Plan Review Details - Permit 20031307
| Plan Review Stops For Permit 20031307 |
| Review Stop |
ASBESTOS |
CONFIRM RPT SENT TO PBC HEALTH |
| Rev No |
4 |
Status |
P |
Date |
2020-08-19 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2020-08-19 |
Time |
16:20 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2020-08-19 |
Time |
15:46 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
ASBESTOS |
CONFIRM RPT SENT TO PBC HEALTH |
| Rev No |
3 |
Status |
F |
Date |
2020-07-27 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2020-07-27 |
Time |
09:30 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2020-07-27 09:38:18 | PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE | | | CONTRACTOR, ON LETTERHEAD, STATING THAT THE | | | INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM | | | COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH | | | COUNTY WILL BE FOLLOWED AND THAT NOTIFICATION WILL BE | | | GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS | | | REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE: | | | | | | HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE | | | S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION- | | | RENOVATION.HTML | | | 19120504 | | | THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO | | | [email protected]. THE INFORMATION SHOULD BE IN PDF | | | FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE | | | THE PERMIT NUMBER AND "ASBESTOS" IN THE SUBJECT LINE. |
|
|
| Review Stop |
ASBESTOS |
CONFIRM RPT SENT TO PBC HEALTH |
| Rev No |
2 |
Status |
F |
Date |
2020-06-08 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2020-06-08 |
Time |
11:32 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2020-06-08 |
Time |
10:52 |
Sent To |
|
|
| Notes |
| 2020-06-08 11:23:13 | PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE | | | CONTRACTOR, ON LETTERHEAD, STATING THAT THE | | | INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM | | | COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH | | | COUNTY WILL BE FOLLOWED AND THAT NOTIFICATION WILL BE | | | GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS | | | REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE: | | | | | | HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE | | | S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION- | | | RENOVATION.HTML | | | 19120504 | | | THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO | | | [email protected]. THE INFORMATION SHOULD BE IN PDF | | | FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE | | | THE PERMIT NUMBER AND ?ASBESTOS? IN THE SUBJECT LINE. |
|
|
| Review Stop |
ASBESTOS |
CONFIRM RPT SENT TO PBC HEALTH |
| Rev No |
1 |
Status |
F |
Date |
2020-04-21 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2020-04-21 |
Time |
10:28 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2020-04-21 |
Time |
09:31 |
Sent To |
|
|
| Notes |
| 2020-04-21 09:56:35 | PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE | | | CONTRACTOR, ON LETTERHEAD, STATING THAT THE | | | INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM | | | COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH | | | COUNTY WILL BE FOLLOWED AND THAT NOTIFICATION WILL BE | | | GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS | | | REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE: | | | | | | HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE | | | S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION- | | | RENOVATION.HTML | | | 19120504 | | | THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO | | | [email protected]. THE INFORMATION SHOULD BE IN PDF | | | FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE | | | THE PERMIT NUMBER AND ?ASBESTOS? IN THE SUBJECT LINE. | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
5 |
Status |
P |
Date |
2020-08-27 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2020-08-27 |
Time |
10:32 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2020-08-27 |
Time |
09:45 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
F |
Date |
2020-08-19 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2020-08-19 |
Time |
16:18 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2020-08-19 |
Time |
15:45 |
Sent To |
|
|
| Notes |
| 2020-08-19 16:18:50 | 2017 FBC- BUILDING PLAN REVIEW | | | W. P. B. PERMIT: 20031307 | | | ADD: 1707 CONSULATE PL. # 202 | | | CONT: BRUNET BROTHERS CONSTRUCTION LLC | | | TEL: 561-904-1465 | | | E-MAIL: BRUNETBROTHERSCONSTRUCTION@GMAIL,COM | | | | | | 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH | | | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, | | | ADMINISTRATION | | | | | | 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW | | | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES | | | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA | | | BUILDING CODE, BUILDING. | | | | | | 4TH REVIEW | | | DATE: WED. AUGUST 19TH/ 2020 | | | ACTION: DENIED | | | | | | 1) COMPLIED. | | | | | | ************4X FEE / NOTICE!!!!! FLORIDA STATUTE | | | 553.80(2)(B) ************* | | | PLEASE CALL 718-9724 | | | | | | | | | | | | WITH RESPECT TO EVALUATION OF DESIGN PROFESSIONALS? | | | DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN | | | ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING | | | CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS | | | REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO | | | CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY | | | NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO, | | | EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY, | | | ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL, | | | MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER | | | REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING | | | COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL | | | GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH | | | REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION, | | | A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE | | | PERMIT FEE ATTRIBUTED TO PLANS REVIEW. | | | | | | | | | | | | 2) 4TH REVIEW CYCLET. THIS REVIEW CYCLE SUBMITTED DATA | | | SHEET FOR LIFEPROOF LUXURY YINYL FLOORING. THE DATA | | | SHEET INDICATES COMPLIANCE WITH ASTM E-90 FOR STC-50 | | | AAND ASTM E-492 IIC 50. WE NEED TO HAVE THE ACTUAL TEST | | | SHEETS FOR THESE CODE ISSUES AND FOR THE CRITICAL FLUX | | | TEST. | | | | | | | | | THE SUBMITTED NUCOR PRODUCT DATA NOR THE LIFE PROOF | | | LUXURY VINYL FLOORING WERE SUBMITTED WITH TEST | | | REPORTS!!!!!!! ADDITIONAL INFORMATION IS REQUIRED TO BE | | | ABLE TO IDENTIFY THE PRODUCT AND CODE REQUIREMENTS. IF | | | THIS IS A VINYL PLANK PRODUCT NO INFORMATION IS | | | REQUIRED, BUT THE PRODUCT NEEDS TO STATE THE TYPE OF | | | PRODUCT IT IS. | | | FLOOR INSULATION (FBC-B 2017) | | | FOR TILE, STONE, MARBLE, AND WOOD FLOORING ALL NEED TO | | | HAVE HAD THE SOUND UNDERLAYMENT TESTED FLOOR ASSEMBLIES | | | TO THE FOLLOWING STANDARDS AND MEET THE QUALIFICATIONS | | | LISTED UNDER EACH OF THE STANDARDS FOR A 6 INCH | | | CONCRETE FLOOR ASSEMBLY/ NO DROPPED CEILING: | | | PLEASE PROVIDE TEST REPORTS SHOWING COMPLIANCE WITH: | | | | | | TYPE I AND II BUILDINGS | | | 2A) FBC-B 2017 1207.3 STRUCTURE-BORNE SOUND. | | | FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR | | | BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA | | | WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION | | | CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD | | | TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492. | | | | | | 2B) FBC-B 2017 1207.2 AIR-BORNE SOUND. | | | WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES | | | SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM | | | PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION | | | CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) | | | FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM | | | E 90. | | | | | | 2C) FLAME SPREAD- FBC-B 2017 603.1. EXCEPTION 2. | | | INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID | | | DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED | | | TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. | | | | | | FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS | | | A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL | | | MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A | | | MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723. | | | | | | TYPE III-TYPE V CONSTRUCTION: | | | A) FBC-B 2017 1207.3 STRUCTURE-BORNE SOUND. | | | FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR | | | BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA | | | WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION | | | CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD | | | TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492. | | | | | | B) FBC-B 2017 1207.2 AIR-BORNE SOUND. | | | WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES | | | SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM | | | PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION | | | CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) | | | FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM | | | E 90. | | | | | | C) FBC-B-2017 720.2 CONCEALED INSTALLATION. INSULATING | | | MATERIALS, WHERE CONCEALED AS INSTALLED IN BUILDINGS OF | | | ANY TYPE OF CONSTRUCTION, SHALL HAVE A FLAME SPREAD | | | INDEX OF NOT MORE THAN 25 AND A SMOKE-DEVELOPED INDEX | | | OF NOT MORE THAN 450. | | | | | | FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS | | | A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL | | | MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A | | | MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723. | | | | | | 3) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW | | | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE | | | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR | | | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE | | | THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED | | | DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE | | | MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS | | | AND INFORMATION LACKING UNDER THE PRIOR REVIEW. | | | | | | JAMES A. WITMER BN, PX, SFP, CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT | | | 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 | | | TEL: 561-805-6717 | | | | | | | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2020-07-27 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2020-07-27 |
Time |
09:46 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2020-07-27 09:46:31 | 2017 FBC- BUILDING PLAN REVIEW | | | W. P. B. PERMIT: 20031307 | | | ADD: 1707 CONSULATE PL. # 202 | | | CONT: BRUNET BROTHERS CONSTRUCTION LLC | | | TEL: 561-904-1465 | | | E-MAIL: BRUNETBROTHERSCONSTRUCTION@GMAIL,COM | | | | | | 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH | | | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, | | | ADMINISTRATION | | | | | | 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW | | | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES | | | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA | | | BUILDING CODE, BUILDING. | | | | | | 3RD REVIEW | | | DATE: MON. JULY 27TH/ 2020 | | | ACTION: DENIED | | | | | | 1) COMPLIED. | | | | | | ************4X FEE / NOTICE!!!!! FLORIDA STATUTE | | | 553.80(2)(B) ************* | | | PLEASE CALL 718-9724 | | | | | | | | | | | | WITH RESPECT TO EVALUATION OF DESIGN PROFESSIONALS? | | | DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN | | | ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING | | | CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS | | | REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO | | | CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY | | | NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO, | | | EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY, | | | ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL, | | | MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER | | | REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING | | | COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL | | | GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH | | | REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION, | | | A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE | | | PERMIT FEE ATTRIBUTED TO PLANS REVIEW. | | | | | | | | | | | | 2) 3RD REVIEW CYCLET. THIS REVIEW CYCLE SUBMITTED DATA | | | SHEET FOR LIFEPROOF LUXURY YINYL FLOORING. THE DATA | | | SHEET INDICATES COMPLIANCE WITH ASTM E-90 FOR STC-50 | | | AAND ASTM E-492 IIC 50. WE NEED TO HAVE THE ACTUAL TEST | | | SHEETS FOR THESECODE ISSUES AND FOR THE CRITICAL FLUX | | | TEST. | | | | | | | | | THE SUBMITTED NUCOR PRODUCT DATA NOR THE LIFE PROOF | | | LUXURY VINYL FLOORING WERE SUBMITTED WITH TEST | | | REPORTS!!!!!!! ADDITIONAL INFORMATION IS REQUIRED TO BE | | | ABLE TO IDENTIFY THE PRODUCT AND CODE REQUIREMENTS. IF | | | THIS IS A VINYL PLANK PRODUCT NO INFORMATION IS | | | REQUIRED, BUT THE PRODUCT NEEDS TO STATE THE TYPE OF | | | PRODUCT IT IS. | | | FLOOR INSULATION (FBC-B 2017) | | | FOR TILE, STONE, MARBLE, AND WOOD FLOORING ALL NEED TO | | | HAVE HAD THE SOUND UNDERLAYMENT TESTED FLOOR ASSEMBLIES | | | TO THE FOLLOWING STANDARDS AND MEET THE QUALIFICATIONS | | | LISTED UNDER EACH OF THE STANDARDS FOR A 6 INCH | | | CONCRETE FLOOR ASSEMBLY/ NO DROPPED CEILING: | | | PLEASE PROVIDE TEST REPORTS SHOWING COMPLIANCE WITH: | | | | | | TYPE I AND II BUILDINGS | | | 2A) FBC-B 2017 1207.3 STRUCTURE-BORNE SOUND. | | | FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR | | | BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA | | | WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION | | | CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD | | | TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492. | | | | | | 2B) FBC-B 2017 1207.2 AIR-BORNE SOUND. | | | WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES | | | SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM | | | PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION | | | CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) | | | FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM | | | E 90. | | | | | | 2C) FLAME SPREAD- FBC-B 2017 603.1. EXCEPTION 2. | | | INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID | | | DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED | | | TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. | | | | | | FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS | | | A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL | | | MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A | | | MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723. | | | | | | TYPE III-TYPE V CONSTRUCTION: | | | A) FBC-B 2017 1207.3 STRUCTURE-BORNE SOUND. | | | FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR | | | BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA | | | WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION | | | CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD | | | TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492. | | | | | | B) FBC-B 2017 1207.2 AIR-BORNE SOUND. | | | WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES | | | SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM | | | PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION | | | CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) | | | FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM | | | E 90. | | | | | | C) FBC-B-2017 720.2 CONCEALED INSTALLATION. INSULATING | | | MATERIALS, WHERE CONCEALED AS INSTALLED IN BUILDINGS OF | | | ANY TYPE OF CONSTRUCTION, SHALL HAVE A FLAME SPREAD | | | INDEX OF NOT MORE THAN 25 AND A SMOKE-DEVELOPED INDEX | | | OF NOT MORE THAN 450. | | | | | | FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS | | | A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL | | | MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A | | | MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723. | | | | | | 3) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW | | | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE | | | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR | | | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE | | | THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED | | | DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE | | | MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS | | | AND INFORMATION LACKING UNDER THE PRIOR REVIEW. | | | | | | JAMES A. WITMER BN, PX, SFP, CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT | | | 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 | | | TEL: 561-805-6717 | | | | | | | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2020-06-08 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2020-06-08 |
Time |
11:32 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2020-06-08 |
Time |
10:52 |
Sent To |
|
|
| Notes |
| 2020-06-08 11:31:53 | 2017 FBC- BUILDING PLAN REVIEW | | | W. P. B. PERMIT: 20031307 | | | ADD: 1707 CONSULATE PL. # 202 | | | CONT: P M BUILDERS | | | TEL: 352-494-2478 | | | E-MAIL: [email protected] | | | | | | 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH | | | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, | | | ADMINISTRATION | | | | | | 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW | | | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES | | | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA | | | BUILDING CODE, BUILDING. | | | | | | 2ND REVIEW | | | DATE: MON. JUNE 08/ 2020 | | | ACTION: DENIED | | | | | | 1) COMPLIED. | | | | | | 2) 2ND REVIEW COMMENT. THIS REVIEW CYCLE SUBMITTED DATA | | | SHEET FOR LIFEPROOF LUXURY YINYL FLOORING. THE DATA | | | SHEET INDICATES COMPLIANCE WITH ASTM E-90 FOR STC-50 | | | AAND ASTM E-492 IIC 50. WE NEED TO HAVE THE ACTUAL TEST | | | SHEETS FOR THESECODE ISSUES AND FOR THE CRITICAL FLUX | | | TEST. | | | | | | | | | THE SUBMITTED NUCOR PRODUCT DATA DOES NOT INDICATE WHAT | | | THE PRODUCT IS COMPOSED OF OTHER THAT A CORK BACKING. | | | IS THIS LAMINATE FLOORING, LUXURY VINYL PLANK FLOORING. | | | ADDITIONAL INFORMATION IS REQUIRED TO BE ABLE TO | | | IDENTIFY THE PRODUCT AND CODE REQUIREMENTS. IF THIS IS | | | A VINYL PLANK PRODUCT NO INFORMATION IS REQUIRED, BUT | | | THE PRODUCT NEEDS TO STATE THE TYPE OF PRODUCT IT IS. | | | FLOOR INSULATION (FBC-B 2017) | | | FOR TILE, STONE, MARBLE, AND WOOD FLOORING ALL NEED TO | | | HAVE HAD THE SOUND UNDERLAYMENT TESTED FLOOR ASSEMBLIES | | | TO THE FOLLOWING STANDARDS AND MEET THE QUALIFICATIONS | | | LISTED UNDER EACH OF THE STANDARDS FOR A 6 INCH | | | CONCRETE FLOOR ASSEMBLY/ NO DROPPED CEILING: | | | PLEASE PROVIDE TEST REPORTS SHOWING COMPLIANCE WITH: | | | | | | TYPE I AND II BUILDINGS | | | 2A) FBC-B 2017 1207.3 STRUCTURE-BORNE SOUND. | | | FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR | | | BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA | | | WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION | | | CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD | | | TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492. | | | | | | 2B) FBC-B 2017 1207.2 AIR-BORNE SOUND. | | | WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES | | | SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM | | | PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION | | | CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) | | | FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM | | | E 90. | | | | | | 2C) FLAME SPREAD- FBC-B 2017 603.1. EXCEPTION 2. | | | INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID | | | DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED | | | TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. | | | | | | FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS | | | A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL | | | MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A | | | MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723. | | | | | | TYPE III-TYPE V CONSTRUCTION: | | | A) FBC-B 2017 1207.3 STRUCTURE-BORNE SOUND. | | | FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR | | | BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA | | | WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION | | | CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD | | | TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492. | | | | | | B) FBC-B 2017 1207.2 AIR-BORNE SOUND. | | | WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES | | | SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM | | | PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION | | | CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) | | | FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM | | | E 90. | | | | | | C) FBC-B-2017 720.2 CONCEALED INSTALLATION. INSULATING | | | MATERIALS, WHERE CONCEALED AS INSTALLED IN BUILDINGS OF | | | ANY TYPE OF CONSTRUCTION, SHALL HAVE A FLAME SPREAD | | | INDEX OF NOT MORE THAN 25 AND A SMOKE-DEVELOPED INDEX | | | OF NOT MORE THAN 450. | | | | | | FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS | | | A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL | | | MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A | | | MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723. | | | | | | 3) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW | | | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE | | | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR | | | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE | | | THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED | | | DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE | | | MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS | | | AND INFORMATION LACKING UNDER THE PRIOR REVIEW. | | | | | | JAMES A. WITMER BN, PX, SFP, CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT | | | 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 | | | TEL: 561-805-6717 | | | | | | | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2020-04-21 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2020-04-21 |
Time |
10:28 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2020-04-21 |
Time |
09:30 |
Sent To |
|
|
| Notes |
| 2020-04-21 10:22:20 | 2017 FBC- BUILDING PLAN REVIEW | | | W. P. B. PERMIT: 20031307 | | | ADD: 1707 CONSULATE PL. # 202 | | | CONT: P M BUILDERS | | | TEL: 352-494-2478 | | | E-MAIL: [email protected] | | | | | | 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH | | | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, | | | ADMINISTRATION | | | | | | 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW | | | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES | | | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA | | | BUILDING CODE, BUILDING. | | | | | | 1ST REVIEW | | | DATE: 1ST REVIEW | | | ACTION: DENIED | | | | | | 1) THE 2 SUBMITTED SHEETS FLOOR PLAN AND KITCHEN | | | CABINET PLAN DOES NOT HAVE WHO DREW THE PLANS, NO | | | DESIGNER. CERTIFICATION BY CONTRACTOR. THE CONTRACTOR | | | (QUALIFIER) THAT CREATED / DRAWN THE SET OF PLANS WILL | | | NEED TO IDENTIFY THEMSELVES AS THE AUTHOR OF THE PLANS. | | | PLEASE PRINT YOUR NAME, SIGN YOUR NAME AND LICENSE | | | NUMBER FOR THE TRADE YOU ARE LICENSED IN AND PLANS | | | DRAWN. 107.3.4.3 CERTIFICATION BY CONTRACTOR. | | | | | | 2) THE SUBMITTED NUCOR PRODUCT DATA DOES NOT INDICATE | | | WHAT THE PRODUCT IS COMPOSED OF OTHER THAT A CORK | | | BACKING. IS THIS LAMINATE FLOORING, LUXURY VINYL PLANK | | | FLOORING. ADDITIONAL INFORMATION IS REQUIRED TO BE ABLE | | | TO IDENTIFY THE PRODUCT AND CODE REQUIREMENTS. IF THIS | | | IS A VINYL PLANK PRODUCT NO INFORMATION IS REQUIRED, | | | BUT THE PRODUCT NEEDS TO STATE THE TYPE OF PRODUCT IT | | | IS. | | | FLOOR INSULATION (FBC-B 2017) | | | FOR TILE, STONE, MARBLE, AND WOOD FLOORING ALL NEED TO | | | HAVE HAD THE SOUND UNDERLAYMENT TESTED FLOOR ASSEMBLIES | | | TO THE FOLLOWING STANDARDS AND MEET THE QUALIFICATIONS | | | LISTED UNDER EACH OF THE STANDARDS FOR A 6 INCH | | | CONCRETE FLOOR ASSEMBLY/ NO DROPPED CEILING: | | | PLEASE PROVIDE TEST REPORTS SHOWING COMPLIANCE WITH: | | | | | | TYPE I AND II BUILDINGS | | | A) FBC-B 2017 1207.3 STRUCTURE-BORNE SOUND. | | | FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR | | | BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA | | | WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION | | | CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD | | | TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492. | | | | | | B) FBC-B 2017 1207.2 AIR-BORNE SOUND. | | | WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES | | | SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM | | | PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION | | | CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) | | | FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM | | | E 90. | | | | | | C) FLAME SPREAD- FBC-B 2017 603.1. EXCEPTION 2. | | | INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID | | | DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED | | | TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. | | | | | | FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS | | | A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL | | | MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A | | | MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723. | | | | | | TYPE III-TYPE V CONSTRUCTION: | | | A) FBC-B 2017 1207.3 STRUCTURE-BORNE SOUND. | | | FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR | | | BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA | | | WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION | | | CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD | | | TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492. | | | | | | B) FBC-B 2017 1207.2 AIR-BORNE SOUND. | | | WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES | | | SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM | | | PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION | | | CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) | | | FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM | | | E 90. | | | | | | C) FBC-B-2017 720.2 CONCEALED INSTALLATION. INSULATING | | | MATERIALS, WHERE CONCEALED AS INSTALLED IN BUILDINGS OF | | | ANY TYPE OF CONSTRUCTION, SHALL HAVE A FLAME SPREAD | | | INDEX OF NOT MORE THAN 25 AND A SMOKE-DEVELOPED INDEX | | | OF NOT MORE THAN 450. | | | | | | FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS | | | A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL | | | MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A | | | MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723. | | | | | | 3) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW | | | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE | | | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR | | | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE | | | THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED | | | DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE | | | MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS | | | AND INFORMATION LACKING UNDER THE PRIOR REVIEW. | | | | | | JAMES A. WITMER BN, PX, SFP, CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT | | | 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 | | | TEL: 561-805-6717 | | | | | | | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
5 |
Status |
P |
Date |
2020-09-01 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2020-09-01 |
Time |
11:55 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2020-09-01 |
Time |
11:55 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
F |
Date |
2020-08-27 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2020-08-27 |
Time |
09:31 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2020-08-27 |
Time |
09:29 |
Sent To |
|
|
| Notes |
| 2020-08-27 09:35:25 | FLORIDA BUILDING CODE 2017 6TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED | | | NFPA 70 2014 EDITION | | | | | | JAKE LEAHY BN, BU, PX | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | | | | PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE EXISTING | | | AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE IS | | | ADEQUATE. NEC 215.2, 220, 408.30; FBC RE3602.3 | | | | | | PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED | | | CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS, | | | AND AFCI OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY | | | WITH CODE. NEC 210.8, 210.12, 215.5, 408.4; FBC | | | RE3706.2, RE3902 | | | | | | PLAN IS REQUIRED TO BE SIGNED AND SEALED BY A DESIGN | | | PROFESSIONAL OR THE ELECTRICAL CONTRACTOR QUALIFIER. FS | | | 471.003(2)(H); 471.025; FBC 107.2.1 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
N |
Date |
2020-08-11 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2020-08-11 |
Time |
09:34 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2020-08-11 |
Time |
09:31 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2020-06-18 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2020-06-18 |
Time |
13:07 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2020-06-18 |
Time |
13:06 |
Sent To |
|
|
| Notes |
| 2020-06-18 13:08:42 | NO ELECTRIC SHOWN JLEAHY |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2020-05-04 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2020-05-04 |
Time |
09:23 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2020-05-04 |
Time |
09:21 |
Sent To |
|
|
| Notes |
| 2020-05-04 09:24:29 | NO ELECTRIC SHOWN |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2020-06-09 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2020-06-09 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2020-06-09 |
Time |
09:11 |
Sent To |
|
|
| Notes |
| 2020-06-09 09:13:57 | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, | | | FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | PLEASE CONSIDER THE FOLLOWING AS PROVISO: | | | | | | THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED | | | AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE | | | PROVISO COMMENTS WILL RESULT IN A FAILED FIRE | | | INSPECTION. | | | | | | | | | 1) MAINTAIN THE FIRE ALARM AND FIRE SPRINKLER | | | PROTECTION. | | | | | | | | | 2) ENSURE PRECAUTION AROUND SPRINKLER HEADS AND FIRE | | | ALARM DEVICES TO AVOID PAINT OVERSPRAY AND ACCIDENTAL | | | ACTIVATION OF WATER DISCHARGE. | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2020-04-20 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2020-04-20 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2020-04-20 |
Time |
09:16 |
Sent To |
|
|
| Notes |
| 2020-04-20 09:18:30 | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, | | | FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | PLEASE CONSIDER THE FOLLOWING AS PROVISO: | | | | | | THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED | | | AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE | | | PROVISO COMMENTS WILL RESULT IN A FAILED FIRE | | | INSPECTION. | | | | | | | | | 1) MAINTAIN THE FIRE ALARM AND FIRE SPRINKLER | | | PROTECTION. | | | | | | | | | 2) ENSURE PRECAUTION AROUND SPRINKLER HEADS AND FIRE | | | ALARM DEVICES TO AVOID PAINT OVERSPRAY AND ACCIDENTAL | | | ACTIVATION OF WATER DISCHARGE. | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2020-08-27 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2020-08-27 |
Time |
09:37 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2020-08-13 |
Time |
08:10 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2020-08-11 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2020-08-11 |
Time |
09:48 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2020-07-23 |
Time |
16:42 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2020-06-18 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2020-06-18 |
Time |
13:09 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2020-06-05 |
Time |
09:21 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2020-05-04 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2020-05-04 |
Time |
09:24 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2020-04-17 |
Time |
08:33 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
N |
Date |
2020-06-15 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2020-06-15 |
Time |
09:56 |
Rev Time |
0.00 |
| Received By |
hmoser |
Date |
2020-06-15 |
Time |
09:33 |
Sent To |
|
|
| Notes |
| 2020-06-15 09:57:57 | NO MECHANICAL WORK BEING DONE AT THIS TIME HM. | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2020-05-01 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2020-05-01 |
Time |
14:37 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2020-05-01 |
Time |
14:37 |
Sent To |
|
|
| Notes |
| 2020-05-01 14:44:31 | | | | 1ST REVIEW FBC-2017 MECHANICAL | | | PERMIT #20031307 | | | 5/1/2020 | | | | | | CODES IN EFFECT: | | | | | | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 | | | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 | | | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION | | | 2017 | | | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 | | | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION | | | 2017 | | | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 | | | FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH | | | EDITION 2017 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) PROVIDE A MECHANICAL PLAN SHOWING THE SCOPE OF WORK | | | FOR THE KITCHEN REMODEL. CLARIFY IF ANY NEW COOKING | | | APPLIANCES, EXHAUST HOODS, EXHAUST DUCTS, OR AC DUCTS | | | ARE TO BE INSTALLED, RELOCATED, OR REPLACED AS PART OF | | | THE KITCHEN REMODEL. SECTION 107.3.5.1.4 WPB. | | | THE PLAN SHALL BE DRAWN BY A LICENSED DESIGN | | | PROFESSIONAL, OR BY THE MECHANICAL CONTRACTOR FOR THE | | | PROJECT. ALL DRAWINGS SHALL BEAR THE WET SIGNATURE AND | | | SEAL OF THE FL. LICENSED DESIGN PROFESSIONAL, OR THE | | | SIGNATURE OF THE CONTRACTOR- SECTIONS 107.1 & 107.2.1 | | | WPB. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
P |
Date |
2020-08-14 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2020-08-14 |
Time |
11:38 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2020-08-14 |
Time |
10:47 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
F |
Date |
2020-07-24 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2020-07-24 |
Time |
09:56 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2020-07-24 |
Time |
07:12 |
Sent To |
|
|
| Notes |
| 2020-07-24 09:57:10 | 3RD REVIEW FBC-2017 PLUMBING | | | PERMIT #20031307 | | | 7/24/2020 | | | | | | CODES IN EFFECT: | | | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 | | | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 | | | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION | | | 2017 | | | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 | | | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION | | | 2017 | | | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 | | | FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH | | | EDITION 2017 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) THE NEW PLUMBING PLAN MUST BEAR THE LICENSE NUMBER | | | AND SIGNATURE OF THE CONTRACTOR OR QUALIFIER WHO | | | PREPARED THE DRAWING- SECTION 107.2.1 WPB AND FL. | | | STATUTES 471.003(2)(H) & 471.025. | | | | | | 2) PREVIOUS REVIEW COMMENT NOT ADDRESSED: REFER TO | | | SECTIONS 409.2 & 608.3 FBC P- INDICATE ON THE PLANS HOW | | | THE WATER SUPPLY LINES TO THE DISHWASHER AND ICE MAKER | | | WILL BE PROTECTED AGAINST BACKFLOW. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2020-06-12 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2020-06-12 |
Time |
08:41 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2020-06-12 |
Time |
07:54 |
Sent To |
|
|
| Notes |
| 2020-06-12 08:55:10 | 1ST REVIEW FBC-2017 PLUMBING | | | PERMIT #20031307 | | | 6/12/2020 | | | | | | CODES IN EFFECT: | | | | | | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 | | | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 | | | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION | | | 2017 | | | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 | | | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION | | | 2017 | | | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 | | | FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH | | | EDITION 2017 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | COMMENT #1 PRINTED FROM THE 1ST REVIEW WAS NOT | | | ADDRESSED. THE NEW KITCHEN PLAN SHOWS THE SINK IS TO BE | | | RELOCATED. PLEASE NOTE THAT WATER HAMMER ARRESTORS ARE | | | REQUIRED FOR THE WATER SUPPLY LINES TO THE DISHWASHER | | | AND ICE MAKER - SECTION 604.9 FBC-17 P; AND THE LINES | | | SHALL BE PROTECTED AGAINST BACKFLOW PER SECTIONS 409.2 | | | & 608.3. | | | PLEASE PROVIDE COMPLETE PLUMBING RISER DRAWINGS. | | | | | | 1) PROVIDE A PLUMBING PLAN SHOWING THE SCOPE OF WORK | | | FOR THE KITCHEN REMODEL. INCLUDE A SANITARY ISOMETRIC | | | DRAWING AND A WATER RISER FOR ALL NEW OR RELOCATED | | | FIXTURE AND APPLIANCE INSTALLATIONS- SECTION | | | 107.3.5.1.3 WPB. | | | . | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2020-05-01 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2020-05-01 |
Time |
14:35 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2020-05-01 |
Time |
14:17 |
Sent To |
|
|
| Notes |
| 2020-05-01 14:36:21 | | | | 1ST REVIEW FBC-2017 PLUMBING | | | PERMIT #20031307 | | | 5/1/2020 | | | | | | CODES IN EFFECT: | | | | | | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 | | | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 | | | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION | | | 2017 | | | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 | | | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION | | | 2017 | | | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 | | | FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH | | | EDITION 2017 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) PROVIDE A PLUMBING PLAN SHOWING THE SCOPE OF WORK | | | FOR THE KITCHEN REMODEL. INCLUDE A SANITARY ISOMETRIC | | | DRAWING AND A WATER RISER FOR ALL NEW OR RELOCATED | | | FIXTURE AND APPLIANCE INSTALLATIONS- SECTION | | | 107.3.5.1.3 WPB. | | | THE PLAN SHALL BE DRAWN BY A LICENSED DESIGN | | | PROFESSIONAL, OR BY THE PLUMBING CONTRACTOR FOR THE | | | PROJECT. ALL DRAWINGS SHALL BEAR THE WET SIGNATURE AND | | | SEAL OF THE FL. LICENSED DESIGN PROFESSIONAL, OR THE | | | SIGNATURE OF THE CONTRACTOR- SECTIONS 107.1 & 107.2.1 | | | WPB. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
4 |
Status |
P |
Date |
2020-09-01 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2020-09-01 |
Time |
11:56 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2020-09-01 |
Time |
11:56 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
3 |
Status |
F |
Date |
2020-08-27 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2020-08-27 |
Time |
09:35 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2020-08-27 |
Time |
09:35 |
Sent To |
|
|
| Notes |
| 2020-08-27 09:36:51 | FLORIDA BUILDING CODE 2017 6TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED | | | NFPA 70 2014 EDITION | | | | | | JAKE LEAHY BN, BU, PX | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | | | | | | | PLAN IS REQUIRED TO BE SIGNED AND SEALED BY A DESIGN | | | PROFESSIONAL OR THE ELECTRICAL CONTRACTOR QUALIFIER. FS | | | 471.003(2)(H); 471.025; FBC 107.2.1 |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
P |
Date |
2020-06-18 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2020-06-18 |
Time |
13:08 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2020-06-18 |
Time |
13:08 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
F |
Date |
2020-05-01 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2020-05-01 |
Time |
14:47 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2020-05-01 |
Time |
14:47 |
Sent To |
|
|
| Notes |
| 2020-05-01 14:50:28 | THE SUBMITTED FLOOR PLAN IS A STOCK CONDO FLOOR PLAN | | | AND, THE KITCHEN PLAN IS A KITCHEN COMPANY PLAN. | | | CURRENTLY NO FL. LICENSED DESIGN PROFESSIONAL ON | | | PROJECT. CONTRACT DID NOT PROVIDE A SIGNATURE ON PLANS. | | | CCOLE- 5/1/2020 |
|
|
|