| Plan Review Stops For Permit 20040233 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2020-05-26 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2020-05-26 |
Time |
15:39 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2020-05-26 |
Time |
15:39 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2020-04-23 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2020-04-23 |
Time |
10:41 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2020-04-22 |
Time |
15:56 |
Sent To |
|
|
| Notes |
| 2020-04-23 10:39:01 | SFR ADDITION | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected]. | | | | | | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 | | | 1) PLEASE SHOW ROOF SLOPE TO COMPLY WITH FBC R905.9.1 | | | 2) SURVEY PROVIDED NEEDS TO BE ELECTRONICALLY SIGNED BY | | | THE SURVEYOR TO BE USED IN ELECTRONIC PLAN REVIEW. | | | 3) PLEASE PROVIDE A SIGNED AND SEALED SOIL REPORT | | | (GEOTECHNICAL REPORT) FROM AN ARCHITECT OR ENGINEER FOR | | | THE SOIL BEARING CAPACITY. FBC R401.4 | | | 4) IN THE ROOFING PRODUCT APPROVALS - PLEASE CIRCLE THE | | | PRODUCTS TO BE USED, THE ROOFING SYSTEMS TO BE USED | | | ETC.. PLEASE PROVIDE SIGNED AND SEALED ADDITIONAL | | | ATTACHMENT DETAILS FROM AN ARCHITECT OR ENGINEER FOR | | | ROOFING ZONES 2 AND 3 WHICH MAY REQUIRE HIGHER | | | PRESSURES THAN THE PRODUCT APPROVAL ROOFING SYSTEM | | | USED. (SEE PRODUCT APPROVALS). | | | 5) PLEASE PROVIDE THE FRONT PAGES FOR THE OVERHEAD DOOR | | | PRODUCT APPROVAL. | | | 6) PLEASE SHOW ALL ROOF SLOPES. | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2020-06-10 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2020-06-10 |
Time |
15:30 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2020-06-10 |
Time |
15:30 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2020-06-03 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2020-06-03 |
Time |
12:57 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2020-06-03 |
Time |
09:56 |
Sent To |
|
|
| Notes |
| 2020-06-03 12:57:18 | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 | | | 6TH ED, CHAPTER 1. | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 | | | 6TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | FAC = FLORIDA ADMINISTRATIVE CODE | | | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED | | | SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS | | | COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY | | | HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW | | | COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS. | | | | | | 1. PLAN STATES THERE IS NO CHANGE TO THE RISER DIAGRAM, | | | BUT THE LOAD TABLE STATES THE UPGRADED ELECTRICAL | | | SERVICE IS 200 AMPS. WHICH IS IT? PROVIDE | | | CLARIFICATION. PROVIDE RISER DIAGRAM OF EXISTING | | | SERVICE. NEC 215.5; WPB FBC 107.2.1 (THERE ARE | | | DISCREPANCIES WITH THE RISER DIAGRAM. IS THIS A 200 AMP | | | AS INDICATED IN THE MAIN PANEL SCHEDULE? OR IS THIS A | | | 400 AMP PANEL AS INDICATED IN THE RISER DIAGRAM? OR IS | | | THIS A 325 AMP SERVICE AS INDICATED IN THE RISER | | | DIAGRAM? INFORMATION ON PLAN NEEDS TO BE CONSISTENT. | | | WIRE SIZE IS DETERMINED BY THE OVER CURRENT PROTECTION | | | OF THE MAIN PANEL. PROVIDE CORRECTION AND | | | CLARIFICATIONS.) | | | 2. CORRECTED. | | | 3. CORRECTED. | | | 4. CORRECTED. | | | 5. IF NEW SERVICE IS TO BE INSTALLED, PROVIDE AVAILABLE | | | SHORT CIRCUIT CALCULATION FOR SERVICE INCLUDING | | | INFORMATION FROM THE POWER COMPANY STATING WHAT THE | | | AVAILABLE SHORT CIRCUIT CURRENT IS FOR THE SERVICE TO | | | CONFIRM THE STATED AIC RATING OF THE SERVICE EQUIPMENT | | | IS ADEQUATE. NEC 110.9, 110.10; FBC RE E3606.3 (NOT | | | PROVIDED.) | | | 6. CORRECTED. | | | 7. CORRECTED. | | | | | | END OF COMMENTS. | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, PROVIDE A RESPONSE LETTER ADDRESSING EACH | | | ITEM ALONG WITH THE CITY RESUBMITTAL FORM. | | | ADDITIONALLY, INSERT CORRECTED PAGES INTO THE ORIGINAL | | | SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS. | | | ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD | | | REMAIN IN PACKAGE AND BE MARKED OLD SHEETS. | | | | | | SINCERELY, | | | | | | JOHN PEARSON | | | ELECTRICAL PLANS EXAMINER | | | 561-805-6746 | | | [email protected] | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2020-04-23 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2020-04-23 |
Time |
15:12 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2020-04-23 |
Time |
11:11 |
Sent To |
|
|
| Notes |
| 2020-04-23 15:12:24 | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 | | | 6TH ED, CHAPTER 1. | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 | | | 6TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | FAC = FLORIDA ADMINISTRATIVE CODE | | | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | 1. PLAN STATES THERE IS NO CHANGE TO THE RISER DIAGRAM, | | | BUT THE LOAD TABLE STATES THE UPGRADED ELECTRICAL | | | SERVICE IS 200 AMPS. WHICH IS IT? PROVIDE | | | CLARIFICATION. PROVIDE RISER DIAGRAM OF EXISTING | | | SERVICE. NEC 215.5; WPB FBC 107.2.1 | | | 2. AFCI PROTECTION SHOWN IN NOTE 8 IS NOT CODE | | | COMPLIANT. ALL BRANCH CIRCUITS THAT SUPPLY 120-VOLT, | | | SINGLE-PHASE, 15- AND 20-AMPERE OUTLETS INSTALLED IN | | | KITCHENS, FAMILY ROOMS, DINING ROOMS, LIVING ROOMS, | | | PARLORS, LIBRARIES, DENS, BEDROOMS, SUN-ROOMS, | | | RECREATIONS ROOMS, CLOSETS, HALLWAYS, LAUNDRY AREAS AND | | | SIMILAR ROOMS OR AREAS SHALL BE AFCI PROTECTED. THIS | | | INCLUDES LIGHTING AND POWER OUTLETS AND RECEPTACLES. | | | SOME AREAS REQUIRE BOTH AFCI AND GFCI PROTECTION. | | | PROVIDE CORRECTION. NEC 210.8, 210.12; FBC RE E3902; | | | FBC EX 607.1.1 OR 801.1, 801.2, OR 901.2 AS APPLICABLE. | | | 3. NOTE 19 STATES THAT LIGHTING IN CLOTHES CLOSETS | | | SHALL COMPLY WITH NEC 4/10.8/D/1, WHICH DOESN?T EXIST. | | | PROVIDE CORRECTION OR NOTE OR COMPLIANCE. NEC 410.16; | | | FBC RE E4003.12 | | | 4. PROVIDE TAMPER RESISTANT RECEPTACLES PER CODE. A | | | NOTE WILL SUFFICE. NEC 406.12; FBC RE E4002.14 | | | 5. IF NEW SERVICE IS TO BE INSTALLED, PROVIDE AVAILABLE | | | SHORT CIRCUIT CALCULATION FOR SERVICE INCLUDING | | | INFORMATION FROM THE POWER COMPANY STATING WHAT THE | | | AVAILABLE SHORT CIRCUIT CURRENT IS FOR THE SERVICE TO | | | CONFIRM THE STATED AIC RATING OF THE SERVICE EQUIPMENT | | | IS ADEQUATE. NEC 110.9, 110.10; FBC RE E3606.3 | | | 6. RECEPTACLES INSTALLED TO SERVE THE COUNTER TOP IN | | | KITCHEN, INCLUDING THE ISLAND, REQUIRE GFCI PROTECTION. | | | PROVIDE CORRECTION. NEC 210.8; FBC RE E3902.6 | | | 7. PROVIDE GFCI PROTECTION FOR DISHWASHER. NEC | | | 210.8(D); FBC RE E3902.10 | | | | | | END OF COMMENTS. | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, PROVIDE A RESPONSE LETTER ADDRESSING EACH | | | ITEM ALONG WITH THE CITY RESUBMITTAL FORM. | | | ADDITIONALLY, INSERT CORRECTED PAGES INTO THE ORIGINAL | | | SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS. | | | ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD | | | REMAIN IN PACKAGE AND BE MARKED OLD SHEETS. | | | | | | SINCERELY, | | | | | | JOHN PEARSON | | | ELECTRICAL PLANS EXAMINER | | | 561-805-6746 | | | [email protected] | | | |
|
|
| Review Stop |
HIST |
HISTORICAL |
| Rev No |
2 |
Status |
P |
Date |
2020-05-20 |
|
|
Cont ID |
|
| Sent By |
fmittner |
Date |
2020-05-20 |
Time |
16:26 |
Rev Time |
0.00 |
| Received By |
fmittner |
Date |
2020-05-20 |
Time |
16:26 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
HIST |
HISTORICAL |
| Rev No |
1 |
Status |
P |
Date |
2020-04-15 |
|
|
Cont ID |
|
| Sent By |
fmittner |
Date |
2020-04-15 |
Time |
10:55 |
Rev Time |
0.00 |
| Received By |
fmittner |
Date |
2020-04-15 |
Time |
10:55 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2020-06-11 |
|
|
Cont ID |
|
| Sent By |
lmarchan |
Date |
2020-06-11 |
Time |
08:29 |
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2020-06-10 |
Time |
14:57 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2020-06-03 |
Time |
|
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2020-05-13 |
Time |
10:10 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2020-04-23 |
Time |
|
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2020-04-10 |
Time |
14:13 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
2 |
Status |
P |
Date |
2020-06-15 |
|
|
Cont ID |
|
| Sent By |
lmarchan |
Date |
2020-06-15 |
Time |
15:44 |
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2020-06-11 |
Time |
13:08 |
Sent To |
|
|
| Notes |
| 2020-06-15 15:45:03 | NO FEES DUE PER IMPACT OFFICE. LEM | | 2020-06-11 13:08:31 | 6/11/20 SENT TO IMPACT OFFICE FOR REVIEW. LEM |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
F |
Date |
2020-04-23 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2020-04-23 |
Time |
10:39 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2020-04-23 |
Time |
10:39 |
Sent To |
|
|
| Notes |
| 2020-04-23 10:40:10 | PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE | | | DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS | | | OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST | | | FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE | | | OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL | | | IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME | | | THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM | | | CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS | | | TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF | | | | | | UPON APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE | | | RECEIPT TO YOUR PROJECT OR EMAIL IT TO | | | [email protected] . | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2020-06-10 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2020-06-10 |
Time |
17:04 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2020-06-10 |
Time |
17:04 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2020-05-21 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2020-05-21 |
Time |
13:15 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2020-05-21 |
Time |
11:56 |
Sent To |
|
|
| Notes |
| 2020-05-21 13:16:08 | 1ST REVIEW FBC-2017 MECHANICAL | | | PERMIT-20040233 | | | | | | CODES IN EFFECT: | | | | | | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION | | | 2017 | | | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION | | | 2017 | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH | | | EDITION 2017 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH | | | EDITION 2017 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) PLEASE PROVIDE ANCHORAGE OF APPLIANCES DETAIL. BFC | | | RES M1307.2 | | | | | | 2) PLEASE SHOW KITCHEN VENTILATION. FBC M TABLE | | | 403.3.1.1 | | | | | | 3) PLEASE PROVIDE INFORMATION FOR THE COOKING | | | EQUIPMENT. IS A HOOD BEING USED? IF SO, PLEASE PROVIDE | | | INFORMATION ON THE HOOD, INCLUDING THE CFM?S. FBC FS | | | 107.2.1 | | | | | | 4) PLEASE SHOW THE BATHROOM EXHAUSTS. FBC M TABLE | | | 403.3.1.1 | | | | | | 5) IS AHU IN ATTIC? IF SO PLEASE PROVIDE A DETAIL | | | DRAWING SHOWING THE UNIT WITH THE OVERFLOW PAN WITH THE | | | FLOAT SWITCH. ALSO IDENTIFY CONDENSATE PIPING ALONG | | | WITH PIPE SIZE AND LOCATION OF THE TERMINATION ON THE | | | DRAWING. FBC FS 107.2.1 | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD | | | SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER | | | SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN | | | THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS | | | PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS | | | PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR | | | UPDATED. | | | | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
N |
Date |
2020-04-15 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2020-04-15 |
Time |
16:30 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2020-04-15 |
Time |
16:21 |
Sent To |
|
|
| Notes |
| 2020-04-15 16:31:12 | NO MECHANICAL WORK SHOWN UNDER THIS PROJECT. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2020-04-15 |
|
|
Cont ID |
|
| Sent By |
lcrespo |
Date |
2020-04-15 |
Time |
07:31 |
Rev Time |
0.00 |
| Received By |
lcrespo |
Date |
2020-04-15 |
Time |
07:04 |
Sent To |
|
|
| Notes |
| 2020-04-15 07:31:27 | 04/15/20 REVIEWED FOR CODE COMPLIANCE | | | (PLUMBING/BACKFLOW) | | | | | | BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE | | | COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN | | | PROFESSIONAL, | | | CONTRACTORS OR THEIR REPRESENTATIVES FROM THE | | | RESPONSIBILITY TO COMPLY WITH ALL LOCAL, STATE AND | | | NATIONAL CODES AND STANDARDS IN EFFECT AT THE TIME OF | | | PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK OF EVERY | | | ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM | | | REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES | | | / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO | | | AVOID VOIDING OF THE PERMIT. | | | | | | LUIS A. CRESPO | | | PLUMBING INSPECTOR / PLUMBING PLAN REVIEW | | | AVAILABLE FROM 6:30 AM TO 7:30 / 2:00 PM TO 5:00 PM | | | EMAIL: [email protected] CELL: 561-701-6437 | | | |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
2 |
Status |
P |
Date |
2020-05-26 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2020-05-26 |
Time |
15:40 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2020-05-26 |
Time |
15:40 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2020-04-23 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2020-04-23 |
Time |
10:40 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2020-04-23 |
Time |
10:40 |
Sent To |
|
|
| Notes |
| 2020-04-23 10:40:39 | SEE BUILDING PLAN REVIEW |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
3 |
Status |
P |
Date |
2020-06-10 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2020-06-10 |
Time |
15:04 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2020-06-10 |
Time |
15:04 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
F |
Date |
2020-05-21 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2020-05-21 |
Time |
13:22 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2020-05-21 |
Time |
13:16 |
Sent To |
|
|
| Notes |
| 2020-05-21 13:24:23 | SHEET M-1: THE DESIGNER WILL NEED TO SIGN AND DATE THE | | | DRAWING. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
P |
Date |
2020-04-15 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2020-04-15 |
Time |
16:37 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2020-04-15 |
Time |
16:37 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2020-05-20 |
|
|
Cont ID |
|
| Sent By |
fmittner |
Date |
2020-05-20 |
Time |
16:26 |
Rev Time |
0.00 |
| Received By |
fmittner |
Date |
2020-05-20 |
Time |
16:26 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2020-04-15 |
|
|
Cont ID |
|
| Sent By |
fmittner |
Date |
2020-04-15 |
Time |
10:55 |
Rev Time |
0.00 |
| Received By |
fmittner |
Date |
2020-04-15 |
Time |
10:55 |
Sent To |
|
|
| Notes |
|
|