| 2020-03-30 14:08:15 | 1. A THOROUGH AND COMPLETE PLAN REVIEW CANNOT BE |
| | COMPLETED AT THIS TIME DUE TO LACK OF INFORMATION |
| | SUBMITTED ON THE PLANS. ADDITIONAL PLAN REVIEW COMMENTS |
| | MAY BE GENERATED DURING PLAN RESUBMISSION. |
| | 2. PLANS DO NOT DIFFERENTIATE EXISTING VS NEW FIRE AND |
| | LIFE SAFETY PLANS. NO LIFE SAFETY PLANS INCLUDED. |
| | UPDATE THE CODE LIST TO REFERENCE THE 6TH EDITION OF |
| | THE FLORIDA FIRE PREVENTION CODE WHICH CONTAINS THE |
| | 2015 EDITION OF BOTH NFPA 1 AND NFPA 101 WITH FLORIDA |
| | AMENDMENTS. |
| | 3. PROVIDE DRAWING NOTE INDICATING ALL CONSTRUCTION AND |
| | DEMOLITION WORK SHALL CONFORM TO THE REQUIREMENTS OF |
| | NFPA 241. TRASH AND CONSTRUCTION DEBRIS SHALL BE |
| | REMOVED FROM THE SITE DAILY. SMOKING SHALL BE |
| | PROHIBITED EXCEPT IN DESIGNATED EXTERIOR AREAS. ALL |
| | OTHER DEMOLITION OR CONSTRUCTION AREAS SHALL HAVE "NO |
| | SMOKING" SIGNS POSTED. WHERE SMOKING IS PERMITTED, SAFE |
| | RECEPTACLES FOR SMOKING MATERIALS SHALL BE PROVIDED. |
| | 4. PROVIDE DRAWING NOTE INDICATING, ?FIRE PROTECTION |
| | SYSTEMS SHALL REMAIN ACTIVE DURING DEMOLITION AND |
| | RENOVATION ACTIVITIES. IN THE EVENT A FIRE PROTECTION |
| | SYSTEM IS OUT OF SERVICE FOR MORE THAN 4-HOURS IN A |
| | 24-HOUR PERIOD, THE BUILDING SHALL BE PLACED UNDER A |
| | FIRE WATCH. ALL FIRE WATCH REQUESTS MUST BE SUBMITTED |
| | BY EMAIL ([email protected]) OR IN WRITING (FAX: |
| | 561-804-4774) AND APPROVED BY THE OFFICE OF THE FIRE |
| | MARSHAL LOCATED AT 500 NORTH DIXIE HIGHWAY.? |
| | 5. SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE |
| | INSTALLATION OR MODIFICATION OF THE FIRE SPRINKLER |
| | SYSTEM AND/OR FIRE ALARM SYSTEM. |
| | 6. ENGINEERED FIRE ALARM AND FIRE SPRINKLER |
| | CONSTRUCTION DOCUMENTS ARE REQUIRED FOR A GENERAL |
| | BUILDING PERMIT. AFTER THE BUILDING PERMIT HAS BEEN |
| | ISSUED, THE SUBCONTRACTORS CAN THEN SUBMIT SHOP |
| | DRAWINGS (CONFORMING TO THE ENGINEERED CONSTRUCTION |
| | DOCUMENTS) FOR A SUB-PERMIT. |
| | 7. PER NFPA 241 SECTION 8.6.2 TEMPORARY SEPARATION |
| | WALLS: PROTECTION SHALL BE PROVIDED TO SEPARATE AN |
| | OCCUPIED PORTION OF THE STRUCTURE FROM A PORTION OF THE |
| | STRUCTURE UNDERGOING ALTERATION, CONSTRUCTION, OR |
| | DEMOLITION OPERATIONS WHEN SUCH OPERATIONS ARE |
| | CONSIDERED AS HAVING A HIGHER LEVEL OF HAZARD THAN THE |
| | OCCUPIED PORTION OF THE BUILDING. WALLS SHALL HAVE AT |
| | LEAST A 1-HOUR FIRE RESISTANCE RATING. OPENING |
| | PROTECTIVES SHALL HAVE AT LEAST A 45-MINUTE FIRE |
| | PROTECTION RATING. NONRATED WALLS AND OPENING |
| | PROTECTIVES SHALL BE PERMITTED WHEN AN APPROVED |
| | AUTOMATIC SPRINKLER SYSTEM IS INSTALLED. |
| | |
| | S. THOMAS |
| | 561-804-4728 |