Plan Review Details - Permit 20040257
Plan Review Stops For Permit 20040257
Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-04-16 Cont ID  
Sent By jleahy Date 2020-04-16 Time 11:07 Rev Time 0.00
Received By jleahy Date 2020-04-16 Time 11:01 Sent To  
Notes
2020-04-16 11:09:43ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 1) VALUE OF WORK IS LOW, PLEASE SUBMIT A SIGNED
 CONTRACT FOR THE TOTAL AMOUNT OF WORK INCLUDING LABOR
 AND MATERIALS.
  
 109.3 BUILDING PERMIT VALUATIONS. IF, IN THE OPINION OF
 THE BUILDING OFFICIAL, THE CLAIMED VALUATION OF
 BUILDING, ALTERATION, STRUCTURE, ELECTRICAL, GAS,
 MECHANICAL OR PLUMBING SYSTEMS APPEARS TO BE
 UNDERESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE
 DENIED, UNLESS THE APPLICANT CAN SHOW DETAILED,
 QUANTITY ESTIMATES, AND/OR BONA FIDE SIGNED CONTRACTS
 (EXCLUDING LAND VALUE) TO MEET THE APPROVAL OF THE
 BUILDING OFFICIAL. FOR PERMITTING PURPOSES, VALUATION
 OF BUILDINGS AND SYSTEMS SHALL BE TOTAL REPLACEMENT
 VALUE TO INCLUDE STRUCTURAL, ELECTRIC, PLUMBING,
 MECHANICAL, INTERIOR FINISH, RELATIVE SITE WORK,
 ARCHITECTURAL AND DESIGN FEES, MARKETING COSTS,
 OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY
 INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT
 VALUATION SHALL BE SET BY THE BUILDING OFFICIAL.
  
 2) FAULT CURRENT CALCULATION REQUIRE ALONG WITH SIGNAGE
 AT SERVICE.
  
 PROVIDE CALCULATION FOR AVAILABLE SHORT CIRCUIT CURRENT
 AT NEW PANEL TO CONFIRM AIC RATING IS ADEQUATE. NEC
 110.10
 PROVIDE NOTE THAT THE SERVICE EQUIPMENT SHALL BE MARKED
 WITH THE MAXIMUM AVAILABLE SHORT CIRCUIT CURRENT
 AVAILABLE PER NEC 110.24.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-06-01 Cont ID  
Sent By lmarchan Date 2020-06-01 Time 14:48 Rev Time 0.00
Received By lmarchan Date 2020-04-08 Time 16:50 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2020-06-29 Cont ID  
Sent By shill Date 2020-06-29 Time 14:19 Rev Time 0.00
Received By shill Date 2020-06-29 Time 14:19 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2020-06-01 Cont ID  
Sent By avann Date 2020-06-01 Time 14:09 Rev Time 0.25
Received By eschneid Date 2020-06-01 Time 13:40 Sent To PC
Notes
2020-06-01 14:31:07FAILED
  
 PLEASE PROVIDE WRITTEN RESPONSES TO COMMENTS.
  
 1) PLEASE PROVIDE VERIFICATION IN THE FORM OF A SURVEY
 TO VERIFY THAT THE PROPOSED FACILITIES ARE LOCATED
 WITHIN THE RIGHT-OF-WAY AND NOT ON PRIVATE PROPERTY.
 THE SUPPLIED PLAN IS SIGNED AND SEALED BY AN ENGINEER,
 NOT A SURVEYOR. THE BACK OF A SIDEWALK IS TYPICALLY THE
 BOUNDARY BETWEEN THE RIGHT-OF-WAY AND THE PRIVATE
 PROPERTY, BUT THE PLAN SHOWS THE SIDEWALKS LOCATED AWAY
 FROM THE PROPERTY LINE.
  
 2) PROVIDE CONSENT FROM FPL, THE OWNER OF THE UTILITY
 POLE, THAT PERMITS THE PLACEMENT OF THE ANTENNAS AND
 RELATED EQUIPMENT ON IT.
  
 3) THE CITY REQUIRES THAT THE EQUIPMENT (UTILITY METER,
 DISCONNECT AD NEMA BOX) BE SCREENED BY LANDSCAPE.
 PLEASE SHOW HOW THIS WILL OCCUR. THE PLANS SHOW THE
 ELECTRIC METER CAN MOUNTED WITH A CENTER AT "6 FOOT
 HIGH MAX" WITH THE PEDESTAL AT LEAST ONE FOOT TALLER.
 PLEASE CONSIDER HAVING THEM MOUNTED ON A SHORTER
 PEDESTAL TO MINIMIZE THE VISUAL IMPACT (A LOWER
 LANDSCAPE SCREEN COULD THEN BE USED) OF THE EQUIPMENT
 IN FRONT OF A SINGLE FAMILY RESIDENCE. PROVIDE THE
 ACTUAL HEIGHT OF THE PEDESTAL THAT IS BEING INSTALLED
 ON THE PLAN.
  
 4) IF THE SURVEY FROM COMMENT #1 SHOWS ALL THE
 EQUIPMENT WITHIN THE RIGHT-OF-WAY, THEN PROVIDE THE
 RIGHT-OF-WAY APPROVAL FROM PALM BEACH COUNTY FOR THE
 CONSTRUCTION OF THE ITEMS THAT ARE NOT ATTACHED TO THE
 POWER POLE BUT ARE LOCATED WITHIN THE RIGHT-OF-WAY.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.
 [email protected]
  