| 2020-04-19 14:08:00 | 2017 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 20040270 |
| | ADD: 501 S FLAGLER DR. SUITE # 200 |
| | CONT: ANDERSON MOORE |
| | TEL: 561-348-4805 |
| | E-MAIL: [email protected] |
| | |
| | 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION. |
| | |
| | 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: SUN. APRIL 19TH/ 2020 |
| | ACTION: DENIED |
| | |
| | 1) SHEET ALS, THE LIFE SAFETY SHEET AND OTHER SHEETS |
| | EXAMPLE A1.1.1: |
| | |
| | 1A) INDICATE ROOM 219 AS COPY AREA/ KITCHEN. WHEN THE |
| | WORDING KITCHEN IS USED IN THE COMMERCIAL CODES THE |
| | 2017 FBC-B SECTION 904.2.2 WOULD REQUIRE COMMERCIAL |
| | HOOD AND EXHAUST SYSTEM. A BETTER WORDING FOR THE AREA |
| | IN QUESTION WOULD BE BREAK ROOM. |
| | |
| | 1B) THERE IS A SECTION IN THE KITCHEN REFERENCING |
| | DETAIL 2/A4.0.2. THIS DETAIL SHOWS A SHELF ABOVE THE |
| | SINK WITH THE TOP OF THE SHELF AT A HEIGHT OF 4 FEET 9 |
| | INCHES. THE ELECTRICAL SHEETS E0.1 & E3.1 SHOW 2 |
| | ELECTRICAL CIRCUITS LABELED LA-12 & LA14 AND THE NOTE |
| | HT- TBD. I WILL TAKE THE NOTE TO MEAN HEIGHT TO BE |
| | DETERMINED. PLEASE NOTE IF THE DESIGNER OF RECORD FOR |
| | BOTH THE ARCHITECTURAL AND ELECTRICAL SHEETS IF IN THE |
| | FUTURE THESE OUTLETS ARE TO FEED A MICROWAVE APPLIANCE |
| | THE SHELF ITSELF IS HIGHER THAN ALLOWED BY THE 2017 |
| | ACCESSIBILITY CODE SEE SECTIONS: |
| | |
| | 308 REACH RANGES |
| | 308.2 FORWARD REACH. / 308.2.1 UNOBSTRUCTED/ 308.2.2 |
| | OBSTRUCTED HIGH REACH. |
| | 308.3 SIDE REACH. / 308.3.1 UNOBSTRUCTED/ 308.3.2 |
| | OBSTRUCTED HIGH REACH. |
| | |
| | 309 OPERABLE PARTS |
| | 309.3 HEIGHT. OPERABLE PARTS SHALL BE PLACED WITHIN ONE |
| | OR MORE OF THE REACH RANGES SPECIFIED IN 308. |
| | 309.4 OPERATION. OPERABLE PARTS SHALL BE OPERABLE WITH |
| | ONE HAND AND SHALL NOT REQUIRE TIGHT GRASPING, |
| | PINCHING, OR TWISTING OF THE WRIST. THE FORCE REQUIRED |
| | TO ACTIVATE OPERABLE PARTS SHALL BE 5 POUNDS MAXIMUM. |
| | |
| | 1C) SHEET ALS UNDER THE HEADING CODE DATA DOES NOT |
| | INDICATE IF THERE ARE GANGED RESTROOMS (WITH ACCESSIBLE |
| | RESTROOMS) AND WATER FOUNTAINS (HIGH/ LOW)IN THE COMMON |
| | ELEMENTS OF THE CORRIDOR CORE OF THE BUILDING? |
| | 107.2.1.2 ADDITIONAL INFORMATION IS REQUIRED. THERE ARE |
| | 2 ISSUES WITH THE RESTROOMS AS CONFIGURED SINCE WE NEED |
| | TO MEET BOTH THE REQUIREMENTS OF THE 2017 FBC-B SECTION |
| | 2902.1 AND TABLE 2902.1 AND THE REQUIREMENTS FOUND |
| | UNDER THE 2017 FBC-ACCESSIBILITY CODE. |
| | IF THERE IS A DIFFERENCE BETWEEN CODES THE MOST |
| | STRINGENT THEN APPLIES. MISSING SERVICE SINK AND |
| | DRINKING FOUNTAIN. |
| | 1C)(1) MUST MEET THE REQUIREMENTS FOUND IN TABLE 2902.1 |
| | FOR BUSINESS OCCUPANCY FOR 39 0CCPUPANTS. SEPARATE |
| | FACILITIES WOULD BE REQUIRED BY FBC-B SECTION 2902.2, |
| | DOES NOT MEET ANY EXCEPTIONS. |
| | |
| | 1C)(2) THE 2ND ISSUE IS UNDER THE 2017 |
| | FBC-ACCESSIBILITY CODE 213.2 WHERE TOILET ROOMS ARE |
| | PROVIDED EACH TOILET ROOM SHALL COMPLY WITH 603. IF ONE |
| | OF THE EXCEPTIONS DOES APPLY PLEASE STATE SO ON THE |
| | PLANS. |
| | |
| | 1D) DRINKING FOUNTAINS MUST COMPLY WITH THE 2017 |
| | FBC-ACCESSIBILITY CODE SECTION 211.2 MINIMUM NUMBER. NO |
| | FEWER THAN 2 DRINKING FOUNTAINS SHALL BE PROVIDED. ONE |
| | DRINKING FOUNTAIN SHALL COMPLY WITH 602.1 THROUGH 602.6 |
| | AND ONE DRINKING FOUNTAIN SHALL COMPLY WITH 602.7. |
| | |
| | 2) SHEET A3.0.1. RESTROOM # 216 HAS A WALL MEASUREMENT |
| | OF 11 FEET 8 INCHES WHEN MEASURING THE DOOR THE DOOR |
| | MEASURES OUT TO BE APPROXIMATELY 4 FEET 5 INCHES. THERE |
| | IS A DISCREPANCY IN MEASUREMENTS FOR 11 FEET 8 INCHES? |
| | DISCREPANCY IN PLANS, 107.2.1.2 ADDITIONAL INFORMATION |
| | IS REQUIRED. WITH THE MEASUREMENT OF THE WALL AT 11 |
| | FEET 8 INCHES THE DOOR SWING SHOULD CLEAR THE REQUIRED |
| | CLEAR FLOOR SPACE. ALSO YOU CAN SHOW COMPLIANCE WITH |
| | 603.2.3 EX. # 2. |
| | |
| | 3) SHEET A3.0.1.NEITHER OF THE RESTROOMS SHOW A |
| | COMPLIANT MIRROR. MIRRORS. 2017 FBC-ACCESSIBILITY CODE |
| | 603.3 MIRRORS. MIRRORS LOCATED ABOVE LAVATORIES OR |
| | COUNTERTOPS SHALL BE INSTALLED WITH THE BOTTOM EDGE OF |
| | THE REFLECTING SURFACE 40 INCHES MAXIMUM ABOVE THE |
| | FINISH FLOOR OR GROUND. MIRRORS NOT LOCATED ABOVE |
| | LAVATORIES OR COUNTERTOPS SHALL BE INSTALLED WITH THE |
| | BOTTOM EDGE OF THE REFLECTING SURFACE 35 INCHES MAXIMUM |
| | ABOVE THE FINISH FLOOR OR GROUND. |
| | |
| | 4) SHEET A3.0.1. ACCESSIBLE LAVATORY. DETAIL # 6 NEEDS |
| | TO SHOW COMPLIANCE WITH: |
| | |
| | 4A) 2017 FBC-ACCESSIBILITY CODE SECTION 606.3 HEIGHT. |
| | LAVATORIES AND SINKS SHALL BE INSTALLED WITH THE FRONT |
| | OF THE HIGHER OF THE RIM OR COUNTER SURFACE 34 INCHES |
| | MAXIMUM ABOVE THE FINISH FLOOR OR GROUND. |
| | |
| | 4B) 2017 FBC-ACCESSIBILITY CODE 606.4 FAUCETS. CONTROLS |
| | FOR FAUCETS SHALL COMPLY WITH 309. HAND-OPERATED |
| | METERING FAUCETS SHALL REMAIN OPEN FOR 10 SECONDS |
| | MINIMUM. |
| | |
| | 4C) 2017 FBC-ACCESSIBILITY CODE 606.5 EXPOSED PIPES AND |
| | SURFACES. WATER SUPPLY AND DRAIN PIPES UNDER LAVATORIES |
| | AND SINKS SHALL BE INSULATED OR OTHERWISE CONFIGURED TO |
| | PROTECT AGAINST CONTACT. THERE SHALL BE NO SHARP OR |
| | ABRASIVE SURFACES UNDER LAVATORIES AND SINKS. |
| | |
| | 5) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | JAMES A. WITMER BN, PX, SFP & CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT |
| | 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 |
| | TEL: 561-805-6717 / FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |