Plan Review Details - Permit 20040240
Plan Review Stops For Permit 20040240
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2020-06-03 Cont ID  
Sent By rmcphers Date 2020-06-03 Time 14:44 Rev Time 0.00
Received By rmcphers Date 2020-06-03 Time 14:43 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-05-05 Cont ID  
Sent By rmcphers Date 2020-05-05 Time 08:44 Rev Time 0.00
Received By rmcphers Date 2020-05-05 Time 08:11 Sent To  
Notes
2020-05-05 08:44:42CHARGING STATION
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) PLEASE SHOW THE WIND DESIGN CRITERIA PER 2017 FBC
 (NOT IBC).
 2) PLEASE SHOW THE RISK CATEGORY USED PER FBC 1604.5
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2020-06-03 Cont ID  
Sent By jleahy Date 2020-06-03 Time 16:05 Rev Time 0.00
Received By jleahy Date 2020-06-03 Time 16:05 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2020-05-27 Cont ID  
Sent By jleahy Date 2020-05-27 Time 14:20 Rev Time 0.00
Received By jleahy Date 2020-05-27 Time 14:20 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-05-04 Cont ID  
Sent By jleahy Date 2020-05-04 Time 15:45 Rev Time 0.00
Received By jleahy Date 2020-05-04 Time 15:44 Sent To  
Notes
2020-05-04 15:47:01ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 1) FAULT CURRENT CALCULATIONS REQUIRED 110.9, 110.10
  
 PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH
 PANEL INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR
 THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE
 SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE.
 NEC 110.9, 110.10
  
 2) 210.64 ELECTRICAL SERVICE AREAS AT LEAST ONE
 125-VOLT, SINGLE-PHASE, 15- OR 20-AMPERE-RATED
 RECEPTACLE OUTLET SHALL BE INSTALLED WITH IN 15 M (50
 FT) OF THE ELECTRICAL SERVICE EQUIPMENT.
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-06-03 Cont ID  
Sent By jleahy Date 2020-06-03 Time 16:05 Rev Time 0.00
Received By jleahy Date 2020-05-29 Time 08:33 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-05-13 Cont ID  
Sent By lmarchan Date 2020-05-13 Time 16:59 Rev Time 0.00
Received By lmarchan Date 2020-04-17 Time 10:42 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2020-06-03 Cont ID  
Sent By rmcphers Date 2020-06-03 Time 14:44 Rev Time 0.00
Received By rmcphers Date 2020-06-03 Time 14:44 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2020-05-27 Cont ID  
Sent By rmcphers Date 2020-05-05 Time 08:49 Rev Time 0.00
Received By rmcphers Date 2020-05-05 Time 08:45 Sent To  
Notes
2020-05-05 08:50:53EMERGENCY RULE APPLIED 61G15ER20-4

Review Stop Z ZONING
Rev No 2 Status P Date 2020-05-29 Cont ID  
Sent By awooten Date 2020-05-29 Time   Rev Time 0.00
Received By awooten Date 2020-05-29 Time   Sent To  
Notes
2020-05-29 10:27:08ZONING PROVISO: ALL MECHANICAL EQUIPMENT WILL BE
 SCREENED FROM STREET VIEW WITH HEDGES.

Review Stop Z ZONING
Rev No 1 Status P Date 2020-05-13 Cont ID  
Sent By awooten Date 2020-05-13 Time   Rev Time 0.00
Received By awooten Date 2020-05-13 Time   Sent To  
Notes
***NONE***