NEW OPENING.
 STORM SHUTTERS. PROVIDE STORM PANEL INFORMATION WITH
 INSTALLATION SCHEDULE AND KEY PLAN WITH SPECIFIC
 ANCHORS AND MOUNTING TO BE USED FOR ALL NON-IMPACT
 GLAZING. FBC 1609.1.2.
 FL BLD CODE 2017 SECTION 107.2.5.,1609.1.2, 1715.8 &
 EXIST BUILD CODE 706.4 PROCEDURES: A COMPLETE
 INSTALLATION SCHEDULE SUMMARIZING & IDENTIFYING OPENING
 SIZES, STORY HEIGHTS, UNIT MARK NUMBERS, UNIT
 SPANS/WIDTHS, UNIT STORM BAR REINFORCING REQUIREMENTS,
 WALL PRESSURE ZONES, SLAT TYPES, ETC.
  
 10) THE PLAN ALSO INDICATED THE INSTALATION OF A
 GUARDRAIL TO BEINSTALLED TO WALL AND FLOOR. THERE IS NO
 DETAIL OF THE RAILING SHOWING IF THIS RAILING IS TO BE
 DESIGNED AS A GUARD RAILING INACCORDANCE WITH CHAPTER
 15 OF THE FBC-B.
 1503 HEIGTH.
 1504. OPENING LIMITATIONS.
 1607.8.1 GUARDRAILS.
 1607.8.1.1 CONCENTRATED LOADS PROVIDE ENGINEERED
 ANALYSIS WHAT ANCHORS TO BE INSTALLED TO ENSURE CODE
 COMPLIANCE WITH THESE REQUIREMENTS.
 1607.8.1.2 INTERMEDIATE RAILS
  
 2017 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION 107.2.1. W.P.B.
 ADMINISTRATIVE CODE/2017 DRAWINGS & SPECIFICATIONS
 SHALL CONTAIN INFORMATION, IN THE FORM OF NOTES OR
 OTHERWISE, AS TO THE QUALITY OF MATERIALS, WHERE
 QUALITY IS ESSENTIAL TO CONFORMITY WITH THE TECHNICAL
 CODES. SUCH INFORMATION SHALL BE SPECIFIC TO THE
 TECHNICAL CODES "SHALL NOT BE CITED AS A WHOLE OR IN
 PART, NOR THE TERM "LEGAL" OR ITS EQUIVALENT BE USED AS
 A SUBSTITUTE FOR SPECIFIC INFORMATION". CONSTRUCTION
 DOCUMENTS SHALL BE SUFFICIENT CLARITY TO INDICATE THE
 LOCATION, NATURE AND EXTENT OF THE WORK PROPOSED AND
 SHOW IN DETAIL THAT IT WILL CONFORM TO THE PROVISIONS
 OF THIS CODE AND RELEVANT LAWS, ORDINANCES, RULES AND
 REGULATIONS, AS DETERMINED BY THE BUILDING OFFICIAL.
  
 11) IMPACT FEES/ IMPACT FEES - DIGITAL SUBMITTALS:
 PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECT DOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON
 APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE RECEIPT TO
 YOUR PROJECT OR EMAIL IT TO [email protected] .
 PALM BEACH COUNTY IMPACT FEE OFFICE IS LOCATED AT 2300
 N. JOG RD. ROOM?S 2W01-2W14 WEST PALM BEACH, FL.
  
 IMPACT FEES- PAPER SUBMITTALS.
 PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE OFFICE. CALL
 (561) 233-5025. UPON APPROVAL, YOU MAY CHECK OUT ONE
 PLAN SET AND TAKE TO THAT OFFICE FOR REVIEW. PLEASE
 RETURNED STAMPED AND WITH A COPY OF THE RECEIPT AS
 APPLICABLE. PLEASE PROVIDE THE MUNICIPAL IMPACT FEE
 QUESTIONNAIRE FORM TO THE PBC IMPACT FEE OFFICE. THE
 FORM CAN BE FOUND AT:
 HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINISTRATION/PDF/IMPAC
 TFEES/FORMS/QUESTIONNAIRE.PDF
  
 12) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE
 THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED
 DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE
 MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS
 AND INFORMATION LACKING UNDER THE PRIOR REVIEW.
 JAMES A. WITMER BN, PX, SFP & CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717 / FAX: 561-805-6676
 E-MAIL: [email protected]
  
2020-04-08 11:30:02EVALUATE REVOCATION OF EXPIRE PERMIT APPLICATIONS. PART
 OF THE WORK WAS COMPLETED IN THIS ERA.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2020-05-05 Cont ID  
Sent By skennedy Date 2020-05-05 Time 13:27 Rev Time 0.00
Received By skennedy Date 2020-05-05 Time 13:27 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-04-27 Cont ID  
Sent By jpearson Date 2020-04-27 Time 14:21 Rev Time 0.00
Received By jpearson Date 2020-04-27 Time 14:11 Sent To  
Notes
2020-04-27 14:21:07CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE CLARIFICATION FOR RECEPTACLE OUTLETS TO BE
 INSTALLED. WILL THIS BE A NEW CIRCUIT, OR ADDED TO AN
 EXITSTING CIRCUIT. WPB FBC 107.2.1
 2. ALL BRANCH CIRCUITS THAT SUPPLY 120-VOLT,
 SINGLE-PHASE, 15- AND 20-AMPERE OUTLETS INSTALLED IN
 KITCHENS, FAMILY ROOMS, DINING ROOMS, LIVING ROOMS,
 PARLORS, LIBRARIES, DENS, BEDROOMS, SUN-ROOMS,
 RECREATIONS ROOMS, CLOSETS, HALLWAYS, LAUNDRY AREAS AND
 SIMILAR ROOMS OR AREAS SHALL BE AFCI PROTECTED. PROVIDE
 CORRECTION. NEC 210.12; FBC RE E3902.16
 3. PROVIDE SMOKE/CO ALARMS IN EACH LOCATION REQUIRED
 PER CODE. PROVIDE FULL FLOOR PLAN SHOWING ALL EXISTING
 ALARMS. IF NONE ARE EXISTING OR NOT TO CODE, SHOW AS
 NEW INSTALLATIONS, OR PROVIDE A NOTE REQUIRING
 COMPLIANCE. FBC RE R314.3, R315.1; WPB FBC 107.2.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, PROVIDE A RESPONSE LETTER ADDRESSING EACH
 ITEM ALONG WITH THE CITY RESUBMITTAL FORM.
 ADDITIONALLY, INSERT CORRECTED PAGES INTO THE ORIGINAL
 SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS.
 ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD
 REMAIN IN PACKAGE AND BE MARKED OLD SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-05-05 Cont ID  
Sent By lmarchan Date 2020-05-05 Time 14:11 Rev Time 0.00
Received By lmarchan Date 2020-05-04 Time 14:55 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2020-04-27 Time   Rev Time 0.00
Received By lmarchan Date 2020-04-14 Time 11:14 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2020-05-08 Cont ID  
Sent By lmarchan Date 2020-05-08 Time 10:50 Rev Time 0.00
Received By lmarchan Date 2020-05-05 Time 15:19 Sent To  
Notes
2020-05-08 09:07:11MU-2020-015320 - $1693.14 - PAID
2020-05-05 15:19:305/5 EMAILED IMPACT OFFICE FOR REVIEW. LEM

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2020-04-20 Cont ID  
Sent By jwitmer Date 2020-04-20 Time 14:03 Rev Time 0.00
Received By jwitmer Date 2020-04-20 Time   Sent To  
Notes
2020-04-20 14:03:13IMPACT FEES - DIGITAL SUBMITTALS:
 PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECT DOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON
 APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE RECEIPT TO
 YOUR PROJECT OR EMAIL IT TO [email protected] .
 PALM BEACH COUNTY IMPACT FEE OFFICE IS LOCATED AT 2300
 N. JOG RD. ROOM?S 2W01-2W14 WEST PALM BEACH, FL.
  
 IMPACT FEES- PAPER SUBMITTALS. PLANS REQUIRE REVIEW BY
 THE PBC IMPACT FEE OFFICE. CALL (561) 233-5025. UPON
 APPROVAL, YOU MAY CHECK OUT ONE PLAN SET AND TAKE TO
 THAT OFFICE FOR REVIEW. PLEASE RETURNED STAMPED AND
 WITH A COPY OF THE RECEIPT AS APPLICABLE. PLEASE
 PROVIDE THE MUNICIPAL IMPACT FEE QUESTIONNAIRE FORM TO
 THE PBC IMPACT FEE OFFICE. THE FORM CAN BE FOUND AT:
 HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINISTRATION/PDF/IMPAC
 TFEES/FORMS/QUESTIONNAIRE.PDF
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2020-05-05 Cont ID  
Sent By skennedy Date 2020-05-05 Time 13:27 Rev Time 0.00
Received By skennedy Date 2020-05-05 Time 13:27 Sent To  
Notes
2020-05-05 13:28:10OWNER IS DESIGNER.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-04-27 Cont ID  
Sent By jpearson Date 2020-04-27 Time 14:18 Rev Time 0.00
Received By jpearson Date 2020-04-27 Time 14:18 Sent To  
Notes
2020-04-27 14:18:13PER THE WPB AMENDMENTS TO THE FBC, EACH SHEET OF PLAN
 IS REQUIRED TO BE SIGNED AND SEALED BY THE PERSON
 RESPONSIBLE FOR THE DESIGN. A DIGITAL PLAN REQUIRES A
 DIGITAL SIGNATURE WITH THE PROPER THIRD PARTY
 VERIFICATION. PROVIDE CORRECTION. ALTERNATIVELY, A
 SIGNED/SEALED PAPER SET MAY BE SUPPLIED TO THE BUILDING
 DEPARTMENT WHEN ALL TRADES ARE APPROVED. WPB FBC 107.1;
 FS 471/481