Plan Review Details - Permit 20040015
Plan Review Stops For Permit 20040015
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2020-05-20 Cont ID  
Sent By rmcphers Date 2020-05-20 Time 10:53 Rev Time 0.00
Received By rmcphers Date 2020-05-20 Time 10:53 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-04-10 Cont ID  
Sent By rmcphers Date 2020-04-10 Time 16:19 Rev Time 0.00
Received By rmcphers Date 2020-04-10 Time 13:42 Sent To  
Notes
2020-04-10 16:07:18SFR ALTERATION
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) WINDOWS MARKED "B" FOR THE 2ND FLOOR BEDROOM NEED TO
 MEET EGRESS REQUIREMENTS PER FBC R310.1
 2) DRAWING A-403 SHOWS WINDOWS TO BE REUSED - CANNOT
 REUSE WINDOWS WITHOUT AN UPDATED PRODUCT APPROVAL - FBC
 EXISTING BUILDING 602.2
 3) STRUCTURAL DRAWINGS DO NOT SHOW IN "ADOBE" AS
 ELECTRONICALLY SIGNED BY THE ENGINEER.
 4) YOU HAVE A PRODUCT APPROVAL FOR FIXED GLASS - PLEASE
 SHOW THE LOCATION FOR THE FIXED GLASS ON THE DRAWINGS.
 5) GARDEN WALL NEEDS TO BE ON A SEPARATE BUILDING
 PERMIT - PLEASE PROVIDE A NOTE ON THE DRAWING FOR SUCH
 OR REMOVE IT FROM THE DRAWINGS.
 6) PLEASE PROVIDE A SIGNED AND SEALED COPY OF THE
 SURVEY - NEEDS TO BE ELECTRONICALLY SIGNED BY THE
 SURVEYOR TO BE USED IN ELECTRONIC PLAN REVIEW.
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2020-05-20 Cont ID  
Sent By jleahy Date 2020-05-20 Time 09:21 Rev Time 0.00
Received By jleahy Date 2020-05-20 Time 09:21 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-04-11 Cont ID  
Sent By jleahy Date 2020-04-11 Time 09:21 Rev Time 0.00
Received By jleahy Date 2020-04-11 Time 08:28 Sent To  
Notes
2020-04-11 09:21:36ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 PAGE E-1
  
 1) OUTLET NNEDED BY FRONT OF THE HOUSE.
  
 E3901.7 OUTDOOR OUTLETS.
 NOT LESS THAN ONE RECEPTACLE OUTLET THAT IS READILY
 ACCESSIBLE FROM GRADE LEVEL AND LOCATED NOT MORE THAN 6
 FEET, 6 INCHES (1981 MM) ABOVE GRADE, SHALL BE
 INSTALLED OUTDOORS AT THE FRONT AND BACK OF EACH
 DWELLING UNIT HAVING DIRECT ACCESS TO GRADE LEVEL
  
 PAGE E-2
  
 2) ROOM SHOWING NO WORK MISSING OUTLETS.
  
 E3901.2.1 SPACING.
 RECEPTACLES SHALL BE INSTALLED SO THAT NO POINT
 MEASURED HORIZONTALLY ALONG THE FLOOR LINE OF ANY WALL
 SPACE IS MORE THAN 6 FEET (1829 MM), FROM A RECEPTACLE
 OUTLET. [210.52(A)(1)
  
 PAGE E-5
  
 3) NOTES ON PAGE
  
 #2 ADD KITCHEN AND LAUNDRY TO AREAS SERVED BY AFCI.
 #5 CHANGE TO 75% OF LAMPS.
 THERE IS NO NOTE FOR NM CABLE PLEASE ADD IF YOU ARE
 GOING TO ALLOW.
  
 4) NEED AIC RATING FOR SERVICE CAN BE A NOTE TO THE
 ELECTRICAL CONTRACTOR TO SUPPLY BY FINAL.
  
 E3606.3AVAILABLE SHORT-CIRCUIT CURRENT. SERVICE
 EQUIPMENT SHALL BE SUITABLE FOR THE MAXIMUM FAULT
 CURRENT AVAILABLE AT ITS SUPPLY TERMINALS, BUT NOT LESS
 THAN 10,000 AMPERES. (110.9)
  
 5) PANEL AT MAIN HOUSE NEEDS A GROUNDING ELECTRODE
 SYSTEM INSTALLED.
  
 250.32 BUILDINGS OR STRUCTURES SUPPLIED BY A FEEDER(S)
 OR BRANCH CIRCUIT(S) (A) GROUNDING ELECTRODE.
 BUILDING(S) OR STRUCTURE(S) SUPPLIED BY FEEDER(S) OR
 BRANCH CIRCUIT(S) SHALL HAVE A GROUNDING ELECTRODE
 OR GROUNDING ELECTRODE SYSTEM INSTALLED IN ACCORDANCE
 WI TH PART III OF ARTICLE 250. THE GROUNDING ELECTRODE
 CONDUCTOR(S) SHALL BE CON NECTED IN ACCORDANCE WITH
 250.32(B) OR (C). WHERE THERE IS NO EXISTING GROUNDING
 ELECTRODE, THE GROUNDING ELECTRODE(S) REQUIRED IN
 250.50 SHALL BE INSTALLED
  

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2020-05-26 Cont ID  
Sent By ccole Date 2020-05-26 Time 10:00 Rev Time 0.00
Received By ccole Date 2020-05-26 Time 10:00 Sent To  
Notes
2020-05-26 10:03:18A SEPARATE GAS PERMIT IS REQUIRED FOR INSTALLATION OF
 THE GAS PIPING TO THE NEW EXTERIOR GAS-FIRED WATER
 HEATER- SECTION 107.2.1 WPB.
 CCOLE-5/26/20

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2020-05-26 Time   Rev Time 0.00
Received By lmarchan Date 2020-05-12 Time 14:05 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2020-04-15 Time   Rev Time 0.00
Received By lmarchan Date 2020-04-09 Time 14:49 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2020-05-13 Cont ID  
Sent By medwards Date 2020-05-13 Time 08:09 Rev Time 0.00
Received By medwards Date 2020-05-13 Time 07:31 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2020-04-10 Cont ID  
Sent By medwards Date 2020-04-10 Time 11:35 Rev Time 0.00
Received By medwards Date 2020-04-10 Time 11:34 Sent To  
Notes
2020-04-10 11:35:431ST REVIEW FBC-2017 MECHANICAL
 PERMIT-20040015
  
 CODES IN EFFECT:
  
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M-2: PLEASE PROVIDE THE SIZE AND CFM?S FOR
 KEYED NOTE 1 NEW RETURN GRILLES. FBC RES M1602.2
  
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2020-05-26 Cont ID  
Sent By ccole Date 2020-05-26 Time 09:59 Rev Time 0.00
Received By ccole Date 2020-05-26 Time 08:55 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2020-04-15 Cont ID  
Sent By ccole Date 2020-04-15 Time 08:29 Rev Time 0.00
Received By ccole Date 2020-04-14 Time 17:21 Sent To  
Notes
2020-04-15 08:31:421ST REVIEW FBC-2017 MECHANICAL
 PERMIT #20040015
 4/15/2020
  
 CODES IN EFFECT:
  
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET P1: THE SCOPE OF WORK NOTES INDICATE A NEW
 TANKLESS WATER HEATER INSTALLATION, BUT KEY NOTE #4
 INDICATES THE WATER HEATER IS EXISTING- WHICH IS IT?-
 SECTION 107.2.1 WPB. THE ELECTRICAL PANEL SCHEDULE
 INDICATES AN ELECTRIC WATER HEATER. IF THIS IS A NEW
 INSTALLATION PLEASE PROVIDE AN EQUIPMENT SCHEDULE ON
 THE PLAN INDICATING THE MAKE AND MODEL, AND SUBMIT
 MANUFACTURER?S SPECIFICATIONS AND INSTALLATION
 INSTRUCTIONS- SECTIONS P2801.3, M2004.1, M2005.1 FBC
 RES, & C404.2 FBC EC.
  
 2) P1, P2, & P5: A RECIRCULATION LINE IS INDICATED.
 PLEASE SHOW THE LOCATIONS OF THE RECIRCULATION PUMP AND
 THE CONTROLS FOR THE PUMP- SEE SECTION R403.5.1.1 FBC
 EC. MANUFACTURER?S SPECIFICATIONS AND INSTALLATION
 GUIDELINES SHALL BE SUBMITTED FOR REVIEW OR BE ONSITE
 AT TIME OF INSPECTION.
  
 3) P1, P2, P5: INSULATION IS REQUIRED FOR THE SUPPLY
 AND RETURN LINES OF THE RECIRCULATION SYSTEM, AND FOR
 ALL PIPING OUTSIDE THE CONDITIONED SPACE. PLEASE
 PROVIDE NOTES ON THE PLAN TO SHOW COMPLIANCE- SECTION
 R403.5.3 FBC EC
  
 4) P3, P5: THE NEW TOILET DRAIN LINE MUST CONNECT TO
 THE SANITARY DRAIN UPSTREAM OF THE SOIL STACK
 CONNECTION, OR BE INDIVIDUALLY VENTED- SECTIONS P3108.1
 & P3106.1 FBC RES.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2020-05-13 Cont ID  
Sent By medwards Date 2020-05-13 Time 08:22 Rev Time 0.00
Received By medwards Date 2020-05-13 Time 08:22 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-04-10 Cont ID  
Sent By medwards Date 2020-04-10 Time 11:40 Rev Time 0.00
Received By medwards Date 2020-04-10 Time 11:40 Sent To  
Notes
2020-04-10 11:48:48YOU WILL NEED TO UPLOAD DIGITALLY SIGNED DOCUMENTS WHEN
 RESUBMITTING OR YOU CAN SUBMIT ONE PAPER ORIGINAL AFTER
 ALL REVIEWS HAVE PASSED.
  
  