Plan Review Details - Permit 20031359
Plan Review Stops For Permit 20031359
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status P Date 2020-04-29 Cont ID  
Sent By rmcdouga Date 2020-04-29 Time 10:24 Rev Time 0.00
Received By rmcdouga Date 2020-04-29 Time 10:24 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2020-04-02 Cont ID  
Sent By rmcdouga Date 2020-04-02 Time 13:01 Rev Time 0.00
Received By rmcdouga Date 2020-04-02 Time 12:23 Sent To  
Notes
2020-04-02 13:01:46FAILED PLAN REVIEW, COMMERCIAL:
  
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2020-09-02 Cont ID  
Sent By rmcdouga Date 2020-09-02 Time 13:56 Rev Time 0.00
Received By rmcdouga Date 2020-09-02 Time 13:56 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2020-08-18 Cont ID  
Sent By rmcdouga Date 2020-08-18 Time 07:49 Rev Time 0.00
Received By rmcdouga Date 2020-08-18 Time 07:49 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2020-07-08 Cont ID  
Sent By rmcdouga Date 2020-07-08 Time 10:43 Rev Time 0.00
Received By rmcdouga Date 2020-07-08 Time 10:43 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2020-05-11 Cont ID  
Sent By rmcdouga Date 2020-05-11 Time 08:10 Rev Time 0.00
Received By rmcdouga Date 2020-05-11 Time 07:56 Sent To  
Notes
2020-05-11 08:10:29PLAN
 REVIEW COMMENTS
 2ND REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SHOW THE CLEAR FLOOR SPACES AT TOILETS AND
 LAVATORIES, TURNING RADIUS REQUIRED BY SECTION 604 OF
 THE FBC ACCESSIBILITY.
  
 2) PROVIDE BATHROOM ELEVATIONS SHOWING HEIGHTS AND
 LOCATIONS OF ALL ACCESSIBLE WATER CLOSETS, LAVATORIES,
 GRAB BARS AND ALL OTHER BATHROOM ACCESSORIES. FBC
 ACCESSIBILITY CHAPTER 6
  
 3) YOU WILL NEED TO SUBMIT THE REVISED PLANS ALONG WITH
 THE COST BREAKDOWN AND LETTER FROM THE ARCHITECT
 EXPLAINING THE 20 PERCENT DISPROPORTIONATE COST
 EXCEPTION, AS DISCUSSED IN OUR EMAIL CORRESPONDENCES.
 NOTE: THE LETTER FROM THE ARCHITECT WILL NEED TO HAVE
 THE ARCHITECT'S ORIGINAL HANDWRITTEN SIGNATURE ON HIS
 SEAL IF PAPER DOCUMENTS ARE SUBMITTED AND HIS DIGITAL
 SIGNATURE IS REQUIRED IF DOCUMENTS ARE SUBMITTED
 ELECTRONICALLY.
  
 A THOROUGH AND COMPLETE PLAN REVIEW CANNOT BE COMPLETED
 AT THIS TIME DUE TO LACK OF INFORMATION ON THE
 SUBMITTED PLANS. ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED WHEN MORE INFORMATION IS PROVIDED. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-04-02 Cont ID  
Sent By rmcdouga Date 2020-04-02 Time 12:24 Rev Time 0.00
Received By rmcdouga Date 2020-04-02 Time 12:24 Sent To  
Notes
2020-04-02 12:55:56PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SHOW THE CLEAR FLOOR SPACES AT TOILETS AND
 LAVATORIES, TURNING RADIUS REQUIRED BY SECTION 604 OF
 THE FBC ACCESSIBILITY.
  
 2) PROVIDE BATHROOM ELEVATIONS SHOWING HEIGHTS AND
 LOCATIONS OF ALL ACCESSIBLE WATER CLOSETS, LAVATORIES,
 GRAB BARS AND ALL OTHER BATHROOM ACCESSORIES. FBC
 ACCESSIBILITY CHAPTER 6
  
 A THOROUGH AND COMPLETE PLAN REVIEW CANNOT BE COMPLETED
 AT THIS TIME DUE TO LACK OF INFORMATION ON THE
 SUBMITTED PLANS. ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED WHEN MORE INFORMATION IS PROVIDED. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2020-09-02 Cont ID  
Sent By jleahy Date 2020-09-02 Time 14:13 Rev Time 0.00
Received By jleahy Date 2020-09-02 Time 14:13 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2020-07-20 Cont ID  
Sent By jleahy Date 2020-07-20 Time 13:55 Rev Time 0.00
Received By jleahy Date 2020-07-20 Time 13:52 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2020-03-31 Cont ID  
Sent By ppetty Date 2020-03-31 Time 08:57 Rev Time 0.00
Received By ppetty Date 2020-03-31 Time 08:57 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2020-08-27 Cont ID  
Sent By pleduc Date 2020-08-27 Time   Rev Time 0.00
Received By pleduc Date 2020-08-27 Time 10:51 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2020-08-05 Cont ID  
Sent By pleduc Date 2020-08-05 Time   Rev Time 0.00
Received By pleduc Date 2020-08-05 Time 09:52 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2020-06-29 Cont ID  
Sent By pleduc Date 2020-06-29 Time   Rev Time 0.00
Received By pleduc Date 2020-06-29 Time 13:59 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2020-04-02 Cont ID  
Sent By pleduc Date 2020-04-02 Time   Rev Time 0.00
Received By pleduc Date 2020-04-02 Time 14:28 Sent To I
Notes
2020-04-02 14:36:31THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 1) THERE IS NO INDICATION OF THE BATHROOM DOOR HANDLES,
 LOCKS AND HARDWARE.
  
 THE HARDWARE, HANDLES AND LOCKS SHALL COMPLY WITH NFPA
 101, CH 7 MEANS OF EGRESS.
  
 7.2.1.5 LOCKS, LATCHES, AND ALARM DEVICES.
 7.2.1.5.1 DOOR LEAVES SHALL BE ARRANGED TO BE OPENED
 READILY FROM
 THE EGRESS SIDE WHENEVER THE BUILDING IS OCCUPIED.
 7.2.1.5.2* THE REQUIREMENT OF 7.2.1.5.1 SHALL NOT APPLY
 TO DOOR
 LEAVES OF LISTED FIRE DOOR ASSEMBLIES AFTER EXPOSURE TO
 ELEVATED
 TEMPERATURE IN ACCORDANCE WITH THE LISTING, BASED ON
 LABORATORY
 FIRE TEST PROCEDURES.
 7.2.1.5.3 LOCKS, IF PROVIDED, SHALL NOT REQUIRE THE USE
 OF A KEY, A
 TOOL, OR SPECIAL KNOWLEDGE OR EFFORT FOR OPERATION FROM
 THE EGRESS
 SIDE.
 7.2.1.5.4 THE REQUIREMENTS OF 7.2.1.5.1 AND 7.2.1.5.3
 SHALL NOT
 APPLY WHERE OTHERWISE PROVIDED IN CHAPTERS 18 THROUGH
 23.
  
 7.2.1.5.10* A LATCH OR OTHER FASTENING DEVICE ON A DOOR
 LEAF SHALL
 BE PROVIDED WITH A RELEASING DEVICE THAT HAS AN OBVIOUS
 METHOD OF
 OPERATION AND THAT IS READILY OPERATED UNDER ALL
 LIGHTING CONDITIONS.
 7.2.1.5.10.1 THE RELEASING MECHANISM FOR ANY LATCH
 SHALL BE
 LOCATED AS FOLLOWS:
 (1) NOT LESS THAN 34 IN. (865 MM) ABOVE THE FINISHED
 FLOOR FOR
 OTHER THAN EXISTING INSTALLATIONS
 (2) NOT MORE THAN 48 IN. (1220 MM) ABOVE THE FINISHED
 FLOOR
 7.2.1.5.10.2 THE RELEASING MECHANISM SHALL OPEN THE
 DOOR LEAF
 WITH NOT MORE THAN ONE RELEASING OPERATION, UNLESS
 OTHERWISE
 SPECIFIED IN 7.2.1.5.10.3, 7.2.1.5.10.4, OR
 7.2.1.5.10.6.
  
 PLEASE REVIEW AND ENSURE COMPLIANCE.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2020-09-17 Cont ID  
Sent By jgomez Date 2020-09-17 Time 11:13 Rev Time 0.00
Received By jgomez Date 2020-09-17 Time 11:12 Sent To  
Notes
2020-09-17 11:13:55PLAN SUBMITTED ON 09/11/2020 WAS ALREADY SUBMITTED AND
 APPROVED. JG.

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2020-09-17 Cont ID  
Sent By jgomez Date 2020-09-10 Time 11:12 Rev Time 0.00
Received By jgomez Date 2020-09-10 Time 14:26 Sent To  
Notes
2020-09-10 14:26:29CONTRACTOR DROPPED ORIGINAL DRAWINGS. JG.

Review Stop I INCOMING/PROCESSING
Rev No 5 Status P Date 2020-09-02 Cont ID  
Sent By jleahy Date 2020-09-02 Time 14:13 Rev Time 0.00
Received By jleahy Date 2020-08-26 Time 10:26 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2020-08-18 Cont ID  
Sent By rmcdouga Date 2020-08-18 Time 07:59 Rev Time 0.00
Received By rmcdouga Date 2020-08-04 Time 13:54 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2020-07-20 Cont ID  
Sent By jleahy Date 2020-07-20 Time 13:55 Rev Time 0.00
Received By jleahy Date 2020-06-26 Time 08:25 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2020-05-12 Time   Rev Time 0.00
Received By jgomez Date 2020-04-30 Time 10:13 Sent To  
Notes
2020-05-08 10:14:20CONVERTED TO DIGITAL. JG.
2020-05-04 14:41:4305/04/2020 SENT TO TEQUESTA FOR SCANNING. PLANS WILL BE
 UPLOADED TO PROJECTDOX ONCE THEY ARE SCANNED. JG.
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-04-02 Cont ID  
Sent By shill Date 2020-04-02 Time 16:48 Rev Time 0.00
Received By shill Date 2020-03-27 Time 09:58 Sent To  
Notes
2020-03-30 09:58:42B14

Review Stop P PLUMBING
Rev No 5 Status P Date 2020-08-27 Cont ID  
Sent By ccole Date 2020-08-27 Time 10:46 Rev Time 0.00
Received By ccole Date 2020-08-27 Time 07:25 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 4 Status F Date 2020-08-07 Cont ID  
Sent By ccole Date 2020-08-07 Time 17:13 Rev Time 0.00
Received By ccole Date 2020-08-07 Time 16:07 Sent To  
Notes
2020-08-07 17:14:314TH REVIEW FBC-2017 PLUMBING
 PERMIT #2001359
 8/7/2020
  
 CODES IN EFFECT:
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET A-1: THE DOOR TO THE WOMEN'S TOILET ROOM SHALL
 NOT SWING INTO THE CLEAR FLOOR SPACE OF THE LAVATORY
 PER SECTION 603.2.3 FBC ACC UNLESS THE DRAWING IS
 REVISED TO SHOW COMPLIANCE WITH EXCEPTION 2.
  
 2) A-1: SHOW THE CLEAR FLOOR SPACE DIAGRAM AND
 DIMENSIONS FOR THE URINAL- SECTION 605.3.
  
 3) A-1: REFER TO SECTION AND FIGURE 605.2 AND SHOW THE
 RIM HEIGHT AND THE DEPTH OF THE ACCESSIBLE URINAL.
  
 4) A-1: KNEE AND TOE CLEARANCES FOR THE LAVATORY SINK
 NOT SHOW- SECTIONS 606.2, 305 & 306.
  
 5) A-1: REFER TO FIGURES 604.5.1 & 604.5.2 AND SHOW THE
 CORRECT LENGTHS AND SPACINGS OF THE GRAB BARS.
  
 6) A-1: REFER TO FIGURE 604.7 FOR CORRECT POSITIONING
 OF THE TOILET PAPER DISPENSER.
  
 7) A-1, TANKLESS WATER HEATER: A) SHOW THE LOCATION OF
 THE WATER HEATER ON THE PLAN AND INDICATE HOW ACCESS
 WILL BE PROVIDED- SECTION 501.4 FBC P. B) PROVIDE THE
 MAKE AND MODEL AND GPM FLOW CAPACITY- TABLE 604.3. C)
 SUBMIT MANUFACTURER'S SPECIFICATIONS- SECTION 502.1.
  
 8) ME1: THE PREVIOUS REVIEW COMMENTS REQUIRING TEMPERED
 WATER AT THE LAVATORIES WAS NOT ADDRESSED- REFER TO
 SECTIONS 416.5 & 607.1.2 FBC P: TEMPERED WATER MAY BE
 DELIVERED BY THE WATER HEATER IF THE UNIT IS EQUIPPED
 WITH A WATER TEMPERATURE LIMITING DEVICE THAT CONFORMS
 TO ASSE 1070 AND SHALL LIMIT THE TEMPERED WATER TO A
 MAXIMUM OF 110 DEGREES F. OTHERWISE A SEPARATE DEVICE
 MEETING COMPLIANCE SHALL BE INSTALLED.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 3 Status F Date 2020-07-09 Cont ID  
Sent By ccole Date 2020-07-09 Time 11:26 Rev Time 0.00
Received By ccole Date 2020-07-08 Time 16:24 Sent To  
Notes
2020-07-09 11:29:36 
 3RD REVIEW FBC-2017 PLUMBING
 PERMIT #2001359
 5/12/20
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET A1: THE PLAN SHOWS ONLY ONE OF THE TWO ALTERED
 TOILET ROOMS BEING MADE ACCESSIBLE. REFER TO SECTIONS
 202.3 AND 213.1 FBC ACC WHICH REQUIRES EACH ALTERED
 TOILET ROOM TO MEET COMPLIANCE. THE ARCHITECT OF RECORD
 HAS SUBMITTED A REQUEST BASED ON DISPROPORTIONATE COSTS
 TO PROVIDE ONLY ONE ACCESSIBLE UNISEX TOILET ROOM. THE
 PROPOSED PLANS, HOWEVER INDICATE DEMOLITION AND
 RECONSTRUCTION OF TWO TOILET ROOMS. BASED ON THE CODE
 SECTIONS LISTED ABOVE, EACH ALTERED TOILET ROOM SHALL
 BE MADE ACCESSIBLE. DISPROPORTIONAL COSTS TO PROVIDE
 ONE ACCESSIBLE TOILET ROOM WOULD NOT BE APPLICABLE IN
 THIS SPECIFIC CASE- SECTIONS 202.4.1 & 202.4.2 FBC ACC.
  
 2) SHEET A1: PLEASE PROVIDE ENLARGED DIMENSIONED
 DRAWINGS OF THE ALTERED TOILET ROOM WITH THE URINAL TO
 SHOW COMPLIANCE WITH SECTION 213.2 FBC ACC. THE
 ENLARGED DRAWINGS SHALL SHOW:
 A) CLEAR FLOOR SPACE FOR THE WATER CLOSET- SECTION
 604.3 FBC ACC.
 B) CLEAR FLOOR SPACE FOR THE LAVATORY- SECTION 606.2.
 C) TURNING SPACE DIAMETER IN THE TOILET ROOM- SECTION
 304.3.
 D) CENTERLINE OF THE WATER CLOSET FROM THE SIDE WALL OR
 PARTITION- SECTION 604.2.
 E) HEIGHT OF THE WATER CLOSET SEAT FROM THE FINISHED
 FLOOR- SECTION 604.4.
 F) HEIGHT OF THE FRONT RIM OF THE LAVATORY FROM THE
 FINISHED FLOOR- SECTION 606.3
 G) KNEE AND TOE CLEARANCES FOR THE LAVATORY- SECTION
 306.
 H) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB
 BARS- SECTIONS 604.5 AND 609.4
 I) LOCATION OF THE WATER CLOSET FLUSH CONTROL- SECTION
 604.6.
 J) LOCATION, CLEARANCE, AND MOUNTING HEIGHT FOR THE
 TOILET PAPER DISPENSER- SECTION 604.7.
 K) HEIGHT OF THE MIRROR FROM THE FINISHED FLOOR TO THE
 BOTTOM OF THE REFLECTIVE SURFACE- SECTION 603.3
 3) A1: MISSING DETAILS FOR THE ENLARGED ACCESSIBLE
 TOILET ROOM DRAWING:
 A) KNEE AND TOE CLEARANCES FOR THE LAVATORY- SECTION
 306.
 B) HEIGHT OF THE MIRROR FROM THE FINISHED FLOOR TO THE
 BOTTOM OF THE REFLECTIVE SURFACE- SECTION 603.3
 C) MOUNTING HEIGHTS OF GRAB BARS- SECTION 609.4
 D) MOUNTING HEIGHT OF THE TOILET PAPER DISPENSER-
 SECTION 604.7.
  
 3) A1: CONCERNING THE TOILET ROOM WITH THE URINAL
 PLEASE NOTE:
 A) THE URINAL SHALL NOT BE LOCATED IN THE REQUIRED
 CLEAR FLOOR SPACE OF THE WATER CLOSET- SECTION 604.3.2
 FBC ACC.
 B) THE WATER CLOSET SHALL OCCUPY A SEPARATE COMPARTMENT
 WITH WALLS OR PARTITIONS AND A DOOR. EXCEPTION: NOT
 REQUIRED IN A SINGLE-OCCUPANT TOILET ROOM WITH A
 LOCKABLE DOOR- SECTION 405.3.4 FBC P.
  
 4) A2: THE PREVIOUS REVIEW COMMENT #6 REQUIRING
 TEMPERED WATER AT THE LAVATORIES WAS NOT ADDRESSED-
 REFER TO SECTIONS 416.5 FBC P. REFER TO SECTION
 607.1.2: TEMPERED WATER SHALL BE SUPPLIED THROUGH A
 WATER TEMPERATURE LIMITING DEVICE THAT CONFORMS TO ASSE
 1070 AND SHALL LIMIT THE TEMPERED WATER TO A MAXIMUM OF
 110 DEGREES F.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2020-05-12 Cont ID  
Sent By ccole Date 2020-05-12 Time 13:42 Rev Time 0.00
Received By ccole Date 2020-05-12 Time 13:27 Sent To  
Notes
2020-05-12 13:49:48 
 2ND REVIEW FBC-2017 PLUMBING
 PERMIT #2001359
 5/12/20
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
 COMMENTS FROM THE 1ST REVIEW HAVE NOT BEEN ADDRESSED-
 PLEASE COMPLY.
  
 1) SHEET A1: PLEASE PROVIDE ENLARGED DIMENSIONED
 DRAWINGS OF THE NEW MEN'S AND WOMEN'S TOILET ROOMS TO
 SHOW COMPLIANCE WITH SECTION 213.2 FBC ACC. THE
 ENLARGED DRAWINGS SHALL SHOW:
 A) CLEAR FLOOR SPACES FOR THE WATER CLOSETS- SECTION
 604.3 FBC ACC.
 B) CLEAR FLOOR SPACES FOR THE LAVATORIES- SECTION
 606.2.
 C) TURNING SPACES IN THE TOILET ROOMS- SECTION 304.3.
 D) CENTERLINES OF THE WATER CLOSETS FROM THE SIDE WALLS
 OR PARTITIONS- SECTION 604.2.
 E) HEIGHTS OF THE WATER CLOSET SEATS FROM THE FINISHED
 FLOORS- SECTION 604.4.
 F) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB
 BARS- SECTION 604.5
 G) LOCATIONS OF FLUSH CONTROLS- SECTION 604.6.
 H) LOCATIONS, CLEARANCES, AND MOUNTING HEIGHTS FOR
 DISPENSERS- SECTION 604.7
  
 2) A1, MENS TOILET ROOM
 A) THE URINAL SHALL NOT BE LOCATED IN THE REQUIRED
 CLEAR FLOOR SPACE OF THE WATER CLOSET- SECTION 604.3.2.
 B) THE WATER CLOSET SHALL OCCUPY A SEPARATE COMPARTMENT
 WITH WALLS OR PARTITIONS AND A DOOR. EXCEPTION: NOT
 REQUIRED IN A SINGLE-OCCUPANT TOILET ROOM WITH A
 LOCKABLE DOOR- SECTION 405.3.4
 C) PROVIDE URINAL PARTITION DETAILS- SECTION 405.3.5
 FBC P.
  
 3) A1, WOMEN'S TOILET ROOM: THE WHEELCHAIR ACCESSIBLE
 TOILET COMPARTMENT SHALL CONTAIN AN ACCESSIBLE LAVATORY
 WITHIN IT, WHICH MUST BE AT LEAST 19 INCHES WIDE BY 17
 INCHES DEEP, NOMINAL SIZE, AND WALL-MOUNTED. THE
 LAVATORY SHALL BE MOUNTED SO AS NOT TO OVERLAP THE
 CLEAR FLOOR SPACE AREAS REQUIRED BY SECTION 604 FOR THE
 WHEELCHAIR ACCESSIBLE TOILET COMPARTMENT AND SHALL
 COMPLY WITH SECTION 606. PLEASE NOTE THAT FLORIDA LAW,
 SECTION 553.504(5), F.S., STIPULATES THAT "...REQUIRED
 BATHING ROOMS AND TOILET ROOMS IN NEW CONSTRUCTION
 SHALL BE DESIGNED AND CONSTRUCTED..." WITH AN
 ACCESSIBLE LAVATORY IN THE WHEELCHAIR ACCESSIBLE
 COMPARTMENT AND THE WATER CLOSET LOCATED IN A CORNER
 DIAGONAL TO THE DOOR.
  
 4) A1: PROVIDE A PLUMBING FIXTURE SCHEDULE ON THE PLAN-
 SECTIONS 416, 419, & 420 FBC P.
  
 5) A1: THE URINAL CANNOT CONNECT TO THE HORIZONTAL WET
 VENT FOR THE TOILET FIXTURES AND SHALL BE INDIVIDUALLY
 VENTED- SECTION 912.1 FBC P.
  
 6) A1: PROVIDE A WATER RISER DRAWING- SECTION 604.2 FBC
 P. THE RISER SHALL INDICATE PIPE SIZES, LOCATIONS OF
 SHUT OFF VALVES, MIXING VALVES ETC- SECTION 107.2.1
 WPB. PLEASE NOTE THAT TEMPERED WATER SHALL BE PROVIDED
 TO THE LAVATORIES IN COMPLIANCE WITH SECTION 416.5 FBC
 P.
  
 7) PROVIDE ARCHITECTURAL DETAILS FOR FLOOR AND WALL
 FINISHES IN THE NEW TOILET ROOMS- SECTION 405.2 FBC P
 AND 107.2.1 WPB
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2020-03-31 Cont ID  
Sent By ccole Date 2020-03-31 Time 16:16 Rev Time 0.00
Received By ccole Date 2020-03-31 Time 16:16 Sent To  
Notes
2020-03-31 17:10:38 
 1ST REVIEW FBC-2017 PLUMBING
 PERMIT #2001359
 3/31/20
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET A1: PLEASE PROVIDE ENLARGED DIMENSIONED
 DRAWINGS OF THE NEW MEN'S AND WOMEN'S TOILET ROOMS TO
 SHOW COMPLIANCE WITH SECTION 213.2 FBC ACC. THE
 ENLARGED DRAWINGS SHALL SHOW:
 A) CLEAR FLOOR SPACES FOR THE WATER CLOSETS- SECTION
 604.3 FBC ACC.
 B) CLEAR FLOOR SPACES FOR THE LAVATORIES- SECTION
 606.2.
 C) TURNING SPACES IN THE TOILET ROOMS- SECTION 304.3.
 D) CENTERLINES OF THE WATER CLOSETS FROM THE SIDE WALLS
 OR PARTITIONS- SECTION 604.2.
 E) HEIGHTS OF THE WATER CLOSET SEATS FROM THE FINISHED
 FLOORS- SECTION 604.4.
 F) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB
 BARS- SECTION 604.5
 G) LOCATIONS OF FLUSH CONTROLS- SECTION 604.6.
 H) LOCATIONS, CLEARANCES, AND MOUNTING HEIGHTS FOR
 DISPENSERS- SECTION 604.7
  
 2) A1, MENS TOILET ROOM
 A) THE URINAL SHALL NOT BE LOCATED IN THE REQUIRED
 CLEAR FLOOR SPACE OF THE WATER CLOSET- SECTION 604.3.2.
 B) THE WATER CLOSET SHALL OCCUPY A SEPARATE COMPARTMENT
 WITH WALLS OR PARTITIONS AND A DOOR. EXCEPTION: NOT
 REQUIRED IN A SINGLE-OCCUPANT TOILET ROOM WITH A
 LOCKABLE DOOR- SECTION 405.3.4
 C) PROVIDE URINAL PARTITION DETAILS- SECTION 405.3.5
 FBC P.
  
 3) A1, WOMEN'S TOILET ROOM: THE WHEELCHAIR ACCESSIBLE
 TOILET COMPARTMENT SHALL CONTAIN AN ACCESSIBLE LAVATORY
 WITHIN IT, WHICH MUST BE AT LEAST 19 INCHES WIDE BY 17
 INCHES DEEP, NOMINAL SIZE, AND WALL-MOUNTED. THE
 LAVATORY SHALL BE MOUNTED SO AS NOT TO OVERLAP THE
 CLEAR FLOOR SPACE AREAS REQUIRED BY SECTION 604 FOR THE
 WHEELCHAIR ACCESSIBLE TOILET COMPARTMENT AND SHALL
 COMPLY WITH SECTION 606. PLEASE NOTE THAT FLORIDA LAW,
 SECTION 553.504(5), F.S., STIPULATES THAT "...REQUIRED
 BATHING ROOMS AND TOILET ROOMS IN NEW CONSTRUCTION
 SHALL BE DESIGNED AND CONSTRUCTED..." WITH AN
 ACCESSIBLE LAVATORY IN THE WHEELCHAIR ACCESSIBLE
 COMPARTMENT AND THE WATER CLOSET LOCATED IN A CORNER
 DIAGONAL TO THE DOOR.
  
 4) A1: PROVIDE A PLUMBING FIXTURE SCHEDULE ON THE PLAN-
 SECTIONS 416, 419, & 420 FBC P.
  
 5) A1: THE URINAL CANNOT CONNECT TO THE HORIZONTAL WET
 VENT FOR THE TOILET FIXTURES AND SHALL BE INDIVIDUALLY
 VENTED- SECTION 912.1 FBC P.
  
 6) A1: PROVIDE A WATER RISER DRAWING- SECTION 604.2 FBC
 P. THE RISER SHALL INDICATE PIPE SIZES, LOCATIONS OF
 SHUT OFF VALVES, MIXING VALVES ETC- SECTION 107.2.1
 WPB. PLEASE NOTE THAT TEMPERED WATER SHALL BE PROVIDED
 TO THE LAVATORIES IN COMPLIANCE WITH SECTION 416.5 FBC
 P.
  
 7) PROVIDE ARCHITECTURAL DETAILS FOR FLOOR AND WALL
 FINISHES IN THE NEW TOILET ROOMS- SECTION 405.2 FBC P
 AND 107.2.1 WPB
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 7 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By jgomez Date 2020-09-17 Time 11:11 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 6 Status P Date 2020-09-10 Cont ID  
Sent By jgomez Date 2020-09-10 Time 14:30 Rev Time 0.00
Received By jgomez Date 2020-09-10 Time 14:26 Sent To  
Notes
2020-09-10 14:32:33DRAWING A-1 MATCHES APPROVED ONE. JG.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 5 Status F Date 2020-09-08 Cont ID  
Sent By jgomez Date 2020-09-08 Time 15:53 Rev Time 0.00
Received By jgomez Date 2020-09-08 Time 15:53 Sent To  
Notes
2020-09-08 16:03:431- DRAWING A-1 SUBMITTED DOESN'T MATCH THE LATEST
 REVISED PLAN THAT WAS UPLOADED TO PROJECTDOX ON
 08/26/2020. NEED TO PROVIDE THE SAME PLAN THAT WAS
 UPLOADED FOR REVIEW. THIS PLAN HAD A COPY OF THE
 ARCHITECT'S DIGITAL SIGNATURE DATED 8/10/2020. DRAWING
 A-1 SUBMITTED NOW SEEMS TO BE THE SAME THAT WAS
 SUBMITTED ON PREVIOUS RESUBMITTAL AND IT WAS DATED
 7/17/20.
 NOTE: ARCHITECT MAY UPLOAD THE PLAN WITH THE DIGITAL
 SIGNATURE THAT CAN BE VERIFIED BY THE PLAN REVIEWER OR
 PROVIDE HARD COPY WITH ARCHITECT'S ORIGINAL SEAL AND
 SIGNATURE.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status F Date 2020-09-02 Cont ID  
Sent By rmcdouga Date 2020-09-02 Time 13:57 Rev Time 0.00
Received By rmcdouga Date 2020-09-02 Time 13:57 Sent To  
Notes
2020-09-02 13:57:34I WAS NOT ABLE TO VERIFY THE DIGITAL SIGNATURE ON THE
 DRAWINGS. IF THE DIGITAL SIGNATURES ON THE
 ELECTRONICALLY SUBMITTED PLANS CAN NOT BE VERIFIED THEN
 PAPER PLANS WITH ORIGINAL HANDWRITTEN SIGNATURES CAN
 SUBMITTED AT THE BUILDING DEPARTMENT'S PHYSICAL
 LOCATION 401 CLEMATIS STREET.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status F Date 2020-08-18 Cont ID  
Sent By rmcdouga Date 2020-08-18 Time 07:54 Rev Time 0.00
Received By rmcdouga Date 2020-08-18 Time 07:54 Sent To  
Notes
2020-08-18 07:59:22I WAS NOT ABLE TO VERIFY THE DIGITAL SIGNATURE ON THE
 DRAWINGS. IF THE DIGITAL SIGNATURES ON THE
 ELECTRONICALLY SUBMITTED PLANS CAN NOT BE VERIFIED THEN
 PAPER PLANS WITH ORIGINAL HANDWRITTEN SIGNATURES CAN
 SUBMITTED AT THE BUILDING DEPARTMENT'S PHYSICAL
 LOCATION 401 CLEMATIS STREET.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2020-07-08 Cont ID  
Sent By rmcdouga Date 2020-07-08 Time 10:44 Rev Time 0.00
Received By rmcdouga Date 2020-07-08 Time 10:44 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2020-05-08 Cont ID  
Sent By jgomez Date 2020-05-08 Time 10:14 Rev Time 0.00
Received By jgomez Date 2020-05-08 Time 10:14 Sent To  
Notes
2020-05-08 10:15:26CONVERTED TO DIGITAL.
 DRAWINGS WITH ARCHITECT'S ORIGINAL SEAL/SIGNATURE ON
 CITY'S FILE. JG