Plan Review Details - Permit 20031321
Plan Review Stops For Permit 20031321
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2020-06-25 Cont ID  
Sent By rmcphers Date 2020-06-25 Time 14:03 Rev Time 0.00
Received By rmcphers Date 2020-06-25 Time 14:03 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-05-13 Cont ID  
Sent By rmcphers Date 2020-05-13 Time 16:32 Rev Time 0.00
Received By rmcphers Date 2020-05-13 Time 14:44 Sent To  
Notes
2020-05-13 16:34:56SIGN
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) DRAWINGS NEED TO BE DIGITALLY SIGNED BY THE ENGINEER
 TO BE USED IN ELECTRONIC PLAN REVIEW.
  
 FYI - ENGINEER CANNOT SELF-CERTIFY THE DIGITAL
 SIGNATURE
 668.003(2) AND (3), F.S.
 (2) A PROFESSIONAL ENGINEER UTILIZING A DIGITAL
 SIGNATURE TO ELECTRONICALLY SIGN AND SEAL ENGINEERING
 PLANS,
 SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS SHALL HAVE
 THEIR IDENTITY AUTHENTICATED BY A CERTIFICATION
 AUTHORITY.
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2020-07-02 Cont ID  
Sent By jleahy Date 2020-07-02 Time 09:00 Rev Time 0.00
Received By jleahy Date 2020-07-01 Time 16:28 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-05-14 Cont ID  
Sent By jleahy Date 2020-05-14 Time 16:30 Rev Time 0.00
Received By jleahy Date 2020-05-14 Time 16:30 Sent To  
Notes
2020-05-14 16:31:55ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 1) VALUE FOR THESE SIGNS IS LOW (15000)
  
 109.3 BUILDING PERMIT VALUATIONS. IF, IN THE OPINION OF
 THE BUILDING OFFICIAL, THE CLAIMED VALUATION OF
 BUILDING, ALTERATION, STRUCTURE, ELECTRICAL, GAS,
 MECHANICAL OR PLUMBING SYSTEMS APPEARS TO BE
 UNDERESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE
 DENIED, UNLESS THE APPLICANT CAN SHOW DETAILED,
 QUANTITY ESTIMATES, AND/OR BONA FIDE SIGNED CONTRACTS
 (EXCLUDING LAND VALUE) TO MEET THE APPROVAL OF THE
 BUILDING OFFICIAL. FOR PERMITTING PURPOSES, VALUATION
 OF BUILDINGS AND SYSTEMS SHALL BE TOTAL REPLACEMENT
 VALUE TO INCLUDE STRUCTURAL, ELECTRIC, PLUMBING,
 MECHANICAL, INTERIOR FINISH, RELATIVE SITE WORK,
 ARCHITECTURAL AND DESIGN FEES, MARKETING COSTS,
 OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY
 INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT
 VALUATION SHALL BE SET BY THE BUILDING OFFICIAL.
  
 2) DISCONNECTS TO BE INSTALLED PER 600.6 (A) LOCATION.
 (1) AT POINT OF ENTRY TO A SIGN ENCLOSURE. THE
 DISCONNECT SHALL BE LOCATED AT THE POINT THE FEEDER
 CIRCUIT OR BRANCH CIRCUIT(S) SUPPLYING A SIGN OR
 OUTLINE LIGHTING SYSTEM ENTERS A SIGN ENCLOSURE OR A
 POLE IN ACCORDANCE WITH 600.5(C)(3) AND SHALL
 DISCONNECT ALL WIRING WHERE IT ENTERS THE ENCLOSURE OF
 THE SIGN OR POL

Review Stop I INCOMING/PROCESSING
Rev No 2 Status F Date 2020-07-02 Cont ID  
Sent By jleahy Date 2020-07-02 Time 09:01 Rev Time 0.00
Received By jleahy Date 2020-06-16 Time 15:23 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-05-14 Cont ID  
Sent By jleahy Date 2020-05-14 Time 16:32 Rev Time 0.00
Received By jleahy Date 2020-04-28 Time 10:57 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2020-06-25 Cont ID  
Sent By rmcphers Date 2020-06-25 Time 14:03 Rev Time 0.00
Received By rmcphers Date 2020-06-25 Time 14:03 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-05-13 Cont ID  
Sent By rmcphers Date 2020-05-13 Time 16:35 Rev Time 0.00
Received By rmcphers Date 2020-05-13 Time 16:35 Sent To  
Notes
2020-05-13 16:35:26SEE BUILDING PLAN REVIEW

Review Stop Z ZONING
Rev No 2 Status P Date 2020-06-25 Cont ID  
Sent By llouie Date 2020-06-25 Time   Rev Time 0.00
Received By llouie Date 2020-06-25 Time   Sent To  
Notes
2020-06-25 11:05:02* FOR BUILDING (SIGNS B, C AND D) AND GAS CANOPY (SIGNS
 E AND F) ONLY.
  
 * SEPARATE PERMITS REQUIRED FOR ALL FREESTANDING
 SIGNAGE (SIGNS A1 AND A2).

Review Stop Z ZONING
Rev No 1 Status F Date 2020-05-04 Cont ID  
Sent By llouie Date 2020-05-04 Time   Rev Time  
Received By llouie Date 2020-05-04 Time   Sent To  
Notes
2020-05-04 10:23:05** FAILED **
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE
 COMMENTS IN WRITING AND/OR ON THE PLANS WHERE
 APPLICABLE:
  
 1.) CONVENIENCE STORE SIGNAGE AND CANOPY WALL SIGNAGE
 MUST BE SUBMITTED AS SEPARATE PERMITS (BY BUILDING).
 PLEASE CONTACT SAMANTHA HILL @ (561) 805-6724, FOR
 ASSISTANCE.
  
  
 NOTES:
  
 * ANY REVISIONS MAY RESULT IN ADDITIONAL COMMENTS.
  
 * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE
 QUESTIONS.
  
 * ZONE: GC
  
 * REFERENCE: PB 1837B (PALM BEACH RIVERSTONE CPD -
 PENDING APPLICATION)
  