| 2021-04-12 16:58:07 | 04/12/21 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | 1. PLEASE SUBMIT SECONDARY (EMERGENCY) ROOF DRAIN |
| | SYSTEMS THAT IS SIZED IN ACCORDANCE WITH SECTION 1106 |
| | BASED ON THE RAINFALL RATE FOR WHICH THE PRIMARY SYSTEM |
| | IS SIZED. SCUPPERS SHALL BE SIZED TO PREVENT THE DEPTH |
| | OF PONDING WATER FROM EXCEEDING THAT FOR WHICH THE ROOF |
| | WAS DESIGNED AS DETERMINED BY SECTION 1101.7. SCUPPERS |
| | SHALL HAVE AN OPENING DIMENSION OF NOT LESS THAN 4 |
| | INCHES (102 MM) IN HEIGHT AND HAVE AN OPENING WIDTH |
| | EQUAL TO THE CIRCUMFERENCE OF THE ROOF DRAIN REQUIRED |
| | FOR THE AREA SERVED PER THE 2020 FBC SECTION 1108.3 |
| | SIZING OF SECONDARY DRAINS. |
| | |
| | 2. PLEASE REFER TO BUILDING COMMENTS AS WELL. |
| | |
| | WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES. |
| | A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION, |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA |
| | |
| | LUIS A. CRESPO |
| | PLUMBING PLAN EXAMINER / INSPECTOR |
| | EMAIL: [email protected] OFFICE: 561 805-6720 |
| | |