Plan Review Details - Permit 20040228
Plan Review Stops For Permit 20040228
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2020-05-12 Cont ID  
Sent By rmcdouga Date 2020-05-12 Time 08:12 Rev Time 0.00
Received By rmcdouga Date 2020-05-12 Time 07:21 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-04-16 Cont ID  
Sent By rmcdouga Date 2020-04-16 Time 08:08 Rev Time 0.00
Received By rmcdouga Date 2020-04-16 Time 06:34 Sent To  
Notes
2020-04-16 08:06:38PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THIS POOL APPEARS TO BE AN AMENITY OF A RESIDENTIAL
 GROUP R OCCUPANCY AND MAY BE REQUIRED TO COMPLY THE
 2017 FBC ACCESSIBILITY. SHOW HOW THE NEW POOL WILL
 COMPLY WITH FBC ACCESSIBILITY SECTION 242.2 SWIMMING
 POOLS.
 AT LEAST TWO ACCESSIBLE MEANS OF ENTRY SHALL BE
 PROVIDED FOR SWIMMING POOLS. ACCESSIBLE MEANS OF ENTRY
 SHALL BE SWIMMING POOL LIFTS COMPLYING WITH 1009.2;
 SLOPED ENTRIES COMPLYING WITH 1009.3; TRANSFER WALLS
 COMPLYING WITH 1009.4; TRANSFER SYSTEMS COMPLYING WITH
 1009.5; AND POOL STAIRS COMPLYING WITH 1009.6. AT LEAST
 ONE ACCESSIBLE MEANS OF ENTRY PROVIDED SHALL COMPLY
 WITH 1009.2 OR 1009.3.
  
 EXCEPTIONS:
  
 1. WHERE A SWIMMING POOL HAS LESS THAN 300 LINEAR FEET
 (91 M) OF SWIMMING POOL WALL, NO MORE THAN ONE
 ACCESSIBLE MEANS OF ENTRY SHALL BE REQUIRED PROVIDED
 THAT THE ACCESSIBLE MEANS OF ENTRY IS A SWIMMING POOL
 LIFT COMPLYING WITH 1009.2 OR SLOPED ENTRY COMPLYING
 WITH 1009.3.
  
 2. WAVE ACTION POOLS, LEISURE RIVERS, SAND BOTTOM
 POOLS, AND OTHER POOLS WHERE USER ACCESS IS LIMITED TO
 ONE AREA SHALL NOT BE REQUIRED TO PROVIDE MORE THAN ONE
 ACCESSIBLE MEANS OF ENTRY PROVIDED THAT THE ACCESSIBLE
 MEANS OF ENTRY IS A SWIMMING POOL LIFT COMPLYING WITH
 1009.2, A SLOPED ENTRY COMPLYING WITH 1009.3, OR A
 TRANSFER SYSTEM COMPLYING WITH 1009.5.
  
 3. CATCH POOLS SHALL NOT BE REQUIRED TO PROVIDE AN
 ACCESSIBLE MEANS OF ENTRY PROVIDED THAT THE CATCH POOL
 EDGE IS ON AN ACCESSIBLE ROUTE.
  
 ADVISORY 242.2 SWIMMING POOLS. WHERE MORE THAN ONE
 MEANS OF ACCESS IS PROVIDED INTO THE WATER, IT IS
 RECOMMENDED THAT THE MEANS BE DIFFERENT. PROVIDING
 DIFFERENT MEANS OF ACCESS WILL BETTER SERVE THE VARYING
 NEEDS OF PEOPLE WITH DISABILITIES IN GETTING INTO AND
 OUT OF A SWIMMING POOL. IT IS ALSO RECOMMENDED THAT
 WHERE TWO OR MORE MEANS OF ACCESS ARE PROVIDED, THEY
 NOT BE PROVIDED IN THE SAME LOCATION IN THE POOL.
 DIFFERENT LOCATIONS WILL PROVIDE INCREASED OPTIONS FOR
 ENTRY AND EXIT, ESPECIALLY IN LARGER POOLS.
 ADVISORY 242.2 SWIMMING POOLS EXCEPTION 1. POOL WALLS
 AT DIVING AREAS AND AREAS ALONG POOL WALLS WHERE THERE
 IS NO POOL ENTRY BECAUSE OF LANDSCAPING OR ADJACENT
 STRUCTURES ARE TO BE COUNTED WHEN DETERMINING THE
 NUMBER OF ACCESSIBLE MEANS OF ENTRY REQUIRED.
  
 2) SHOW COMPLIANCE WITH 2017 FBC-ACCESSIBILITY SECTION
 206 ACCESSIBLE ROUTES.
 206.1 GENERAL.
 ACCESSIBLE ROUTES SHALL BE PROVIDED IN ACCORDANCE WITH
 206 AND SHALL COMPLY WITH CHAPTER 4.
  
 206.2.2 WITHIN A SITE.
 AT LEAST ONE ACCESSIBLE ROUTE SHALL CONNECT ACCESSIBLE
 BUILDINGS, ACCESSIBLE FACILITIES, ACCESSIBLE ELEMENTS,
 AND ACCESSIBLE SPACES THAT ARE ON THE SAME SITE.
  
  
 COMMUNITY POOLS THAT ARE ASSOCIATED WITH A PRIVATE
 RESIDENTIAL COMMUNITY THAT DO NOT RECEIVE GOVERNMENTAL
 FINANCIAL ASSISTANCE OR SPONSORSHIP AND ARE LIMITED TO
 THE EXCLUSIVE OF RESIDENTS AND THEIR GUESTS ARE NOT
 COVERED BY THE ADA ACCESSIBILITY REQUIREMENTS,
 INCLUDING PROVISIONS FOR POOL LIFTS OR SLOPED ENTRIES.
 IF A SWIMMING POOL LOCATED IN A RESIDENTIAL COMMUNITY
 IS MADE AVAILABLE TO THE PUBLIC FOR RENTAL OR USE IT IS
 REQUIRED TO COMPLY WITH TITLE II OF THE ADA. SPECIFY ON
 THE PLANS THE FORMER OR SHOW COMPLIANCE WITH THE LATTER
 STATEMENTS. SEE DECLARATORY STATEMENT, DS 2013-011.
  
 NOTE: ALTHOUGH THE POOL MAY NOT HAVE TO APPLY WITH THE
 FLORIDA ACCESSIBILITY CODE, IT WILL STILL NEED NEED TO
 COMPLY WITH FAIR HOUSING.
  
 2) PORTIONS OF THIS PROPERTY IS LOCATED IN A SPECIAL
 FLOOD HAZARD AREA, "AE" WITH A BFE OF 14.1'
 NAVD(INCLUDING THE CITY'S 2 FOOT FREEBOARD). ALL OF THE
 POOL EQUIPMENT LOCATED IN THE SFHA IS REQUIRED TO BE
 LOCATED ABOVE THE BFE OR BE FLOOD PROOFED.
  
 3) WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A
 RESPONSE LETTER ADDRESSING EACH ITEM ALONG WITH THE
 CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2020-05-11 Cont ID  
Sent By jleahy Date 2020-05-11 Time 17:03 Rev Time 0.00
Received By jleahy Date 2020-05-11 Time 16:19 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-04-22 Cont ID  
Sent By jleahy Date 2020-04-22 Time 08:15 Rev Time 0.00
Received By jleahy Date 2020-04-22 Time 07:49 Sent To  
Notes
2020-04-22 08:34:54FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 1) POOL PERMIT VALUE FOR THIS SIZE POOL IS TOO LOW.
 PLEASE SUBMIT A SIGNED CONTRACT FOR THE POOL.
  
 109.3 BUILDING PERMIT VALUATIONS. IF, IN THE OPINION OF
 THE BUILDING OFFICIAL, THE CLAIMED VALUATION OF
 BUILDING, ALTERATION, STRUCTURE, ELECTRICAL, GAS,
 MECHANICAL OR PLUMBING SYSTEMS APPEARS TO BE
 UNDERESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE
 DENIED, UNLESS THE APPLICANT CAN SHOW DETAILED,
 QUANTITY ESTIMATES, AND/OR BONA FIDE SIGNED CONTRACTS
 (EXCLUDING LAND VALUE) TO MEET THE APPROVAL OF THE
 BUILDING OFFICIAL. FOR PERMITTING PURPOSES, VALUATION
 OF BUILDINGS AND SYSTEMS SHALL BE TOTAL REPLACEMENT
 VALUE TO INCLUDE STRUCTURAL, ELECTRIC, PLUMBING,
 MECHANICAL, INTERIOR FINISH, RELATIVE SITE WORK,
 ARCHITECTURAL AND DESIGN FEES, MARKETING COSTS,
 OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY
 INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT
 VALUATION SHALL BE SET BY THE BUILDING OFFICIAL.
  
 2) NEED TO SHOW FEEDER SIZE, PANEL SIZE, PANEL
 SCHEDULE, AND LOCATION OF FEEDER MAIN. 215.5

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2020-04-24 Cont ID  
Sent By Mgonzale Date 2020-04-24 Time   Rev Time 1.00
Received By mgonzale Date 2020-04-24 Time   Sent To I
Notes
2020-04-24 13:28:34APPROVED WITH CONDITIONS:
  
 TO HELP PROTECT FLORIDA?S ENVIRONMENT, THE FOLLOWING
 BEST MANAGEMENT PRACTICES SHOULD BE FOLLOWED WHEN
 DRAINING SWIMMING POOLS OR DISCHARGING FILTER BACKWASH
 INTO THE ENVIRONMENT.
  
 ONLY DRAIN YOUR POOL WHEN NECESSARY. AVOID
 DRAINING/BACKWASHING YOUR POOL DURING PERIODS OF
 DROUGHT AND DURING SIGNIFICANT RAINFALL EVENTS. DO NOT
 DRAIN YOUR POOL WHEN WATERING RESTRICTIONS ARE IN
 PLACE.
  
 BEFORE DRAINING YOUR POOL, ALLOW THE WATER TO STAND FOR
 AT LEAST 48 HOURS AFTER THE LAST ADDITION OF CHLORINE
 OR UNTIL THE FREE CHLORINE RESIDUAL IS < 0.01 MG/L. (IF
 YOU NEED TO DRAIN YOUR POOL QUICKLY, YOU CAN PURCHASE
 CHLORINE-NEUTRALIZING CHEMICALS SUCH AS SODIUM
 THIOSULFATE AT YOUR LOCAL POOL SUPPLY COMPANY.)
  
 TEST THE FREE CHLORINE RESIDUAL BEFORE DISCHARGING. A
 FREE CHLORINE RESIDUAL SHOULD NOT BE DETECTED. THE
 CHLORINE RESIDUAL CAN BE TESTED USING A STANDARD POOL
 TEST KIT. (REFER TO 64E-9.004 (11), F.A.C. FOR
 ADDITIONAL INFORMATION.)
  
 THE WATER SHOULD BE CLEAR AND FREE OF SOLIDS.
  
 THE PH MUST BE BETWEEN 6.5 AND 8.5 BEFORE IT IS
 DISCHARGED.
  
 ALGAECIDES CONTAINING COPPER OR SILVER CAN INTERRUPT
 NORMAL ALGAL AND PLANT GROWTH IN SURFACE WATER BODIES
 AND SHOULD BE USED WITH CAUTION. FOLLOW THE
 MANUFACTURER?S INSTRUCTIONS BEFORE DISCHARGING WATER
 THAT HAS HAD AN ALGAECIDE ADDED RECENTLY.
  
 CONTROL THE RATE OF DISCHARGE ACROSS YOUR PROPERTY TO
 AVOID EROSION AND NUISANCE CONDITIONS FOR NEIGHBORING
 PROPERTIES. NUISANCE CONDITIONS SUCH AS THE CREATION OF
 ODORS, MOSQUITO BREEDING CONDITIONS, OR FLOODING CAN
 OCCUR WHEN WATER IS PONDED FOR A PROLONGED PERIOD.
  
 DIRECT THE DISCHARGE OVER A VEGETATED SURFACE SO THAT
 SOME LEVEL OF FILTRATION CAN OCCUR.
  
 DO NOT DISCHARGE ON AREAS RECENTLY TREATED WITH
 HERBICIDES OR PESTICIDES.
 DISPOSAL TO SANITARY SEWER SYSTEMS:
  
 POOL AND SPA WASTEWATER CAN BE DISCHARGED INTO THE
 SANITARY SEWER SYSTEM WITH PERMISSION OF THE CITY OF
 WPB PUBLIC UTILITY / ENGINEERING DEPT. FOR WASTEWATER
 TREATMENT FACILITY.
  
 AVOID DISCHARGING TO THE SANITARY SEWER SYSTEM DURING
 OR IMMEDIATELY AFTER A SIGNIFICANT RAINFALL EVENT.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-05-15 Cont ID  
Sent By ajones Date 2020-05-15 Time 16:43 Rev Time 0.00
Received By ajones Date 2020-05-07 Time 11:18 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-05-06 Cont ID  
Sent By rmcdouga Date 2020-05-06 Time 09:39 Rev Time 0.00
Received By rmcdouga Date 2020-04-09 Time 09:01 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2020-05-12 Cont ID  
Sent By tklarge Date 2020-05-12 Time 10:38 Rev Time 0.00
Received By tklarge Date 2020-05-12 Time 06:23 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2020-04-20 Cont ID  
Sent By tklarge Date 2020-04-20 Time 15:13 Rev Time 0.00
Received By tklarge Date 2020-04-16 Time 04:48 Sent To  
Notes
2020-04-20 13:44:051) PLANS ARE REQUIRED TO BE DIGITALLY SIGNED AND SEALED
 PER FL. ADMIN. CODE RULE 61G15-23.004, 61G15-23.005.
 2) THE GAS POOL HEATERS SHALL HAVE A MINIMUM 82%
 EFFICIENCY PER 2017 FBC-ENERGY TABLE C404.2.
 3) OUTDOOR HEATED SWIMMING POOLS SHALL BE EQUIPPED WITH
 A VAPOR-RETARDANT COVER ON OR AT THE WATER SURFACE OR A
 LIQUID COVER OR OTHER MEANS PROVEN TO REDUCE HEAT LOSS
 PER 2017 FBC-ENERGY SEC.C404.9.3.
 4) THE PLANS NOTE THE OVERFLOW LINE FOR THE POOL SHALL
 DISCHARGE TO THE STORM SYSTEM AND THE POOL WASTE TO
 DISCHARGE TO THE SANITARY. POOL WATER CANNOT DISCHARGE
 TO THE STORM SYSTEM OR TO THE SANITARY SYSTEM PER CITY
 OF WEST PALM BEACH CODE OF ORDINANCES CHAPTER 90,
 ARTICLE V, SEC. 90-203 (A) & CHAPTER 90, ARTICLE III,
 SEC. 90-126 (5). PERMISSION MUST BE OBTAINED FROM THE
 CITY OF WPB ENGINEERING DEPT.PLEASE CONTACT MANNY
 GONZALEZ IN THE ENGINEERING DEPT. AT 561-494-1085 -FOR
 FURTHER DIRECTION. THIS INFORMATION/DETAIL APPEARS ON
 SEVERAL SHEETS OF THE PLANS AND ALL SHEETS SHALL BE
 REVISED TO COMPLY WITH THE DECISION FROM THE CITY'S
 ENGINEERING DEPARTMENT. REFER TO SHEETS SP-1.06 ( POOL
 PIPING LEGEND NOTES G, I, K ) ET.AL.
 5) SHT. SP-1.07 - DETAIL #11 REFERS TO POOLS WITH FLOOR
 INLETS ONLY. THIS POOL HAS WALL INLETS IN ADDITION TO A
 COUPLE FLOOR INLETS. CLARIFY.
 6) SHT.SP-1.08 - DETAIL #3 - ITEM D1 ON THE POOL PIPING
 ISOMETRIC IS NOT LISTED IN THE LEGENDS ON SP-1.06, OR
 SP-1.10. CLARIFY.
 7) SHT. SP-1.09 SHOWS THE COLLECTOR TANK AS 300 GALLONS
 BUT THE FILTRATION EQUIPMENT TABLE ITEM #27 ON SHT.
 SP-1.10 CALLS OUT THE COLLECTOR TANK AS 525 GALLONS.
 CLARIFY.
 8) A SEPARATE PERMIT IS REQUIRED FOR THE BACKFLOW
 PREVENTION DEVICE ON THE WATER FILL LINE. THE DEVICE
 MUST BE LEAD FREE PER THE CITY OF WPB CROSS CONNECTION
 CONTROL MANUAL.
 9) A SEPARATE GAS PERMIT IS REQUIRED FOR THE
 INSTALLATION OF THE GAS POOL HEATERS.
 10) THE PLANS REFER TO THE CIVIL DRAWINGS FOR THE
 CONTINUATION OF THE OVERFLOW AND POOL WASTE LINES.THERE
 ARE NO CIVIL DRAWINGS WITH THESE PLANS. CLARIFY.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2020-05-14 Cont ID  
Sent By shill Date 2020-05-14 Time 15:58 Rev Time 0.00
Received By shill Date 2020-05-14 Time 15:58 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2020-05-14 Cont ID  
Sent By shill Date 2020-05-14 Time 13:59 Rev Time 0.00
Received By shill Date 2020-05-14 Time 13:59 Sent To  
Notes
2020-05-14 14:02:12****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 DOCUMENTS UPLOADED ON 4/6 WERE NOT DIGITALLY SIGNED.
  
 DOCUMENTS UPLOADED ON 5/8 ARE OK.
  
 TO RESOLVE: EITHER PROVIDE ONE DIGITALLY SIGNED PDF OR
 PROVIDE DIGITALLY SIGNED PAGES FOR THE SHEETS UPLOADED
 ON 4/6.
  
 THIS CAN BE EITHER UPLOADED TO THE SIGNATURE FOLDER, OR
 EMAILED TO ME OR [email protected].
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-04-16 Cont ID  
Sent By rmcdouga Date 2020-04-16 Time 08:08 Rev Time 0.00
Received By rmcdouga Date 2020-04-16 Time 08:08 Sent To  
Notes
2020-04-16 08:09:40PLANS DO NOT HAVE DIGITAL SIGNATURES.

Review Stop Z ZONING
Rev No 2 Status P Date 2020-05-15 Cont ID  
Sent By ajones Date 2020-05-15 Time 16:43 Rev Time 0.00
Received By ajones Date 2020-05-15 Time 16:43 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2020-04-30 Cont ID  
Sent By avann Date 2020-04-30 Time 09:41 Rev Time 0.00
Received By ajones Date 2020-04-30 Time 09:41 Sent To  
Notes
***NONE***