| 2020-04-28 09:21:58 | 2017 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 20040170 |
| | ADD: 2600 N FLAGLER DR. # 706 |
| | CONT: B & A DESIGN BUILDERS |
| | TEL: 561-722-3591 |
| | E-MAIL: BRIAN@ B&ADESIGNBUILDERS.COM |
| | |
| | 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: TUES. APRIL 28TH/ 2020 |
| | ACTION: DENIED |
| | |
| | 1) THE SUBMITTED PLANS DOES NOT HAVE DIGITAL SIGNATURE |
| | AND SEAL. ARCHITECT DIGITAL SIGNING & SEALING PLANS. |
| | 61G1-16.005 PROCEDURES FOR DIGITALLY SIGNING AND |
| | SEALING AND FOR ELECTRONICALLY TRANSMITTING PLANS, |
| | SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS. |
| | |
| | 2) SHEET A2 INDICATES THE CONSTRUCTION TYPE AS TYPE II |
| | WHEREAS THE DESIGN PARAMETERS STATE THE BUILDING TYPE |
| | AS 1-A UNDER WHICH THE BUILDING WAS BUILT (10 STORY |
| | BUILDING). THE PROJECT DATA DOES NOT STATE IF THE |
| | BUILDING IS FIRE SPRINKLERED OR NOT. UNDER TODAY?S CODE |
| | 2017 FBC-B THE CONSTRUCTION TYPE WOULD BE I-B. UNDER |
| | THE FORMER SOUTHERN BUILDING CODE AND 2001 FBC-B THE |
| | BUILDING TYPE WOULD HAVE BEEN II. |
| | |
| | 3) SHEET A2 IN THE NOTES STATES ALL NEW FLOORING AND |
| | FLOOR INSULATION. FLOORING TBD (TO BE DETERMINED). |
| | BEFORE A THROUGH PLAN REVIEW CAN BE COMPLETED THE FLOOR |
| | FINISH MATERIAL MUST BE A KNOWN, TO BE ABLE TO |
| | DETERMINE THE CODE REQUIREMENTS. |
| | FLOOR INSULATION (FBC-B 2017) |
| | FOR TILE, STONE, MARBLE, AND WOOD FLOORING ALL NEED TO |
| | HAVE HAD THE SOUND UNDERLAYMENT TESTED FLOOR ASSEMBLIES |
| | TO THE FOLLOWING STANDARDS AND MEET THE QUALIFICATIONS |
| | LISTED UNDER EACH OF THE STANDARDS FOR A 6 INCH |
| | CONCRETE FLOOR ASSEMBLY/ NO DROPPED CEILING: |
| | PLEASE PROVIDE TEST REPORTS SHOWING COMPLIANCE WITH: |
| | |
| | TYPE I AND II BUILDINGS |
| | 3A) FBC-B 2017 1207.3 STRUCTURE-BORNE SOUND. |
| | FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR |
| | BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA |
| | WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION |
| | CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD |
| | TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492. |
| | |
| | 3B) FBC-B 2017 1207.2 AIR-BORNE SOUND. WALLS, |
| | PARTITIONS AND FLOOR/CEILING ASSEMBLIES SEPARATING |
| | DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR |
| | SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS |
| | (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR |
| | AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E |
| | 90. |
| | |
| | 3C) FLAME SPREAD- FBC-B 2017 603.1. EXCEPTION 2. |
| | INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID |
| | DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED |
| | TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. |
| | FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS |
| | A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL |
| | MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A |
| | MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723. |
| | |
| | 4) THE FLOOR PLAN INDICATES TO RAISE THE DROPPED |
| | CEILINGS IN THE DINING ROOM AND KITCHEN AS HIGH AS |
| | POSSIBLE. THERE IS NO CEILING FRAMING PLAN SHOWING THE |
| | SPAN, THE SIZE OF THE FRAMING MATERIAL, TYPE OF FRAMING |
| | MATERIAL, SPACING C/C, NOR IF THERE IS TO BE STRUCTURAL |
| | SUPPORTS MID-SPAN, ANCHOR TO THE SLAB ABOVE, ANCHOR |
| | EMBEDMENT OR THE TYPE AND THICKNESS OF THE FINISH |
| | MATERIAL. |
| | 2017 FBC-B TABLE 2506.2 ASTM C645, TABLE 2508.1 ASTM |
| | C754, GA-216 OR ASTM C840. |
| | |
| | 5) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE |
| | THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED |
| | DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE |
| | MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS |
| | AND INFORMATION LACKING UNDER THE PRIOR REVIEW. |
| | |
| | |
| | JAMES A. WITMER BN, PX, SFP, CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT |
| | 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 |
| | TEL: 561-805-6717 |
| | |
| | |
| | |