Plan Review Details - Permit 20040268
Plan Review Stops For Permit 20040268
Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2020-06-04 Time   Rev Time 0.00
Received By lmarchan Date 2020-05-26 Time 13:28 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2020-05-15 Time   Rev Time 0.00
Received By lmarchan Date 2020-04-23 Time 10:59 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2020-06-04 Cont ID  
Sent By ccole Date 2020-06-04 Time 13:22 Rev Time 0.00
Received By ccole Date 2020-06-04 Time 12:30 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2020-05-15 Cont ID  
Sent By ccole Date 2020-05-15 Time 07:20 Rev Time 0.00
Received By ccole Date 2020-05-15 Time 07:02 Sent To  
Notes
2020-05-15 08:03:031ST REVIEW FBC-2017 PLUMBING
 PERMIT #20040268
 5/15/2020
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 PLEASE SEE APPENDIX F FBC P.
  
 1) PLEASE SUBMIT SHEET 2 OF THE IRRIGATION PLAN. IT
 APPEARS ONLY SHEET 1 OF 2 WAS UPLOADED FOR REVIEW-
 SECTION 107.2.1 WPB.
  
 2) PROVIDE AN EQUIPMENT SCHEDULE ON THE PLAN INDICATING
 THE MAKES AND MODELS OF THE PUMP, CONTROLLER, RAIN
 SENSOR, SPRINKLER HEADS, CONTROL VALVES ETC.- SECTION
 107.2.1 WPB. PROVIDE MOUNTING DETAILS FOR THE PUMP AND
 ALL ABOVE GROUND EQUIPMENT,
  
 3) PROVIDE A SPRINKLER LEGEND ON THE PLAN THAT
 CORRELATES WITH THE SYMBOLS AND ZONES SHOWN ON THE IR-1
 PLAN.
  
 4) PROVIDE A MATERIALS LIST INDICATING TYPES OF
 IRRIGATION PIPING AND SLEEVES,
  
 5) PROVIDE BASIC INSTALLATION DETAILS- DEPTH OF COVER
 FOR THE PIPING, CLEARANCE OF PIPING FROM OTHER
 UNDERGOUND UTILITIES, SPACING OF SPRINKLER HEADS,
 CLEARANCE DISTANCES OF HEADS TO BUILDINGS.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status N Date 2020-06-04 Cont ID  
Sent By ccole Date 2020-06-04 Time 13:22 Rev Time 0.00
Received By ccole Date 2020-06-04 Time 13:22 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status N Date 2020-05-15 Cont ID  
Sent By ccole Date 2020-05-15 Time 08:03 Rev Time 0.00
Received By ccole Date 2020-05-15 Time 08:03 Sent To  
Notes
***NONE***