Plan Review Details - Permit 20040056
Plan Review Stops For Permit 20040056
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status P Date 2020-04-10 Cont ID  
Sent By shill Date 2020-04-10 Time 10:05 Rev Time 0.00
Received By shill Date 2020-04-10 Time 10:05 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2020-04-04 Cont ID  
Sent By shill Date 2020-04-04 Time 11:19 Rev Time 0.00
Received By shill Date 2020-04-04 Time 11:19 Sent To  
Notes
2020-04-04 11:20:26PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN PDF
 FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE
 THE PERMIT NUMBER AND ?ASBESTOS? IN THE SUBJECT LINE.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2020-04-19 Cont ID  
Sent By jwitmer Date 2020-04-19 Time 09:15 Rev Time 0.00
Received By jwitmer Date 2020-04-19 Time 09:01 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2020-04-14 Cont ID  
Sent By jwitmer Date 2020-04-14 Time 06:59 Rev Time 0.00
Received By jwitmer Date 2020-04-19 Time 09:01 Sent To  
Notes
2020-04-13 15:51:03ADDRESS IS CORRECT ON BOTH THE APPLICATION AND PLANS.
 JIM WITMER PLAN REVIEW

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2020-04-20 Cont ID  
Sent By jpearson Date 2020-04-20 Time 14:17 Rev Time 0.00
Received By jpearson Date 2020-04-20 Time 14:17 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2020-04-15 Cont ID  
Sent By jpearson Date 2020-04-15 Time 12:49 Rev Time 0.00
Received By jpearson Date 2020-04-15 Time 12:49 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2020-04-27 Cont ID  
Sent By bwoods Date 2020-04-27 Time   Rev Time 0.00
Received By bwoods Date 2020-04-27 Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2020-04-09 Cont ID  
Sent By bwoods Date 2020-04-09 Time   Rev Time 0.00
Received By bwoods Date 2020-04-08 Time   Sent To  
Notes
2020-04-08 14:52:12PERMIT #20040056
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 1.SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE
 INSTALLATION OR MODIFICATION OF THE FIRE SPRINKLER
 SYSTEM AND/OR FIRE ALARM SYSTEM.
  
 2.?FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE DURING
 DEMOLITION AND RENOVATION ACTIVITIES. IN THE EVENT A
 FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR MORE THAN
 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING SHALL BE
 PLACED UNDER A FIRE WATCH.
  
 3.THE NATURE OF THE REMODEL REQUIRES AN EVALUATION OF
 ANY FIRE ALARM SYSTEM EQUIPMENT FOR CODE COVERAGE AND
 COMPLIANCE. ANY REMOVAL AND/OR CONSTRUCTION OF WALLS
 REQUIRE AN EVALUATION OF THE EXISTING EQUIPMENT.
  
 BRITTANY WOODS
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 804-4754
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-04-27 Cont ID  
Sent By lmarchan Date 2020-04-27 Time 13:57 Rev Time 0.00
Received By lmarchan Date 2020-04-15 Time 16:12 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2020-04-15 Time   Rev Time 0.00
Received By lmarchan Date 2020-04-03 Time 13:59 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2020-04-23 Cont ID  
Sent By medwards Date 2020-04-23 Time 11:07 Rev Time 0.00
Received By medwards Date 2020-04-23 Time 11:05 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2020-04-09 Cont ID  
Sent By medwards Date 2020-04-09 Time 13:12 Rev Time 0.00
Received By medwards Date 2020-04-09 Time 11:41 Sent To  
Notes
2020-04-09 13:13:321ST REVIEW FBC-2017 MECHANICAL
 PERMIT-20040056
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 THERE IS NOT ENOUGH INFORMATION IN THIS PACKET TO DO A
 MECHANICAL REVIEW, PLEASE PROVIDE M SHEETS FOR THIS
 REVIEW. FOLLOWING IS A LIST OF INFORMATION WE NEED.
 THIS IS NOT A COMPLETE LIST AS THERE MAY BE QUESTIONS
 ARISE FROM THE NEW INFORMATION WHEN SUBMITTED.
  
 1) PLEASE PROVIDE AN EXISTING MECHANICAL SYSTEM SHEET.
 THIS APPEARS THAT THIS WILL CREATE A NEW TENANT SPACE
 FROM A LARGER AREA. WHAT ARE YOU DOING WITH THE
 EXISTING DUCTWORK AND GRILLES? IS THERE ANYTHING ELSE
 BEING CONDITIONED BY THE EXISTING HP-4 3.5 TON UNIT?
 FBC FS 107.2.1
 2) PLEASE SHOW WHERE THE PROPOSED 24X10 RETURN IS
 COMING FROM. FBC FS 107.2.1
 3) PLEASE SHOW VOLUME DAMPERS. FBC M 603.18
 4) SHEET 2 OF 2: ROOM 106 DOES NOT SHOW A DUCT TO THE
 SUPPLY GRILLE.
 FBC FS 107.2.1
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2020-04-23 Cont ID  
Sent By tklarge Date 2020-04-23 Time 13:11 Rev Time 0.00
Received By tklarge Date 2020-04-23 Time 13:11 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2020-04-06 Cont ID  
Sent By tklarge Date 2020-04-06 Time 05:32 Rev Time 0.00
Received By tklarge Date 2020-04-06 Time 05:23 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2020-04-23 Cont ID  
Sent By medwards Date 2020-04-23 Time 11:09 Rev Time 0.00
Received By medwards Date 2020-04-23 Time 11:09 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2020-04-04 Cont ID  
Sent By shill Date 2020-04-04 Time 08:43 Rev Time 0.00
Received By shill Date 2020-04-04 Time 08:43 Sent To  
Notes
2020-04-04 08:43:46S&S ORIGINALS IN THE LIBRARY WITH ORIGINAL PERMIT
 APPLICATIONS ("NEW PERMITS" BIN)
  