Plan Review Details - Permit 20031300
Plan Review Stops For Permit 20031300
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2020-06-01 Cont ID  
Sent By rmcdouga Date 2020-06-01 Time 12:38 Rev Time 0.00
Received By rmcdouga Date 2020-06-01 Time 12:38 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2020-04-30 Cont ID  
Sent By rmcdouga Date 2020-04-30 Time 10:18 Rev Time 0.00
Received By rmcdouga Date 2020-04-30 Time 10:18 Sent To  
Notes
2020-04-30 10:20:15PLAN
 REVIEW COMMENTS
 4TH REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SEE THE TWO (2) PREVIOUS REVIEWS.NONE OF THE
 COMMENTS HAVE BEEN CORRECTED. PLEASE READ THE COMMENTS
 AND PROVIDE CORRECTIONS.
  
 2) SUBMIT A RESPONSE LETTER SIGNED BY THE LICENSED
 CONTRACTOR STATING HOW EACH OF THE REVIEW COMMENTS HAS
 BEEN ADDRESSED.
  
 3) PLEASE CROSS OUT AND VOID ALL OF THE OLD SUBMITTAL
 DOCUMENTS THAT HAVE BEEN REVIEWED AND FAILED.
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2020-04-27 Cont ID  
Sent By rmcdouga Date 2020-04-27 Time 14:32 Rev Time 0.00
Received By rmcdouga Date 2020-04-27 Time 14:32 Sent To  
Notes
2020-04-27 14:36:45PLAN
 REVIEW COMMENTS
  
 3RD REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
  
 1) SEE THE TWO (2) PREVIOUS REVIEWS.NONE OF THE
 COMMENTS HAVE BEEN CORRECTED. PLEASE READ THE COMMENTS
 AND PROVIDE CORRECTIONS.
  
 2) SUBMIT A RESPONSE LETTER SIGNED BY THE LICENSED
 CONTRACTOR STATING HOW EACH OF THE REVIEW COMMENTS HAS
 BEEN ADDRESSED.
  
 3) PLEASE CROSS OUT AND VOID ALL OF THE OLD SUBMITTAL
 DOCUMENTS THAT HAVE BEEN REVIEWED AND FAILED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2020-04-15 Cont ID  
Sent By rmcdouga Date 2020-04-15 Time 15:49 Rev Time 0.00
Received By rmcdouga Date 2020-04-15 Time 15:35 Sent To  
Notes
2020-04-15 15:49:45PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 PREVIOUS COMMENTS WERE NOT ADDRESSED
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) IF SUBMITTING PAPER DOCUMENTS, THEN SUBMIT A WIND
 LOAD CHART WITH THE ENGINEER'S ORIGNAL SEAL AND
 SIGNATURE. IF SUBMITTING ELECTRONICALLY THE ENGINEER'S
 DIGITAL SIGNATURE IS REQUIRED. FAC 61G15-23.003
  
 2) SUBMIT A DRAWING THAT SHOWS THE LOCATION OF THIS
 UNIT IN THE BUILDING. IS IT AN END UNIT,ETC? IT IS
 NUMBERED 201, IS IT ON THE SECOND FLOOR? ARE ANY OF THE
 OPENINGS LOCATED IN THE CORNERS (ZONE 5) ? FBC 107.2.1
  
 3) THIS IS A FOUR STORY BUILDING AND THE PRESSURES
 INDICATED ARE FOR A BUILDING HEIGHT OF 15 FEET. YOU
 NEED TO USE THE PRESSURES FOR A FOUR STORY BUILDING.
 FBC CHAPTER 16
  
 4) I DON'T KNOW WHAT THE SHUTTER GLASS SEPARATION THAT
 YOU FILLED IN ON THE SHUTTER SCHEDULE OF 21/8 AND 27/8
 MEANS. THE PRODUCT APPROVAL HAS 3" GLASS SEPARATION.
 FBC 107.2.1
  
 5) THE SUBSTRATE COLUMN WAS LEFT BLANK ON THE SHUTTER
 SCHEDULE. THIS IS NEEDED TO DETERMINE THE ANCHOR TYPE
 TO USE IN THE ANCHOR SPACING TABLES ON PAGES 13 AND 14
 OF THE PRODUCT APPROVAL. FBC 107.2.1
  
 6) ON THE SHUTTER SCHEDULE UNDER SHUTTER MOUNTING 3A IS
 LISTED. THERE IS NO MOUNT TYPE 3A IN THE ANCHOR SPACING
 TABLES. INDICATE THE MOUNT TYPE THAT CORRESPONDS WITH
 THE ANCHOR SPACING TABLES IN THE PRODUCT APPROVAL ON
 THE SHUTTER SCHEDULE.
  
 7) CIRCLE THE ITEMS IN THE ANCHOR SPACING TABLES THAT
 ARE APPLICABLE TO YOUR PROJECT. FBC 107.2.1
  
 NOTE: THE ANCHOR SPACING TABLE IS LOCATED ON SHEET 12
 OF THE PRODUCT APPROVAL. IN ORDER TO DETERMINE THE
 SPACING YOU WILL USE 50 IN THE PD COLUMN. THE MOUNT
 TYPE IS THE SECTION LETTER ON THE DIAGRAMS IN THE
 PRODUCT APPROVAL, NOT THE TRACK TYPE. THE ANCHOR TYPES
 ARE LISTED IN THE ANCHOR SCHEDULE ON SHEET 12 AND ARE
 DETERMINED BY THE ANCHOR AND THE MATERIAL (SUBSTRATE)
 THAT THE TRACKS WILL BE ATTACHED TO.
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-04-10 Cont ID  
Sent By rmcdouga Date 2020-04-10 Time 09:28 Rev Time 0.00
Received By rmcdouga Date 2020-04-10 Time 09:28 Sent To  
Notes
2020-04-10 10:42:40PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) IF SUBMITTING PAPER DOCUMENTS, THEN SUBMIT A WIND
 LOAD CHART WITH THE ENGINEER'S ORIGNAL SEAL AND
 SIGNATURE. IF SUBMITTING ELECTRONICALLY THE ENGINEER'S
 DIGITAL SIGNATURE IS REQUIRED. FAC 61G15-23.003
  
 2) SUBMIT A DRAWING THAT SHOWS THE LOCATION OF THIS
 UNIT IN THE BUILDING. IS IT AN END UNIT,ETC? IT IS
 NUMBERED 201, IS IT ON THE SECOND FLOOR? ARE ANY OF THE
 OPENINGS LOCATED IN THE CORNERS (ZONE 5) ? FBC 107.2.1
  
 3) THIS IS A FOUR STORY BUILDING AND THE PRESSURES
 INDICATED ARE FOR A BUILDING HEIGHT OF 15 FEET. YOU
 NEED TO USE THE PRESSURES FOR A FOUR STORY BUILDING.
 FBC CHAPTER 16
  
 4) I DON'T KNOW WHAT THE SHUTTER GLASS SEPARATION THAT
 YOU FILLED IN ON THE SHUTTER SCHEDULE OF 21/8 AND 27/8
 MEANS. THE PRODUCT APPROVAL HAS 3" GLASS SEPARATION.
 FBC 107.2.1
  
 5) THE SUBSTRATE COLUMN WAS LEFT BLANK ON THE SHUTTER
 SCHEDULE. THIS IS NEEDED TO DETERMINE THE ANCHOR TYPE
 TO USE IN THE ANCHOR SPACING TABLES ON PAGES 13 AND 14
 OF THE PRODUCT APPROVAL. FBC 107.2.1
  
 6) ON THE SHUTTER SCHEDULE UNDER SHUTTER MOUNTING 3A IS
 LISTED. THERE IS NO MOUNT TYPE 3A IN THE ANCHOR SPACING
 TABLES. INDICATE THE MOUNT TYPE THAT CORRESPONDS WITH
 THE ANCHOR SPACING TABLES IN THE PRODUCT APPROVAL ON
 THE SHUTTER SCHEDULE.
  
 7) CIRCLE THE ITEMS IN THE ANCHOR SPACING TABLES THAT
 ARE APPLICABLE TO YOUR PROJECT. FBC 107.2.1
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2020-06-01 Cont ID  
Sent By rmcdouga Date 2020-06-01 Time 12:39 Rev Time 0.00
Received By rmcdouga Date 2020-05-29 Time 08:33 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2020-04-30 Cont ID  
Sent By rmcdouga Date 2020-04-30 Time 10:18 Rev Time 0.00
Received By rmcdouga Date 2020-04-27 Time 16:06 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2020-04-27 Cont ID  
Sent By rmcdouga Date 2020-04-27 Time 14:36 Rev Time 0.00
Received By rmcdouga Date 2020-04-24 Time 13:23 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-04-15 Cont ID  
Sent By rmcdouga Date 2020-04-15 Time 15:50 Rev Time 0.00
Received By rmcdouga Date 2020-04-14 Time 13:06 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-04-10 Cont ID  
Sent By rmcdouga Date 2020-04-10 Time 11:21 Rev Time 0.00
Received By rmcdouga Date 2020-04-08 Time 13:55 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 5 Status P Date 2020-06-01 Cont ID  
Sent By rmcdouga Date 2020-06-01 Time 12:39 Rev Time 0.00
Received By rmcdouga Date 2020-06-01 Time 12:39 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status F Date 2020-04-30 Cont ID  
Sent By rmcdouga Date 2020-04-30 Time 10:18 Rev Time 0.00
Received By rmcdouga Date 2020-04-30 Time 10:18 Sent To  
Notes
2020-04-30 10:19:38WIND PRESSURE CALULATIONS ARE REQUIRED TO BE SIGNED AND
 SEALED BY THE ENGINEER. ELECTRONICALLY SUBMITTED PLANS
 ARE REQUIRED TO BE DIGITALLY SIGNED BY THE ENGINEER.
 CITY AMENDMENTS 107.1

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status F Date 2020-04-27 Cont ID  
Sent By rmcdouga Date 2020-04-27 Time 14:33 Rev Time 0.00
Received By rmcdouga Date 2020-04-27 Time 14:33 Sent To  
Notes
2020-04-27 14:34:13WIND PRESSURE CALULATIONS ARE REQUIRED TO BE SIGNED AND
 SEALED BY THE ENGINEER.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2020-04-15 Cont ID  
Sent By rmcdouga Date 2020-04-15 Time 15:50 Rev Time 0.00
Received By rmcdouga Date 2020-04-15 Time 15:50 Sent To  
Notes
2020-04-27 14:33:50WIND PRESSURE CALULATIONS ARE REQUIRED TO BE SIGNED AND
 SEALED BY THE ENGINEER.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-04-10 Cont ID  
Sent By rmcdouga Date 2020-04-10 Time 09:28 Rev Time 0.00
Received By rmcdouga Date 2020-04-10 Time 09:28 Sent To  
Notes
2020-04-10 11:23:06WIND PRESSURE CALULATIONS ARE REQUIRED TO BE SIGNED AND
 SEALED BY THE ENGINEER.