| 2020-04-06 15:23:09 | ALL INFORMATION WAS LOCATED ON THE MASTER PERMIT |
| | 18091185. MECHANICAL REVISIONS APPROVED. |
| 2020-03-31 09:36:28 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT- 20031282 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| | EDITION 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) PLEASE PROVIDE THE ENERGY GAUGE AND THE MANUAL S FOR |
| | THE MECHANICAL SYSTEM USED. SIMULATED PERFORMANCE |
| | ALTERNATIVE. |
| | AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R405 |
| | (GENERATED BY COMMISSION APPROVED SOFTWARE) SHALL BE |
| | SUBMITTED TO THE BUILDING OFFICIAL TO DEMONSTRATE CODE |
| | COMPLIANCE BY SECTION 405. |
| | FBC EC 101.5.1.1.2 |
| | |
| | 2) PROVIDE THE MANUAL S,J AND D CALCULATIONS FOR THIS |
| | INSTALLATION. FBC E R403.7.1EQUIPMENT SIZING. |
| | M1401.3EQUIPMENT AND APPLIANCE SIZING. |
| | |
| | 3) . BALANCED RETURN AIR - M1602.3 |
| | 4) ANCHORAGE OF APPLIANCES - PROVIDE ANCHORING DETAILS |
| | FOR THE OUTDOOR UNIT. M1307.2 |
| | 5) M1507.4LOCAL EXHAUST RATES. |
| | 6) PLEASE PROVIDE THE SPEC. SHEETS FOR ALL EQUIPMENT |
| | USED. LOCAL EXHAUST SYSTEMS SHALL BE DESIGNED TO HAVE |
| | THE CAPACITY TO EXHAUST THE MINIMUM AIR FLOW RATE |
| | DETERMINED IN ACCORDANCE WITH TABLE M1507.4. |
| | MINIMUM REQUIRED LOCAL EXHAUST RATES FOR ONE- AND |
| | TWO-FAMILY DWELLINGS |
| | AREA TO BE EXHAUSTED |
| | EXHAUST RATES |
| | KITCHENS 100 CFM INTERMITTENT OR 25 CFM CONTINUOUS |
| | BATHROOMS-TOILET ROOMS MECHANICAL EXHAUST CAPACITY OF |
| | 50 CFM INTERMITTENT OR 20 CFM CONTINUOUS |
| | |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD |
| | SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER |
| | SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN |
| | THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS |
| | PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS |
| | PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR |
| | UPDATED. |
| | |
| | |