Plan Review Details - Permit 20040217
Plan Review Stops For Permit 20040217
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 3 Status N Date 2020-06-30 Cont ID  
Sent By rmcphers Date 2020-06-30 Time 10:37 Rev Time 0.00
Received By rmcphers Date 2020-06-30 Time 10:37 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status F Date 2020-06-08 Cont ID  
Sent By rmcphers Date 2020-06-08 Time 16:04 Rev Time 0.00
Received By rmcphers Date 2020-06-08 Time 16:04 Sent To  
Notes
2020-06-08 16:05:19PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN PDF
 FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE
 THE PERMIT NUMBER AND ?ASBESTOS? IN THE SUBJECT LINE.
  

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2020-05-15 Cont ID  
Sent By rmcphers Date 2020-05-15 Time 16:23 Rev Time 0.00
Received By rmcphers Date 2020-05-15 Time 16:23 Sent To  
Notes
2020-05-15 16:24:26ASBESTOS ? PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM
 THE CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2020-07-13 Cont ID  
Sent By cthroop Date 2020-07-13 Time 14:53 Rev Time 0.00
Received By cthroop Date 2020-07-13 Time 14:39 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2020-06-30 Cont ID  
Sent By rmcphers Date 2020-06-30 Time 10:29 Rev Time 0.00
Received By rmcphers Date 2020-06-30 Time 10:29 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2020-06-08 Cont ID  
Sent By rmcphers Date 2020-06-08 Time 16:04 Rev Time 0.00
Received By rmcphers Date 2020-06-08 Time 15:54 Sent To  
Notes
2020-06-08 16:01:56SFR ADDITION
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) DRAWING S-0 SHOWS WIND SPEED AT 165MPH SHOULD BE
 170MPH.
 2) PRODUCT APPROVAL PROVIDED FOR THE SINGLE HUNG
 WINDOWS HAS A MAXIMUM WIDTH OF 53 1/8 INCHES WHICH WILL
 NOT WORK FOR THE WINDOW WIDTHS OF 60 INCHES.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2020-05-15 Cont ID  
Sent By rmcphers Date 2020-05-15 Time 16:29 Rev Time 0.00
Received By rmcphers Date 2020-05-15 Time 14:53 Sent To  
Notes
2020-05-15 14:54:55SFR ADDITION
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) DRAWING S-0 SHOWS WIND SPEED AT 165MPH SHOULD BE
 170MPH.
 2) PLEASE PROVIDE COMPLETE (FRONT PAGES AND THE
 INSTALLATION INSTRUCTIONS) MIAMI DADE OR FLORIDA STATE
 PRODUCT APPROVALS FOR THE ROOFING, WINDOW MULL BARS AND
 THE OVERHEAD GARAGE DOOR.
 3) SOME WINDOWS SHOWN ON THE WINDOW SCHEDULE MAY BE MIS
 LABELED AS SINGLE HUNG - WINDOWS W1, W11, W12 ARE TOO
 WIDE TO BE SINGLE HUNG.
 4) FLOOR SHEATHING SHOULD BE SHOWN TO COMPLY WITH FBC
 R503.1
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-04-10 Cont ID  
Sent By rmcphers Date 2020-04-10 Time 11:24 Rev Time 0.00
Received By rmcphers Date 2020-04-09 Time 15:58 Sent To  
Notes
2020-04-10 10:38:25SFR ADDITION
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) DRAWING S-0 SHOWS WIND SPEED AT 165MPH SHOULD BE
 170MPH.
 2) DRAWING S-1 SHOWS -REMOVE EXTERIOR BLOCK WALL AND
 INSTALL BLOCK BOND BEAM - I DON'T THINK A BOND BEAM CAN
 HOLD ITSELF UP - PLEASE REEVALUATE.
 3) PLEASE PROVIDE COMPLETE (FRONT PAGES AND THE
 INSTALLATION INSTRUCTIONS) MIAMI DADE OR FLORIDA STATE
 PRODUCT APPROVALS FOR THE ROOFING AND THE OVERHEAD
 GARAGE DOOR.
 4) PLEASE SHOW THE TRUSS STRAPPING NAILING REQUIREMENTS
 TO MEET THE REQUIRED UPLIFTS.
 5) PLEASE SHOW THE CEILING HEIGHTS FOR THE BATHROOMS
 AND THE OFFICE TO COMPLY WITH FBC R305.
 6) PLEASE SHOW THE LOCATION OF THE REQUIRED ATTIC
 ACCESS TO COMPLY WITH FBC R807.
 7) PLEASE SHOW THE ENCLOSED SPACE UNDER THE STAIRWAY TO
 COMPLY WITH FBC R302.7
 8) PLEASE SHOW THE DOOR FROM GARAGE TO LIVING SPACE TO
 COMPLY WITH FBC R302.5.1
 9) PLEASE SHOW A FOUNDATION SOIL BEARING DESIGN
 CAPACITY. FBC R401.2
 10) PLEASE PROVIDE A SOIL REPORT TO CONFIRM THE SOIL
 BEARING CAPACITY. FBC R401.2
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2020-07-13 Cont ID  
Sent By cthroop Date 2020-07-13 Time 15:06 Rev Time 0.00
Received By cthroop Date 2020-07-13 Time 14:39 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2020-04-16 Cont ID  
Sent By jleahy Date 2020-04-16 Time 09:58 Rev Time 0.00
Received By jleahy Date 2020-04-16 Time 09:58 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 5 Status P Date 2020-07-13 Cont ID  
Sent By cthroop Date 2020-07-13 Time 15:08 Rev Time 0.00
Received By cthroop Date 2020-07-13 Time 14:39 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 4 Status P Date 2020-06-19 Cont ID  
Sent By ccole Date 2020-06-19 Time 10:40 Rev Time 0.00
Received By ccole Date 2020-06-19 Time 07:16 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 3 Status F Date 2020-06-05 Cont ID  
Sent By ccole Date 2020-06-05 Time 11:55 Rev Time 0.00
Received By ccole Date 2020-06-05 Time 09:50 Sent To  
Notes
2020-06-05 12:04:453RD REVIEW FBC RES 2017
 PERMIT 20040217
 6/5/2020
  
 CODES IN EFFECT:
  
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
 PLAN REVIEW RESULTS: DENIED.
  
 COMMENTS FROM THE 2ND REVIEW BELOW WILL BE MARKED AS
 PASSED OR FAILED. SEE NOTES ADDED FOR FAILED COMMENTS.
  
 1) PASSED.
 2) PASSED.
  
 3.) PASSED. LIST THE BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO THE 2017
 FBC-FUEL GAS SECS.401.8, 402.2, AND TABLES 402.4 (1)
 THRU 402.4 (37) OR 2017 FBC-RES. SEC. G2413.3, G2413.4
 AND TABLES G2413.4 (1 ) THROUGH G2413.4 (21).
  
 4.) PASSED SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (GAS METER / MP REGULATOR / LP TANK) TO THE
 MOST REMOTE OUTLET IN THE BUILDING AND / OR SYSTEM PER
 THE 2017 FBC-FUEL GAS SEC.402.4.1, 402.4.2, OR 2017
 FBC-RES. SEC. G 2413.4.1, G2413.4.2.
  
 5.) FAILED SUBMIT CALCULATIONS FOR COMBUSTION AIR.
 PROVIDE VERIFICATION & CALCULATIONS AS TO HOW THE
 REQUIREMENTS ARE BEING MET. PROVIDE THE CODE SECTIONS
 FROM THE GAS CODE THAT YOU ARE USING IN THE DESIGN OF
 THE COMBUSTION AIR REQUIREMENTS PER THE 2017 FBC-FUEL
 GAS CODE SEC.304.1, 614.6 (CLOTHES DRYERS) OR 2017
 FBC-RES. SEC.G 2407.1 AND G2439.4 (CLOTHES DRYERS).
 SECTION G2407.1- MAKEUP AIR NOT PROVIDED FOR THE
 CLOTHES DRYER. DETAIL 4/P1 INDICATES OUTDOOR AIR WHICH
 WOULD REQUIRE AN OPENING OR OPENINGS TO THE EXTERIOR
 PER SECTIONS G2407.6- G2407.7. FBC RES.
  
 6) PASSED
  
 7) FAILED. SUBMIT TWO COPIES OF A DETAIL SHOWING THE
 TYPE OF VENT, LOCATION, SIZE, TERMINATION POINT, HEIGHT
 ABOVE THE ROOF AND ANCHORING DETAILS OF THE GAS VENT(S)
 PER 2017 FBC-FUEL GAS SECS. 502 THRU 505 OR 2017
 FBC-RES. SEC.G2426 THROUGH G2439. THE REVISED DETAIL ON
 P1 DOES NOT SHOW THE METAL FLUE VENT SIZE, TOTAL VENT
 LENGTH AND TERMINATION POINT WITH PROPER TERMINATION
 CAP. PLEASE PROVIDE THE CORRECT RINNAI MODEL NUMBER ON
 THE PLAN AND REVIEW THE VENTING SPECIFICATIONS ON PAGE
 7-8 OF THE MANUFACTURER?S SPECIFICATIONS. THE VENT FLUE
 IS NOT REQUIRED [PER THE SPECS BUT PROPER CLEARANCES
 ARE. PLEASE SHOW COMPLIANCE.
  
 8) PASSED. SUBMIT TWO COPIES OF THE MANUFACTURER'S
 SPECIFICATION SHEETS / INSTALLATION MANUAL FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA 54,
 NFPA 58, AND FBC-2017 FUEL GAS CODE SEC. 402.2, AND
 301.3 OR 2017 FBC-RES. SEC. G2404.3. GAS APPLIANCES
 SHALL BE LISTED AND LABELED. THE INSTALLATION MANUALS
 FOR ALL GAS APPLIANCES / EQUIPMENT SHALL BE ONSITE AT
 THE TIME OF INSPECTION. FGC SEC.305.1, FBC-RES.
 SEC.G2408.1.
  
 9) FAILED. SUBMIT TWO COPIES OF THE APPLICABLE SIZING
 TABLES USED TO SIZE THE GAS SYSTEM OR PLACE A NOTE ON
 THE PLANS/DRAWINGS SPECIFYING WHICH SIZING TABLE(S)
 FROM THE GAS CODE OR OTHER STANDARD THAT WERE USED IN
 THE DESIGN OF THIS GAS SYSTEM. REFER TO THE 2017
 FBC-FUEL GAS SECS. 401.4, 401.8, 402.3, AND TABLES
 402.4 (1) THRU 402.4 (37) OR 2017 FBC-RES. SEC.
 G2413.3, G2412.8, G2413.1, G2413.2, & G2413.3. TABLE
 402.4(9) CALLED OUT ON THE ISO IS FOR SEMI-RIGID COPPER
 TUBING, BUT SCHEDULE 40 METALLIC PIPE IS CALLED OUT FOR
 INSTALLATION. PLEASE NOTE THAT DETAIL 1/P-2 DOES NOT
 SHOW THE GAS LINE RUNS TO THE WATER HEATER, STOVE, AND
 THE DRYER. PLEASE NOTE THAT THE GAS PIPING INSTALLATION
 MAY BE DONE UNDER A SEPARATE PERMIT IF THAT WOULD
 FACILITATE THE ISSUANCE OF THE MAIN PERMIT.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2020-05-21 Cont ID  
Sent By ccole Date 2020-05-21 Time 14:52 Rev Time 0.00
Received By ccole Date 2020-05-21 Time 11:42 Sent To  
Notes
2020-05-21 14:58:242ND REVIEW FBC-2017
 PERMIT 20040217
 5/21/2020
  
 CODES IN EFFECT:
  
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
 PLAN REVIEW RESULTS: DENIED.
  
 COMMENTS FROM THE 1ST REVIEW BELOW WILL BE MARKED AS
 PASSED OR FAILED. SEE NOTES ADDED FOR FAILED COMMENTS.
  
 1) PASSED.
 2) PASSED.
  
 3.) FAILED. LIST THE BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO THE 2017
 FBC-FUEL GAS SECS.401.8, 402.2, AND TABLES 402.4 (1)
 THRU 402.4 (37) OR 2017 FBC-RES. SEC. G2413.3, G2413.4
 AND TABLES G2413.4 (1 ) THROUGH G2413.4 (21). TOTAL BTU
 LOAD OF THE SYSTEM NOT INDICATED.
  
 4.) FAILED. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (GAS METER / MP REGULATOR / LP TANK) TO THE
 MOST REMOTE OUTLET IN THE BUILDING AND / OR SYSTEM PER
 THE 2017 FBC-FUEL GAS SEC.402.4.1, 402.4.2, OR 2017
 FBC-RES. SEC. G 2413.4.1, G2413.4.2. TOTAL DEVELOPED
 LENGTH NOT PROVIDED. A THOUROUGH REVIEW OF PIPE SIZING
 CANNOT BE COMPLETED W/O TOTAL DEVELOPED LENGTH.
  
 5.) FAILED SUBMIT CALCULATIONS FOR COMBUSTION AIR.
 PROVIDE VERIFICATION & CALCULATIONS AS TO HOW THE
 REQUIREMENTS ARE BEING MET. PROVIDE THE CODE SECTIONS
 FROM THE GAS CODE THAT YOU ARE USING IN THE DESIGN OF
 THE COMBUSTION AIR REQUIREMENTS PER THE 2017 FBC-FUEL
 GAS CODE SEC.304.1, 614.6 (CLOTHES DRYERS) OR 2017
 FBC-RES. SEC.G 2407.1 AND G2439.4 (CLOTHES DRYERS).
 REFER TO SECTION G2407.1 EXCEPTION: MAKEUP AIR SHALL BE
 PROVIDED FOR DRYERS WITH EXHAUST CAPACITIES OF 200 CFMS
 OR MORE. PLEASE SUBMIT THE REQUESTED SPECS FOR THE
 DRYER.
  
 6) PASSED
  
 7) FAILED. SUBMIT TWO COPIES OF A DETAIL SHOWING THE
 TYPE OF VENT, LOCATION, SIZE, TERMINATION POINT, HEIGHT
 ABOVE THE ROOF AND ANCHORING DETAILS OF THE GAS VENT(S)
 PER 2017 FBC-FUEL GAS SECS. 502 THRU 505 OR 2017
 FBC-RES. SEC.G2426 THROUGH G2439. THE ISO AND PLAN
 INDICATE THE WH WILL BE LOCATED ON THE EXTERIOR WALL,
 BUT THE DETAIL INDICATES A METAL FLUE UP THROUGH THE
 ROOF. WILL THE FLUE PASS THROUGH THE SOFFIT AND THEN
 THROUGH THE ROOF? PLEASE MODIFY THE DETAIL TO SHOW THE
 ACTUAL LOCATION OF THE WH AND VENT, AND INCLUDE THE
 REQUESTED ANCHORING DETAILS FOR THE FLUE VENT.
  
 8) FAILED. SUBMIT TWO COPIES OF THE MANUFACTURER'S
 SPECIFICATION SHEETS / INSTALLATION MANUAL FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA 54,
 NFPA 58, AND FBC-2017 FUEL GAS CODE SEC. 402.2, AND
 301.3 OR 2017 FBC-RES. SEC. G2404.3. GAS APPLIANCES
 SHALL BE LISTED AND LABELED. THE INSTALLATION MANUALS
 FOR ALL GAS APPLIANCES / EQUIPMENT SHALL BE ONSITE AT
 THE TIME OF INSPECTION. FGC SEC.305.1, FBC-RES.
 SEC.G2408.1. THE REQUESTED SPECIFICATIONS AND
 INSTALLATION MANUALS WERE NOT PROVIDED.
  
 9) FAILED. SUBMIT TWO COPIES OF THE APPLICABLE SIZING
 TABLES USED TO SIZE THE GAS SYSTEM OR PLACE A NOTE ON
 THE PLANS/DRAWINGS SPECIFYING WHICH SIZING TABLE(S)
 FROM THE GAS CODE OR OTHER STANDARD THAT WERE USED IN
 THE DESIGN OF THIS GAS SYSTEM. REFER TO THE 2017
 FBC-FUEL GAS SECS. 401.4, 401.8, 402.3, AND TABLES
 402.4 (1) THRU 402.4 (37) OR 2017 FBC-RES. SEC.
 G2413.3, G2412.8, G2413.1, G2413.2, & G2413.3. TABLE
 402.4(9) CALLED OUT ON THE ISO IS FOR SEMI-RIGID COPPER
 TUBING, BUT SCHEDULE 40 METALLIC PIPE IS CALLED OUT FOR
 INSTALLATION.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2020-04-13 Cont ID  
Sent By tklarge Date 2020-04-13 Time 11:12 Rev Time 0.00
Received By tklarge Date 2020-04-13 Time 11:03 Sent To  
Notes
2020-04-13 11:12:011) SUBMIT TWO COPIES OF AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS THE LENGTH OF ALL CUT SECTIONS OF PIPE
 PER 2017 FBC-FUEL GAS, SECS. 402.4.1, 402.4.2. OR 2017
 FBC-R SEC. G2413.4.1, G2413.4.2.
 2) SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED, ALL
 PIPE SIZES, TYPE OF GAS (LP OR NATURAL). WPB AMEND. TO
 FBC SEC. 107.2.1.
 3.) LIST THE BTU LOAD OF EACH APPLIANCE AND THE TOTAL
 BTU LOAD ON THE SYSTEM. REFER TO THE 2017 FBC-FUEL GAS
 SECS.401.8, 402.2, AND TABLES 402.4 (1) THRU 402.4 (37)
 OR 2017 FBC-RES. SEC. G2413.3, G2413.4 AND TABLES
 G2413.4 (1 ) THROUGH G2413.4 (21).
 4.) SHOW THE DISTANCE FROM THE POINT OF DELIVERY, (GAS
 METER / MP REGULATOR / LP TANK) TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND / OR SYSTEM PER THE 2017
 FBC-FUEL GAS SEC.402.4.1, 402.4.2, OR 2017 FBC-RES.
 SEC. G 2413.4.1, G2413.4.2.
 5.) SUBMIT CALCULATIONS FOR COMBUSTION AIR. PROVIDE
 VERIFICATION & CALCULATIONS AS TO HOW THE REQUIREMENTS
 ARE BEING MET. PROVIDE THE CODE SECTIONS FROM THE GAS
 CODE THAT YOU ARE USING IN THE DESIGN OF THE COMBUSTION
 AIR REQUIREMENTS PER THE 2017 FBC-FUEL GAS CODE
 SEC.304.1, 614.6 (CLOTHES DRYERS) OR 2017 FBC-RES.
 SEC.G 2407.1 AND G2439.4 (CLOTHES DRYERS).
 6) INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM
 ON THE PLAN PER 2017 FBC-FUEL GAS SEC.402.1, 402.4.3
 THRU 402.6 OR 2017 FBC RES. SEC. G2413.2, G2413.4.3.
 7).SUBMIT TWO COPIES OF A DETAIL SHOWING THE TYPE OF
 VENT, LOCATION, SIZE, TERMINATION POINT, HEIGHT ABOVE
 THE ROOF AND ANCHORING DETAILS OF THE GAS VENT(S) PER
 2017 FBC-FUEL GAS SECS. 502 THRU 505 OR 2017 FBC-RES.
 SEC.G2426 THROUGH G2439.
 8.) SUBMIT TWO COPIES OF THE MANUFACTURER?S
 SPECIFICATION SHEETS / INSTALLATION MANUAL FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA 54,
 NFPA 58, AND FBC-2017 FUEL GAS CODE SEC. 402.2, AND
 301.3 OR 2017 FBC-RES. SEC. G2404.3. GAS APPLIANCES
 SHALL BE LISTED AND LABELED. THE INSTALLATION MANUALS
 FOR ALL GAS APPLIANCES / EQUIPMENT SHALL BE ONSITE AT
 THE TIME OF INSPECTION. FGC SEC.305.1, FBC-RES.
 SEC.G2408.1.
 9) SUBMIT TWO COPIES OF THE APPLICABLE SIZING TABLES
 USED TO SIZE THE GAS SYSTEM OR PLACE A NOTE ON THE
 PLANS/DRAWINGS SPECIFYING WHICH SIZING TABLE(S) FROM
 THE GAS CODE OR OTHER STANDARD THAT WERE USED IN THE
 DESIGN OF THIS GAS SYSTEM. REFER TO THE 2017 FBC-FUEL
 GAS SECS. 401.4, 401.8, 402.3, AND TABLES 402.4 (1)
 THRU 402.4 (37) OR 2017 FBC-RES. SEC. G2413.3, G2412.8,
 G2413.1, G2413.2, & G2413.3.
 10) A SEPARATE PERMIT IS REQUIRED FOR THE GAS
 INSTALLATION.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
 NOTE - A COMPLETE AND THOROUGH REVIEW COULD NOT BE DONE
 AT THIS TIME DUE TO THE LACK OF REQUIRED INFORMATION ON
 THE PLANS / DRAWINGS AND ADDITIONAL PLAN REVIEW
 COMMENTS MAY BE GENERATED UPON THE RE-REVIEW OF
 SUBMITTED CORRECTIONS.
  
  

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2020-07-13 Cont ID  
Sent By cthroop Date 2020-07-13 Time 15:09 Rev Time 0.00
Received By cthroop Date 2020-07-02 Time 13:54 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2020-06-30 Cont ID  
Sent By rmcphers Date 2020-06-30 Time 10:39 Rev Time 0.00
Received By rmcphers Date 2020-06-18 Time 16:45 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2020-06-08 Cont ID  
Sent By rmcphers Date 2020-06-08 Time 16:10 Rev Time 0.00
Received By rmcphers Date 2020-05-27 Time 08:22 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2020-05-21 Time   Rev Time 0.00
Received By lmarchan Date 2020-05-05 Time 08:46 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-05-04 Cont ID  
Sent By cpuell Date 2020-05-04 Time 10:36 Rev Time 0.00
Received By cpuell Date 2020-04-07 Time 10:12 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2020-07-07 Cont ID  
Sent By rmcphers Date 2020-07-07 Time 10:54 Rev Time 0.00
Received By lmarchan Date 2020-06-30 Time 10:38 Sent To  
Notes
2020-07-02 16:47:21MU2020-23335 - $1463.48 - PAID
2020-06-18 09:48:076/18/20 EMAILED IMPACT FEE OFFICE FOR REVIEW. LEM

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2020-04-10 Cont ID  
Sent By rmcphers Date 2020-04-10 Time 11:25 Rev Time 0.00
Received By rmcphers Date 2020-04-10 Time 11:24 Sent To  
Notes
2020-04-10 11:26:10PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2020-07-13 Cont ID  
Sent By cthroop Date 2020-07-13 Time 15:05 Rev Time 0.00
Received By cthroop Date 2020-07-13 Time 14:39 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2020-05-06 Cont ID  
Sent By medwards Date 2020-05-06 Time 13:01 Rev Time 0.00
Received By medwards Date 2020-05-06 Time 12:24 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2020-04-09 Cont ID  
Sent By medwards Date 2020-04-09 Time 09:47 Rev Time 0.00
Received By medwards Date 2020-04-09 Time 07:56 Sent To  
Notes
2020-04-09 09:48:061ST REVIEW FBC-2017 MECHANICAL
 PERMIT- 20040217
  
 CODES IN EFFECT:
  
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M-1: MECHANICAL DRAWINGS ARE NOT CONSISTENT
 WITH PAGE 16 OF THE ADTEK ACCULOAD REPORT DUCT RUNS.
 THIS REPORT CALLS FOR DUCTS IN ROOMS THAT EITHER DON?T
 SHOW ANY DUCTS OR ARE MISSING THE MULTIPLE DUCTS IN THE
 SAME ROOM. FBC FS 107.2.1
 2) THE ADTEK ACCULOAD REPORT SPECS OUT DUCT SIZES FOR
 EACH ROOM. PLEASE SHOW DUCT SIZES ON SHEET M-1. FBC FS
 107.2.1
 3) SHEET M-2: YOU ARE SPECIFYING BATHROOM EXHAUST DUCT
 FOR THE DRYER DUCT. PLEASE CORRECT THIS. FBC RES M1502.
 4) SHEET M-1: SPECS. OUT A BATH EXHAUST FAN WITH A 3?
 DUCT DIAMETER, SHEET M-2 SPECS. OUT A 4? TO THE
 TERMINATION POINT. PLEASE BE MAKE CORRECTIONS. FBC FS
 107.2.1
 5) SHEET M-1: INDICATES A LOUVERED DOOR AS THE RETURN
 PATH TO THE AHU, PLEASE SHOW THAT THIS DOES NOT
 RESTRICT THE RETURN PATH. FBC RES M1602.3
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  
  

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 1 Status N Date 2020-05-15 Cont ID  
Sent By rmcphers Date 2020-05-15 Time 16:21 Rev Time 0.00
Received By rmcphers Date 2020-05-15 Time 16:21 Sent To  
Notes
2020-05-15 16:22:17FLOOD ZONE X

Review Stop P PLUMBING
Rev No 5 Status P Date 2020-07-13 Cont ID  
Sent By cthroop Date 2020-07-13 Time 15:08 Rev Time 0.00
Received By cthroop Date 2020-07-13 Time 14:39 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 4 Status P Date 2020-06-19 Cont ID  
Sent By ccole Date 2020-06-19 Time 10:40 Rev Time 0.00
Received By ccole Date 2020-06-19 Time 07:16 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2020-06-05 Cont ID  
Sent By ccole Date 2020-06-05 Time 10:54 Rev Time 0.00
Received By ccole Date 2020-06-05 Time 09:50 Sent To  
Notes
2020-06-05 12:07:12PLUMBING APPROVAL STAMPS AND PROVISOS WILL BE PLACED ON
 THE PLANS AFTER THE FUEL GAS PLANS ARE APPROVED.
 CCOLE -6/5/2020

Review Stop P PLUMBING
Rev No 2 Status F Date 2020-05-21 Cont ID  
Sent By ccole Date 2020-05-21 Time 13:54 Rev Time 0.00
Received By ccole Date 2020-05-21 Time 11:42 Sent To  
Notes
2020-05-21 13:55:202ND REVIEW FBC-2017
 PERMIT 20040217
 5/21/2020
  
 CODES IN EFFECT:
  
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 COMMENTS FROM THE 1ST REVIEW BELOW WILL BE MARKED AS
 PASSED OR FAILED. SEE NOTESIN CAPS FOR FAILED COMMENTS.
  
 1) FAILED. SHT. A-1 - THE WIDTH OF THE SHOWER IN THE
 GUEST BATH ON THE FIRST FLOOR IS SHOWN AS 1' - 11 3/4
 INCHES WIDE. THE MINIMUM WIDTH IS 30 INCHES PER 2017
 FBC- RES. SEC.P2708.1. THE SHOWER CAN BE A MINIMUM OF
 25 INCHES IN WIDTH IF THE CROSS-SECTIONAL AREA IS NOT
 LESS THAN 1300 SQUARE INCHES. CLARIFY. PROVIDE A NOTE
 AT THE SHOWER TO INDICATE A MINIMUM 1300 SQ. IN.
 CROSS-SECTIONAL AREA.
  
 2) FAILED. SHT. A-1 - THE WIDTH OF THE SHOWER IN BATH
 #1 ON THE SECOND FLOOR IS SHOWN AS 2'-0" WIDE. THE
 MINIMUM WIDTH IS 30 INCHES PER 2017 FBC- RES.
 SEC.P2708.1. THE SHOWER CAN BE A MINIMUM OF 25 INCHES
 IN WIDTH IF THE CROSS-SECTIONAL AREA IS NOT LESS THAN
 1300 SQUARE INCHES. CLARIFY. PROVIDE A NOTE AT THE
 SHOWER TO INDICATE A MINIMUM 1300 SQ. IN.
 CROSS-SECTIONAL AREA.
  
 3) FAILED. THE WATER SHUTOFF VALVES FOR THE STACKED
 WASHER/DRYER UNIT SHALL BE PROVIDED WITH ACCESS PER
 2017 FBC-RES. SEC.2903.9.3. PROVIDE A NOTE FOR ACCESS
 ON THE PLUMBING PLANS.
  
 4) PASSED.
  
 5) PASSED.
  
 6) PASSED.
  
 7) PASSED.
  
 8) FAILED. SHT. P-1 - DETAIL #2 - AIR ARRESTORS SHALL
 BE INSTALLED ON THE WATER LINES AT THE WASHING MACHINE
 BOX. 2017 FBC-RES. SEC.P2903.5. THE DRAIN FOR THE
 WASHER DETAIL SHOWS UNIONS. ACCESS SHALL BE PROVIDED TO
 THESE CONNECTIONS OR THEY SHALL BE REMOVED.2017
 FBC-RES. SEC.P2704. PROVIDE NOTE FOR ACCESS TO UNIONS
 AND VALVES.
  
 9) FAILED. THE ELECTRIC PLANS SHOW THE TANKLESS WATER
 HEATER AS BEING ELECTRIC BUT SHT. P-1 SHOWS THE WATER
 HEATER AS BEING GAS. SUBMIT MANUFACTURER'S
 SPECIFICATIONS FOR THE WATER HEATER IF IT IS GAS.WPB
 AMEND. TO FBC SEC. 107.2.1.THE REQUESTED SPECS FOR THE
 WATER HEATER NOT PROVIDED.
  
 10) FAILED. SUBMIT A WATER RISER FOR REVIEW. WPB AMEND.
 TO FBC SEC. 107.3.5.3.THE WATER RISER WAS PROVIDED BUT
 DOES NOT SHOW LOCATIONS DISHWASHER AND ICE MAKER WATER
 SUPPLY LINES, AND LOCATIONS OF AIR ARRESTORS AND
 BACKFLOW PREVENTERS- SECTIONS P2902.2, P2902.4, P2903.5
 FBC RES.
  
 11) PASSED.
  
 12) PASSED.
  
 13) PASSED.
  
 NEW COMMENT:
 1) P2- FIRST FLOOR DRAIN LINES: SHOW REQUIRED CLEANOUT
 LOCATION AT THE JMUNCTION OF THE BUILDING SANITARY
 DRAIN AND THE SANITARY SEWER- SECTION P3005.2.3 FBC
 RES.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2020-04-13 Cont ID  
Sent By tklarge Date 2020-04-13 Time 11:03 Rev Time 0.00
Received By tklarge Date 2020-04-13 Time 06:13 Sent To  
Notes
2020-04-13 11:03:001) SHT. A-1 - THE WIDTH OF THE SHOWER IN THE GUEST BATH
 ON THE FIRST FLOOR IS SHOWN AS 1' - 11 3/4 INCHES WIDE.
 THE MINIMUM WIDTH IS 30 INCHES PER 2017 FBC- RES.
 SEC.P2708.1. THE SHOWER CAN BE A MINIMUM OF 25 INCHES
 IN WIDTH IF THE CROSS-SECTIONAL AREA IS NOT LESS THAN
 1300 SQUARE INCHES. CLARIFY.
 2) SHT. A-1 - THE WIDTH OF THE SHOWER IN BATH #1 ON THE
 SECOND FLOOR IS SHOWN AS 2'-0" WIDE. THE MINIMUM WIDTH
 IS 30 INCHES PER 2017 FBC- RES. SEC.P2708.1. THE SHOWER
 CAN BE A MINIMUM OF 25 INCHES IN WIDTH IF THE
 CROSS-SECTIONAL AREA IS NOT LESS THAN 1300 SQUARE
 INCHES. CLARIFY.
 3) THE WATER SHUTOFF VALVES FOR THE STACCKED
 WASHER/DRYER UNIT SHALL BE PROVIDED WITH ACCESS PER
 2017 FBC-RES. SEC.2903.9.3.
 4) SHOW THE INSIDE DIMENSIONS (L X W ) OF THE SHOWER IN
 THE MASTER BATH. COMPLY WITH 2017 FBC RES. SEC.P2708.1.
 5) THE WIDT OF THE SPACE FOR THE WATER CLOSET ON THE
 2ND FLOOR IS SHAOWN AS 1'- 8 1/2 INCHES. THE MINIMUM
 DISTANCE OF A WATER CLOSET FROM A WALL, VANITY,
 PARTITION, ETC. TO THE CENTERLINE OF THE WATER CLOSET
 IS 15 INCHES. 2017 FBC-RES. SEC.P2705.1 (5).
 6) SHOW THE FIXTURE CLEARANCES OF ALL THE WATER CLOSETS
 ON THE PLANS. COMPLY WITH 2017 FBC-RES. SEC.P2705.1
 (5).
 7) SHT. P-1 - DETAIL #1 - THE SHOWER PAN SHALL BE
 PITCHED 1/4 INCH PER FOOT TO THE DRAIN PERR 2017
 FBC-RES. SEC.P2709.1.
 8) SHT. P-1 - DETAIL #2 - AIR ARRESTORS SHALL BE
 INSTALLED ON THE WATER LINES AT THE WASHING MACHINE
 BOX. 2017 FBC-RES. SEC.P2903.5. THE DRAIN FOR THE
 WASHER DETAIL SHOWS UNIONS. ACCEESS SHALL BE PROVIDED
 TO THESE CONNECTIONS OR THEY SHALL BE REMOVED.2017
 FBC-RES. SEC.P2704.
 9) THE ELECTRIC PLANS SHOW THE TANKLESS WATER HEATER AS
 BEING ELECTRIC BUT SHT. P-1 SHOWS THE WATER HEATER AS
 BEING GAS. SHT.SUBMIT MANUFACTURER'S SPECIFICATIONS FOR
 THE WATER HEATER IF IT IS GAS.WPB AMEND. TO FBC SEC.
 107.2.1.
 10) SUBMIT A WATER RISER FOR REVIEW. WPB AMEND. TO FBC
 SEC. 107.3.5.3.
 11) SHT. P-1 - DETAIL #4 - CALLS OUT AN ELECTRIC
 TANKLESS WATER HEATER BUT THE DETAIL ALSO SHOWS GAS.
 CLARIFY.
 12) SHT. P-1 - THE SOIL STACK FOR THE FIRST FLOOR
 POWDER ROOM AND SECOND FLOOR BATH #2 DOES NOT MEET
 CODE. AS DRAWN, IT VIOLATES 2017 FBC-RES. SECS.P3108.4,
 P3109.2.
 13) THE STACK FOR THE FIRST FLOOR GUEST BATH AND 2ND
 FLOOR MASTER BATH DOES NOT MEET CODE. AS DRAWN, IT
 VIOLATES 2017 FBC-RES. SECS.P3108.4, P3109.2.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  

Review Stop R ROOF PLAN REVIEW
Rev No 4 Status P Date 2020-07-13 Cont ID  
Sent By cthroop Date 2020-07-13 Time 15:09 Rev Time 0.00
Received By cthroop Date 2020-07-13 Time 14:39 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status P Date 2020-06-08 Cont ID  
Sent By rmcphers Date 2020-06-08 Time 16:06 Rev Time 0.00
Received By rmcphers Date 2020-06-08 Time 16:06 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status F Date 2020-05-15 Cont ID  
Sent By rmcphers Date 2020-05-15 Time 16:24 Rev Time 0.00
Received By rmcphers Date 2020-05-15 Time 16:24 Sent To  
Notes
2020-05-15 16:25:30SEE BUILDING PLAN REVIEW

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2020-04-10 Cont ID  
Sent By rmcphers Date 2020-04-10 Time 11:26 Rev Time 0.00
Received By rmcphers Date 2020-04-10 Time 11:26 Sent To  
Notes
2020-04-10 11:27:00PLEASE SEE BUILDING PLAN REVIEW

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 5 Status P Date 2020-07-13 Cont ID  
Sent By cthroop Date 2020-07-13 Time 15:04 Rev Time 0.00
Received By cthroop Date 2020-07-13 Time 14:39 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2020-06-30 Cont ID  
Sent By rmcphers Date 2020-06-30 Time 10:39 Rev Time 0.00
Received By rmcphers Date 2020-06-30 Time 10:38 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2020-06-08 Cont ID  
Sent By rmcphers Date 2020-06-08 Time 16:08 Rev Time 0.00
Received By rmcphers Date 2020-06-08 Time 16:08 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2020-05-06 Cont ID  
Sent By medwards Date 2020-05-06 Time 13:13 Rev Time 0.00
Received By medwards Date 2020-05-06 Time 13:13 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2020-04-09 Cont ID  
Sent By medwards Date 2020-04-09 Time 09:49 Rev Time 0.00
Received By medwards Date 2020-04-09 Time 09:48 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2020-05-12 Cont ID  
Sent By RTHERMID Date 2020-05-12 Time   Rev Time 0.00
Received By rthermid Date 2020-05-12 Time   Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2020-05-04 Cont ID  
Sent By rthermid Date 2020-05-04 Time   Rev Time  
Received By rthermid Date 2020-05-04 Time   Sent To I
Notes
***NONE***