| Plan Review Stops For Permit 20040015 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2020-05-20 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2020-05-20 |
Time |
10:53 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2020-05-20 |
Time |
10:53 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2020-04-10 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2020-04-10 |
Time |
16:19 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2020-04-10 |
Time |
13:42 |
Sent To |
|
|
| Notes |
| 2020-04-10 16:07:18 | SFR ALTERATION | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected]. | | | | | | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 | | | 1) WINDOWS MARKED "B" FOR THE 2ND FLOOR BEDROOM NEED TO | | | MEET EGRESS REQUIREMENTS PER FBC R310.1 | | | 2) DRAWING A-403 SHOWS WINDOWS TO BE REUSED - CANNOT | | | REUSE WINDOWS WITHOUT AN UPDATED PRODUCT APPROVAL - FBC | | | EXISTING BUILDING 602.2 | | | 3) STRUCTURAL DRAWINGS DO NOT SHOW IN "ADOBE" AS | | | ELECTRONICALLY SIGNED BY THE ENGINEER. | | | 4) YOU HAVE A PRODUCT APPROVAL FOR FIXED GLASS - PLEASE | | | SHOW THE LOCATION FOR THE FIXED GLASS ON THE DRAWINGS. | | | 5) GARDEN WALL NEEDS TO BE ON A SEPARATE BUILDING | | | PERMIT - PLEASE PROVIDE A NOTE ON THE DRAWING FOR SUCH | | | OR REMOVE IT FROM THE DRAWINGS. | | | 6) PLEASE PROVIDE A SIGNED AND SEALED COPY OF THE | | | SURVEY - NEEDS TO BE ELECTRONICALLY SIGNED BY THE | | | SURVEYOR TO BE USED IN ELECTRONIC PLAN REVIEW. | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2020-05-20 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2020-05-20 |
Time |
09:21 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2020-05-20 |
Time |
09:21 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2020-04-11 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2020-04-11 |
Time |
09:21 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2020-04-11 |
Time |
08:28 |
Sent To |
|
|
| Notes |
| 2020-04-11 09:21:36 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | FLORIDA BUILDING CODE 2017 6TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED | | | NFPA 70 2014 EDITION | | | | | | JAKE LEAHY BN, BU, PX | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | PAGE E-1 | | | | | | 1) OUTLET NNEDED BY FRONT OF THE HOUSE. | | | | | | E3901.7 OUTDOOR OUTLETS. | | | NOT LESS THAN ONE RECEPTACLE OUTLET THAT IS READILY | | | ACCESSIBLE FROM GRADE LEVEL AND LOCATED NOT MORE THAN 6 | | | FEET, 6 INCHES (1981 MM) ABOVE GRADE, SHALL BE | | | INSTALLED OUTDOORS AT THE FRONT AND BACK OF EACH | | | DWELLING UNIT HAVING DIRECT ACCESS TO GRADE LEVEL | | | | | | PAGE E-2 | | | | | | 2) ROOM SHOWING NO WORK MISSING OUTLETS. | | | | | | E3901.2.1 SPACING. | | | RECEPTACLES SHALL BE INSTALLED SO THAT NO POINT | | | MEASURED HORIZONTALLY ALONG THE FLOOR LINE OF ANY WALL | | | SPACE IS MORE THAN 6 FEET (1829 MM), FROM A RECEPTACLE | | | OUTLET. [210.52(A)(1) | | | | | | PAGE E-5 | | | | | | 3) NOTES ON PAGE | | | | | | #2 ADD KITCHEN AND LAUNDRY TO AREAS SERVED BY AFCI. | | | #5 CHANGE TO 75% OF LAMPS. | | | THERE IS NO NOTE FOR NM CABLE PLEASE ADD IF YOU ARE | | | GOING TO ALLOW. | | | | | | 4) NEED AIC RATING FOR SERVICE CAN BE A NOTE TO THE | | | ELECTRICAL CONTRACTOR TO SUPPLY BY FINAL. | | | | | | E3606.3AVAILABLE SHORT-CIRCUIT CURRENT. SERVICE | | | EQUIPMENT SHALL BE SUITABLE FOR THE MAXIMUM FAULT | | | CURRENT AVAILABLE AT ITS SUPPLY TERMINALS, BUT NOT LESS | | | THAN 10,000 AMPERES. (110.9) | | | | | | 5) PANEL AT MAIN HOUSE NEEDS A GROUNDING ELECTRODE | | | SYSTEM INSTALLED. | | | | | | 250.32 BUILDINGS OR STRUCTURES SUPPLIED BY A FEEDER(S) | | | OR BRANCH CIRCUIT(S) (A) GROUNDING ELECTRODE. | | | BUILDING(S) OR STRUCTURE(S) SUPPLIED BY FEEDER(S) OR | | | BRANCH CIRCUIT(S) SHALL HAVE A GROUNDING ELECTRODE | | | OR GROUNDING ELECTRODE SYSTEM INSTALLED IN ACCORDANCE | | | WI TH PART III OF ARTICLE 250. THE GROUNDING ELECTRODE | | | CONDUCTOR(S) SHALL BE CON NECTED IN ACCORDANCE WITH | | | 250.32(B) OR (C). WHERE THERE IS NO EXISTING GROUNDING | | | ELECTRODE, THE GROUNDING ELECTRODE(S) REQUIRED IN | | | 250.50 SHALL BE INSTALLED | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
N |
Date |
2020-05-26 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2020-05-26 |
Time |
10:00 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2020-05-26 |
Time |
10:00 |
Sent To |
|
|
| Notes |
| 2020-05-26 10:03:18 | A SEPARATE GAS PERMIT IS REQUIRED FOR INSTALLATION OF | | | THE GAS PIPING TO THE NEW EXTERIOR GAS-FIRED WATER | | | HEATER- SECTION 107.2.1 WPB. | | | CCOLE-5/26/20 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2020-05-26 |
Time |
|
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2020-05-12 |
Time |
14:05 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2020-04-15 |
Time |
|
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2020-04-09 |
Time |
14:49 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2020-05-13 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2020-05-13 |
Time |
08:09 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2020-05-13 |
Time |
07:31 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2020-04-10 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2020-04-10 |
Time |
11:35 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2020-04-10 |
Time |
11:34 |
Sent To |
|
|
| Notes |
| 2020-04-10 11:35:43 | 1ST REVIEW FBC-2017 MECHANICAL | | | PERMIT-20040015 | | | | | | CODES IN EFFECT: | | | | | | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION | | | 2017 | | | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION | | | 2017 | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH | | | EDITION 2017 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH | | | EDITION 2017 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SHEET M-2: PLEASE PROVIDE THE SIZE AND CFM?S FOR | | | KEYED NOTE 1 NEW RETURN GRILLES. FBC RES M1602.2 | | | | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD | | | SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER | | | SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN | | | THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS | | | PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS | | | PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR | | | UPDATED. | | | | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2020-05-26 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2020-05-26 |
Time |
09:59 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2020-05-26 |
Time |
08:55 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2020-04-15 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2020-04-15 |
Time |
08:29 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2020-04-14 |
Time |
17:21 |
Sent To |
|
|
| Notes |
| 2020-04-15 08:31:42 | 1ST REVIEW FBC-2017 MECHANICAL | | | PERMIT #20040015 | | | 4/15/2020 | | | | | | CODES IN EFFECT: | | | | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH | | | EDITION 2017 | | | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION | | | 2017 | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH | | | EDITION 2017 | | | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH | | | EDITION 2017 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SHEET P1: THE SCOPE OF WORK NOTES INDICATE A NEW | | | TANKLESS WATER HEATER INSTALLATION, BUT KEY NOTE #4 | | | INDICATES THE WATER HEATER IS EXISTING- WHICH IS IT?- | | | SECTION 107.2.1 WPB. THE ELECTRICAL PANEL SCHEDULE | | | INDICATES AN ELECTRIC WATER HEATER. IF THIS IS A NEW | | | INSTALLATION PLEASE PROVIDE AN EQUIPMENT SCHEDULE ON | | | THE PLAN INDICATING THE MAKE AND MODEL, AND SUBMIT | | | MANUFACTURER?S SPECIFICATIONS AND INSTALLATION | | | INSTRUCTIONS- SECTIONS P2801.3, M2004.1, M2005.1 FBC | | | RES, & C404.2 FBC EC. | | | | | | 2) P1, P2, & P5: A RECIRCULATION LINE IS INDICATED. | | | PLEASE SHOW THE LOCATIONS OF THE RECIRCULATION PUMP AND | | | THE CONTROLS FOR THE PUMP- SEE SECTION R403.5.1.1 FBC | | | EC. MANUFACTURER?S SPECIFICATIONS AND INSTALLATION | | | GUIDELINES SHALL BE SUBMITTED FOR REVIEW OR BE ONSITE | | | AT TIME OF INSPECTION. | | | | | | 3) P1, P2, P5: INSULATION IS REQUIRED FOR THE SUPPLY | | | AND RETURN LINES OF THE RECIRCULATION SYSTEM, AND FOR | | | ALL PIPING OUTSIDE THE CONDITIONED SPACE. PLEASE | | | PROVIDE NOTES ON THE PLAN TO SHOW COMPLIANCE- SECTION | | | R403.5.3 FBC EC | | | | | | 4) P3, P5: THE NEW TOILET DRAIN LINE MUST CONNECT TO | | | THE SANITARY DRAIN UPSTREAM OF THE SOIL STACK | | | CONNECTION, OR BE INDIVIDUALLY VENTED- SECTIONS P3108.1 | | | & P3106.1 FBC RES. | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | CHRISTOPHER L. COLE | | | PLUMBING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
P |
Date |
2020-05-13 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2020-05-13 |
Time |
08:22 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2020-05-13 |
Time |
08:22 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
F |
Date |
2020-04-10 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2020-04-10 |
Time |
11:40 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2020-04-10 |
Time |
11:40 |
Sent To |
|
|
| Notes |
| 2020-04-10 11:48:48 | YOU WILL NEED TO UPLOAD DIGITALLY SIGNED DOCUMENTS WHEN | | | RESUBMITTING OR YOU CAN SUBMIT ONE PAPER ORIGINAL AFTER | | | ALL REVIEWS HAVE PASSED. | | | | | | |
|
|