Plan Review Details - Permit 20031395
Plan Review Stops For Permit 20031395
Review Stop G GAS REVIEW
Rev No 5 Status P Date 2020-06-17 Cont ID  
Sent By ccole Date 2020-06-17 Time 09:29 Rev Time 0.00
Received By ccole Date 2020-06-16 Time 14:55 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 4 Status F Date 2020-06-03 Cont ID  
Sent By ccole Date 2020-06-03 Time 09:41 Rev Time 0.00
Received By ccole Date 2020-06-03 Time 07:47 Sent To  
Notes
2020-06-03 09:41:164TH REVIEW FBC-2017 RES. FUEL GAS
 PERMIT- 20031395
 6/3/2020
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 THE REQUIRED PLAN CORRECTIONS LISTED BELOW WERE
 DISCUSSED IN A TELEPHONE CALL WITH THE NEW ENGINEER OF
 RECORD- DANIEL RIVEROS PE. MR. RIVEROS WILL CORRECT THE
 PLANS ACCORDINGLY.
  
 1) SHEET G-02, GAS RISER: SHOW THE SIZE OF THE INCOMING
 GAS PIPE TO THE METER AND PROVIDE THE CORRECT SIZING
 TABLE FOR A 2 PSI SYSTEM- TABLE 402.4(5) FBC FG. PLEASE
 NOTE THAT TABLE 402.4(2) IS THE SIZING TABLE FOR LESS
 THAN 2 PSI WHICH WOULD BE THE PRESSURE DOWNSTREAM OF
 THE REGULATOR.
  
 2) G-02, GAS RISER: PROVIDE THE LENGTHS OF THE 1.2" AND
 3/4" BRANCH PIPES SUPPLYING THE RANGE AND THE WATER
 HEATER FROM THE 1" TEE. PLEASE SEE TABLE 402.4(2)- THE
 3/4" BRANCH PIPE TO THE WATER HEATER IS UNDERSIZED AND
 MUST BE INCREASED TO A 1" PIPE.
  
 3) G-02, GAS RISER: THE SPECS FOR THE NAVIEN GAS WATER
 HEATER INDICATE A MAXIMUM 10.5 "WC PRESSURE TO THE
 UNIT. PLEASE PLACE A NOTE BY THE REGULATOR AND SUBMIT
 SPECS- G2408.1 FBC RES.
  
 4) G-01: PLACE A NOTE TO INDICATE THE LENGTH OF THE
 WATER HEATER VENT SHALL NOT EXCEED 60 FT. PER
 MANUFACTURER' S SPECIFICATIONS- SECTION G2408.1 FBC
 RES.
  
 5) PLEASE NOTE THE RELATIVE GAS PIPE SIZING TABLES IN
 THE FBC RES FOR SINGLE FAMILY HOMES: G2413.4(1),
 G2413.4(2), AND G24133.4(5).
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop G GAS REVIEW
Rev No 3 Status F Date 2020-05-06 Cont ID  
Sent By jpearson Date 2020-05-06 Time 08:05 Rev Time 0.00
Received By jpearson Date 2020-05-06 Time 08:05 Sent To  
Notes
2020-05-06 08:05:02JERRY SMITH:
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION
 NFPA 54 = NATIONAL FUEL GAS CODE
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
  
 3RD REVIEW
  
 GAS COMMENTS: DENIED
 AS REQUIRED BY TIM LARGE, THE INFORMATION ON THE
 RESPONSE NARRATIVE WAS TO BE ON THE PLANS. WPB AMEND.
 TO FBC SEC. 107.2.1.
 REGARDING THE SUBMITTED PLANS, THE FOLLOWING IS NOTED:
 1) NEW STOVE APPEARS TO HAVE A TOTAL GAS DEMAND OF
 77,600 BTUS, NOT 43,100 BTUS AS NOTED ON THE RISER
 DIAGRAMS. PER WPB FBC 107.2.1, CORRECT THE DRAWING. IT
 IS NOTED THAT TOTAL DEMAND FOR THE SYSTEM AT 260,000
 BTUS IS ADEQUATE BUT SHOULD REFLECT ACTUAL TOTAL BTU
 DEMAND. PER WPB FBC 107.2.1, CORRECT THE DRAWING.
 2) FBC FG TABLE 402.4(15) NOTED ON PLANS USED FOR
 SIZING CSST TUBING SHALL BE ADDRESSED AS FOLLOWS:
 A. METER IS FOR INLET PRESSURE LESS THAN 2 PSI/PRESSURE
 DROP 0.5 INCH W.C./SPECIFIC GRAVITY 0.60 AND IS NOT THE
 TABLE TO BE USED FOR SIZING THE CSST TUBING IN THE 2
 PSI SYSTEM. PER WPB FBC 107.2.1, PROVIDE CORRECT TABLE
 FOR THE CSST TUBING IN THE 2 PSI SYSTEM (PLEASE NOTE
 THAT PRESSURE DROP IN 2 PSI SYSTEMS IS IN PSI, NOT W.C.
 AND NEEDS TO BE CORRECTLY EXPRESSED ON THE PLANS).
 B. IS EXPRESSED IN EHD (EQUIVALENT HYDRAULIC DIAMETER)
 UNITS, NOT DIAMETER IN INCHES. SIZING ON THE PLANS FOR
 CSST TUBING IS ? INCH. PER WPB FBC 107.2.1, PROVIDE
 CORRECT EHD (EQUIVALENT HYDRAULIC DIAMETER) SIZE.
 3) FBC FG TABLE 402.4(2) NOTED AT THE METER IS FOR
 INLET PRESSURE LESS THAN 2 PSI/PRESSURE DROP 0.5 INCH
 W.C./SPECIFIC GRAVITY 0.60 AND IS NOT THE TABLE TO BE
 USED FOR SIZING THE GALVANIZED PIPING IN THE 2 PSI
 SYSTEM (PLEASE NOTE THAT PRESSURE DROP IN 2 PSI SYSTEMS
 IS IN PSI, NOT WC). PER WPB FBC 107.2.1, PROVIDE
 CORRECT TABLE FOR THE GALVANIZED PIPING IN THE 2 PSI
 SYSTEM (PLEASE NOTE THAT PRESSURE DROP IN 2 PSI SYSTEMS
 IS IN PSI, NOT W.C. AND NEEDS TO BE CORRECTLY EXPRESSED
 ON THE PLANS). TABLE 402.4(2) SHALL BE USED FOR SIZING
 GALVANIZED PIPING DOWNSTREAM OF THE MP REGULATOR AND
 SHALL BE INDICATED AS SUCH WHERE APPLICABLE ON THE
 PLANS. PLEASE NOTE; IF YOUR SYSTEM IS FOR THE HOUSE IS
 LESS THAN 2 PSI THEN IT NEEDS TO BE CLEARLY INDICATED
 ON THE PLANS. THERE IS CONFUSION AND CONFLICTION
 BETWEEN 003 P-ISOMETRIC AND 004 P-GAS ISOMETRIC.
 ADDITIONALLY IF THE SYSTEM IS LESS THAN 2 PSI THEN
 REGULATORS AT THE APPLIANCES SHOULD ONLY BE FURNISHED
 IF REQUIRED BY THE MANUFACTURER.
 4) PER WPB FBC 107.2.1, PROVIDE ON THE PLAN 003
 P-ISOMETRIC DRAWING STATING HOW THE WATER HEATER
 CONDENSATION LINE WILL BE HANDLED. REFER TO RESPONSE
 LETTER DATED 4/24/2020.
 5) PER WPB FBC 107.2.1, PROVIDE DETAIL (ELEVATION) FOR
 VENT TERMINALS. ARE THE VENT TERMINALS UNDER A ROOF?
 VERIFY ALL REQUIRED MINIMUM CLEARANCES AS REQUIRED BY
 FBC FG 503.8 (3) AND AS REQUIRED BY MANUFACTURER.
 MANUFACTURER?S INSTALLATION MANUAL WAS PREVIOUSLY
 REQUESTED BUT AS OF YET HAS NOT BEEN SUBMITTED. SEE HTT
 PS://WWW.AIRSOLUTIONS.CA/IMAGES/PRODUCTS/NAVIEN/PRODUCT
 S/NPE-SERIES/NAVIEN-NPE-INSTALLATION-MANUAL.PDF
 6) IS THE NEW STOVE AN EXACT REPLACEMENT FOR THE OLD
 STOVE? IF NOT, SUBMIT CALCULATIONS FOR COMBUSTION AIR
 FOR THE PER FBC FG.304.1 USING ONE OF THE METHODS
 LISTED IN FBC FG 304.5
 7) IT IS NOTED THAT THERE ARE SEVERAL ISOMETRIC AND
 PLAN VIEW DRAWINGS WITH SOME REDUNDANCY AS WELL AS
 CONFLICTS ACROSS THEM. PLEASE BE SURE TO KEEP ALL
 INFORMATION ON ALL PLANS CONSISTENT TO AVOID CONFUSION
 AND FURTHER COMMENTS THAT COULD DELAY APPROVAL.
 8) ALL UPDATED INFORMATION SHALL BE INDICATED ON THE
 PLANS PER WPB FBC 107.2.1.
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
 ALL PLANS TO BE SIGNED AND SEALED BY THE DESIGNER IN
 ACCORDANCE WITH FAC AND FS.
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-246-0882 MOBILE
  
 20031395 204 GREGORY RD
  
  

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2020-04-28 Cont ID  
Sent By tklarge Date 2020-04-28 Time 11:17 Rev Time 0.00
Received By tklarge Date 2020-04-28 Time 09:34 Sent To  
Notes
2020-04-28 11:09:391) SUBMIT THE MANUFACTURER'S SPECIFICATIONS FOR THE NEW
 STOVE. THE STOVE SHALL BE LISTED AND LABELED PER 2017
 FBC-FUEL GAS SEC.301.3.
 2) THE RESPONSE NARRATIVE STATES THE TANKLESS WATER
 HEATER IS 199,000 BTU'S BUT THE MANUFACTURER'S
 SPECIFICATIONS THAT HAVE BEEN SUBMITTED SHOW 180,000
 BTU'S. CLARIFY.
 3) THE RESPONSE NARRATIVE AND PLANS NOTE THE GAS
 PRESSURE IS 2 PSI WITH A PRESSURE DROP OF 0.6 WATER
 COLUMN. THERE IS NO SUCH SIZING TABLE IN THE GAS CODE.
 CLARIFY.
 4) THE SIZING TABLE NOTED IN THE RESPONSE NARRATIVE FOR
 THE CSST IS FOR A GAS SYSTEM WITH AN INLET PRESSURE OF
 5 PSI. THIS SYSTEM IS NOTED ON THE PLAN AS A 2 PSI
 SYSTEM. CLARIFY.
 5) INDICATE ON THE PLAN WHICH SIZING TABLE IS BEING
 USED FOR THE 2 PSI SYSTEM.
 6) THE INFORMATION ON THE RESPONSE NARRATIVE SHALL BE
 ON THE PLANS. WPB AMEND. TO FBC SEC. 107.2.1.
 7) A PALM BEACH COUNTY PLAN REVISION FORM HAS BEEN
 SUBMITTED WITH THIS PERMIT. CLARIFY WHY THIS FORM HAS
 BEEN SUBMITTED.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  
  
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2020-03-31 Cont ID  
Sent By ccole Date 2020-03-31 Time 11:26 Rev Time 0.00
Received By ccole Date 2020-03-31 Time 10:51 Sent To  
Notes
2020-03-31 11:40:011ST REVIEW FBC-2017 FUEL GAS
 PERMIT #20031395
 3/31/20
  
 CODES IN EFFECT:
  
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 PLEASE NOTE THAT ALL GAS PIPING AND APPLIANCES EITHER
 INSTALLED UNDER THE EXPIRED PERMIT #09010132, OR ANY
 OTHER UNPERMITTED GAS PIPING AND GAS APPLIANCE
 INSTALLATIONS MUST BE ACCOUNTED FOR UNDER THIS NEW GAS
 PERMIT.
  
 1) THE GAS PIPING DRAWING IS INCOMPLETE AND MORE
 INFORMATION IS REQUIRED FOR A FULL REVIEW. PLEASE
 PROVIDE A CLEARLY DRAWN GAS PIPING ISOMETRIC DRAWING
 THAT SHOWS THE FOLLOWING LIST OF ITEMS:
  
 A) TYPES OF PIPING, PIPE DIAMETERS, THE MEASUREMENTS OF
 EACH CUT LENGTH OF PIPE, AND THE TOTAL DEVELOPED LENGTH
 OF THE PIPING FROM THE POINT OF DELIVERY AT THE METER
 TO THE MOST REMOTE OUTLET IN THE BUILDING- SECTION
 G2413.4.1 & G2413.4.2 FBC RES.
  
 B) BTUH LOADS OF THE NEW WATER HEATER, THE EXISTING
 STOVE, AND ANY OTHER EXISTING GAS-FIRED APPLIANCES OR
 EQUIPMENT. SHOW THE LOAD AT EACH APPLIANCE LOCATION AND
 THE TOTAL LOAD ON THE SYSTEM- SECTION G2413.3,
 G24113.4, AND TABLES G2413.4(1) THROUGH G2413.4(21) FBC
 RES.
  
 C) GAS DELIVERY PRESSURE (PSI) OF THE SYSTEM AT THE
 METER AND AT EACH STEPDOWN (MP) REGULATOR- SECTION
 G2413.2 & G2413.3 FBC RES.
  
 D) INDICATE WHICH SIZING TABLES WERE USED FOR THE
 GALVANIZED PIPING AND THE CSST. PLEASE INDICATE THE
 CORRESPONDING EHD (EQUIVALENT HYDRAULIC DIAMETER) OF
 THE CSST AS INDICATED IN THE PIPE SIZING TABLES AND IN
 ACCORDANCE WITH THE CSST MANUFACTURER'S SPECIFICATIONS-
 SEE TABLES G2413.4(1) THROUGH (21).
  
 E) SHOW THE REQUIRED UNIONS FOR THE RIGID PIPING WITHIN
 ONE FOOT OF THE MP REGULATORS- SECTION G2421.2(7) FBC
 RES.
  
 F) ADVISORY: PLEASE NOTE THAT THE REGULATOR FOR THE
 TANKLESS WATER HEATER MUST BE CAPABLE OF REDUCING THE
 PRESSURE DOWN TO 10.5 " WC PER THE SUBMITTED CUT SHEET.
  
 2) SUBMIT A SEPARATE FLOOR PLAN DRAWING THAT SHOWS THE
 LOCATIONS OF ALL NEW AND EXISTING GAS-FIRED APPLIANCES
 ON THE SYSTEM- SECTION G2406.1 & G2406.2 FBC RES. SHOW
 THE GAS VENT AND AIR INLET DUCT RUNS THROUGH THE
 BUILDING AND THEIR TOTAL RUN LENGTHS FOR THE WATER
 HEATER TO THEIR EXTERIOR INLET AND OUTLET LOCATIONS.
 INDICATE THE TYPES AND SIZES OF VENT AND AIR INLET
 PIPINGS AND SUBMIT MANUFACTURER'S INSTALLATION
 INSTRUCTIONS FOR THE WATER HEATER AND THE PIPING-
 SECTION M2005.1 & G2408.1 FBC RES.
  
 3) SHOW HOW ACCESS FOR SERVICE AND REPLACEMENT OF THE
 WEATER HEATER WILL BE PROVIDED, AND THE REQUIRED 30X30
 " LEVEL WORKING SPACE FOR THE APPLIANCE- SECTION
 P2801.4 FBC RES.
  
 4) INDICATE HOW CONDENSATE FOR THE TANKLESS WATER
 HAETER WILL BE PROPERLY DISCHARGED TO THE EXTERIOR OF
 THE BUILDING- M1411.3 FBC RES.
  
 5) IF POSSIBLE PLEASE SUBMIT MANUFACTURER'S
 SPECIFICATIONS AND INSTALLATION INSTRUCTIONS FOR ALL
 UNPERMITED OR EXISTING GAS-FIRED APPLIANCES OR
 EQUIPMENT- SECTION G2408.1 FBC RES.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date   Cont ID  
Sent By   Date 2020-06-17 Time   Rev Time 0.00
Received By lmarchan Date 2020-06-12 Time 11:21 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date   Cont ID  
Sent By   Date 2020-06-03 Time   Rev Time 0.00
Received By lmarchan Date 2020-05-28 Time 16:30 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2020-05-06 Time   Rev Time 0.00
Received By lmarchan Date 2020-04-29 Time 11:01 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-04-28 Cont ID  
Sent By tklarge Date 2020-04-28 Time 11:18 Rev Time 0.00
Received By tklarge Date 2020-04-24 Time 11:41 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2020-03-31 Time   Rev Time 0.00
Received By lmarchan Date 2020-03-30 Time 14:28 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 5 Status P Date 2020-06-17 Cont ID  
Sent By ccole Date 2020-06-17 Time 09:08 Rev Time 0.00
Received By ccole Date 2020-06-16 Time 14:55 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 4 Status F Date 2020-06-03 Cont ID  
Sent By ccole Date 2020-06-03 Time 09:43 Rev Time 0.00
Received By ccole Date 2020-06-03 Time 07:47 Sent To  
Notes
2020-06-03 09:47:13 
 4TH REVIEW FBC-2017 RES. PLUMBING
 PERMIT 20031395
 6/2/2020
  
 CODES IN EFFECT:
  
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) IT APPEARS THE PREVIOUSLY APPROVED PLUMBING PLANS
 HAVE BEEN REMOVED FROM THE PERMIT FILE. PLEASE PROVIDE
 A PLAN INDICATING HOW CONDENSATE FROM THE NEW WATER
 HEATER WILL BE DRAINED AND DISPOSED OF- SECTION 107.2.1
 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2020-05-06 Cont ID  
Sent By jpearson Date 2020-05-06 Time 08:05 Rev Time 0.00
Received By jpearson Date 2020-05-05 Time 11:53 Sent To  
Notes
2020-05-05 11:53:06REVIEWED BY JERRY SMITH.

Review Stop P PLUMBING
Rev No 2 Status P Date 2020-04-28 Cont ID  
Sent By tklarge Date 2020-04-28 Time 11:17 Rev Time 0.00
Received By tklarge Date 2020-04-28 Time 11:17 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2020-03-31 Cont ID  
Sent By ccole Date 2020-03-31 Time 14:07 Rev Time 0.00
Received By ccole Date 2020-03-31 Time 10:51 Sent To  
Notes
2020-03-31 14:17:00 
 1ST REVIEW FBC-2017 PLUMBING
 PERMIT #20031395
 3/31/20
  
 CODES IN EFFECT:
  
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE A FLOOR PLAN DRAWING SHOWING THE LOCARION OF
 THE NEW WATER HEATER- SECTION P2801.4 FBC RES. CLARIFY
 IF THIS A NEW INSTALLATION OR A REPLACEMENT- SECTION
 107.2.1 WPB
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 5 Status P Date 2020-06-17 Cont ID  
Sent By ccole Date 2020-06-17 Time 07:54 Rev Time 0.00
Received By ccole Date 2020-06-17 Time 07:54 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2020-06-03 Cont ID  
Sent By ccole Date 2020-06-03 Time 09:47 Rev Time 0.00
Received By ccole Date 2020-06-03 Time 09:47 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status F Date 2020-05-06 Cont ID  
Sent By jpearson Date 2020-05-06 Time 08:08 Rev Time 0.00
Received By jpearson Date 2020-05-06 Time 08:08 Sent To  
Notes
2020-05-06 08:08:14PER THE WPB AMENDMENTS TO THE FBC, EACH SHEET OF PLAN
 IS REQUIRED TO BE SIGNED BY PERSON RESPONSIBLE FOR THE
 DESIGN. PROVIDE CORRECTION. FS 481.229; WPB FBC 107.1,
 107.2.1, 107.3.5.1.2

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status N Date 2020-04-28 Cont ID  
Sent By tklarge Date 2020-04-28 Time 11:18 Rev Time 0.00
Received By tklarge Date 2020-04-28 Time 11:18 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status N Date 2020-03-31 Cont ID  
Sent By ccole Date 2020-03-31 Time 13:58 Rev Time 0.00
Received By ccole Date 2020-03-31 Time 13:58 Sent To  
Notes
***NONE***