Plan Review Details - Permit 20031248
Plan Review Stops For Permit 20031248
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 4 Status P Date 2020-05-22 Cont ID  
Sent By rmcphers Date 2020-05-22 Time 09:13 Rev Time 0.00
Received By rmcphers Date 2020-05-22 Time 09:13 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 3 Status F Date 2020-05-18 Cont ID  
Sent By rmcphers Date 2020-05-18 Time 14:22 Rev Time 0.00
Received By rmcphers Date 2020-05-18 Time 14:22 Sent To  
Notes
2020-05-18 14:25:17***NOT ASKING FOR THE ASBESTOS REPORT*****
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN PDF
 FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE
 THE PERMIT NUMBER AND ?ASBESTOS? IN THE SUBJECT LINE.
  

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status F Date 2020-04-23 Cont ID  
Sent By rmcphers Date 2020-04-23 Time 15:29 Rev Time 0.00
Received By rmcphers Date 2020-04-23 Time 15:29 Sent To  
Notes
2020-04-23 15:31:00ASBESTOS ? PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM
 THE CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE.
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected] THE INFORMATION SHOULD BE IN PDF FORMAT
 AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE THE
 PERMIT NUMBER AND (ASBESTOS) IN THE SUBJECT LINE.
  

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2020-03-31 Cont ID  
Sent By rmcphers Date 2020-03-31 Time 08:41 Rev Time 0.00
Received By rmcphers Date 2020-03-31 Time 08:41 Sent To  
Notes
2020-03-31 08:42:32ASBESTOS ? PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM
 THE CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2020-05-18 Cont ID  
Sent By rmcphers Date 2020-05-18 Time 14:26 Rev Time 0.00
Received By rmcphers Date 2020-05-18 Time 14:26 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2020-04-23 Cont ID  
Sent By rmcphers Date 2020-04-23 Time 15:29 Rev Time 0.00
Received By rmcphers Date 2020-04-23 Time 15:29 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-03-31 Cont ID  
Sent By rmcphers Date 2020-03-31 Time 08:40 Rev Time 0.00
Received By rmcphers Date 2020-03-30 Time 16:14 Sent To  
Notes
2020-03-31 08:40:25TARGET ALT
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS
 1) ARCHITECTURAL DRAWINGS DO NOT SHOW AS ELECTRONICALLY
 SIGNED IN "ADOBE" .
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2020-03-31 Cont ID  
Sent By jpearson Date 2020-03-31 Time 10:36 Rev Time 0.00
Received By jpearson Date 2020-03-31 Time 08:17 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2020-04-16 Cont ID  
Sent By sathomas Date 2020-04-16 Time 00:00 Rev Time 0.00
Received By sathomas Date 2020-04-16 Time 00:00 Sent To B
Notes
2020-04-16 09:47:19PROVISO:
 THE 6TH EDITION OF THE FLORIDA FIRE PREVENTION CODE IS
 2015, NOT 2017.
  
 S. THOMAS
 561-804-4728

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2020-03-30 Cont ID  
Sent By sathomas Date 2020-03-30 Time 00:00 Rev Time 0.00
Received By sathomas Date 2020-03-30 Time 00:00 Sent To M
Notes
2020-03-30 14:08:151. A THOROUGH AND COMPLETE PLAN REVIEW CANNOT BE
 COMPLETED AT THIS TIME DUE TO LACK OF INFORMATION
 SUBMITTED ON THE PLANS. ADDITIONAL PLAN REVIEW COMMENTS
 MAY BE GENERATED DURING PLAN RESUBMISSION.
 2. PLANS DO NOT DIFFERENTIATE EXISTING VS NEW FIRE AND
 LIFE SAFETY PLANS. NO LIFE SAFETY PLANS INCLUDED.
 UPDATE THE CODE LIST TO REFERENCE THE 6TH EDITION OF
 THE FLORIDA FIRE PREVENTION CODE WHICH CONTAINS THE
 2015 EDITION OF BOTH NFPA 1 AND NFPA 101 WITH FLORIDA
 AMENDMENTS.
 3. PROVIDE DRAWING NOTE INDICATING ALL CONSTRUCTION AND
 DEMOLITION WORK SHALL CONFORM TO THE REQUIREMENTS OF
 NFPA 241. TRASH AND CONSTRUCTION DEBRIS SHALL BE
 REMOVED FROM THE SITE DAILY. SMOKING SHALL BE
 PROHIBITED EXCEPT IN DESIGNATED EXTERIOR AREAS. ALL
 OTHER DEMOLITION OR CONSTRUCTION AREAS SHALL HAVE "NO
 SMOKING" SIGNS POSTED. WHERE SMOKING IS PERMITTED, SAFE
 RECEPTACLES FOR SMOKING MATERIALS SHALL BE PROVIDED.
 4. PROVIDE DRAWING NOTE INDICATING, ?FIRE PROTECTION
 SYSTEMS SHALL REMAIN ACTIVE DURING DEMOLITION AND
 RENOVATION ACTIVITIES. IN THE EVENT A FIRE PROTECTION
 SYSTEM IS OUT OF SERVICE FOR MORE THAN 4-HOURS IN A
 24-HOUR PERIOD, THE BUILDING SHALL BE PLACED UNDER A
 FIRE WATCH. ALL FIRE WATCH REQUESTS MUST BE SUBMITTED
 BY EMAIL ([email protected]) OR IN WRITING (FAX:
 561-804-4774) AND APPROVED BY THE OFFICE OF THE FIRE
 MARSHAL LOCATED AT 500 NORTH DIXIE HIGHWAY.?
 5. SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE
 INSTALLATION OR MODIFICATION OF THE FIRE SPRINKLER
 SYSTEM AND/OR FIRE ALARM SYSTEM.
 6. ENGINEERED FIRE ALARM AND FIRE SPRINKLER
 CONSTRUCTION DOCUMENTS ARE REQUIRED FOR A GENERAL
 BUILDING PERMIT. AFTER THE BUILDING PERMIT HAS BEEN
 ISSUED, THE SUBCONTRACTORS CAN THEN SUBMIT SHOP
 DRAWINGS (CONFORMING TO THE ENGINEERED CONSTRUCTION
 DOCUMENTS) FOR A SUB-PERMIT.
 7. PER NFPA 241 SECTION 8.6.2 TEMPORARY SEPARATION
 WALLS: PROTECTION SHALL BE PROVIDED TO SEPARATE AN
 OCCUPIED PORTION OF THE STRUCTURE FROM A PORTION OF THE
 STRUCTURE UNDERGOING ALTERATION, CONSTRUCTION, OR
 DEMOLITION OPERATIONS WHEN SUCH OPERATIONS ARE
 CONSIDERED AS HAVING A HIGHER LEVEL OF HAZARD THAN THE
 OCCUPIED PORTION OF THE BUILDING. WALLS SHALL HAVE AT
 LEAST A 1-HOUR FIRE RESISTANCE RATING. OPENING
 PROTECTIVES SHALL HAVE AT LEAST A 45-MINUTE FIRE
 PROTECTION RATING. NONRATED WALLS AND OPENING
 PROTECTIVES SHALL BE PERMITTED WHEN AN APPROVED
 AUTOMATIC SPRINKLER SYSTEM IS INSTALLED.
  
 S. THOMAS
 561-804-4728

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2020-05-18 Cont ID  
Sent By rmcphers Date 2020-05-18 Time 14:26 Rev Time 0.00
Received By rmcphers Date 2020-05-06 Time 07:52 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-04-23 Cont ID  
Sent By rmcphers Date 2020-04-23 Time 15:31 Rev Time 0.00
Received By rmcphers Date 2020-04-15 Time 16:30 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-03-31 Cont ID  
Sent By shill Date 2020-03-31 Time 15:41 Rev Time 0.00
Received By shill Date 2020-03-25 Time 08:19 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2020-03-30 Cont ID  
Sent By ccole Date 2020-03-30 Time 16:49 Rev Time 0.00
Received By ccole Date 2020-03-30 Time 15:05 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2020-03-31 Cont ID  
Sent By thunt Date 2020-03-31 Time 09:54 Rev Time 0.00
Received By tklarge Date 2020-03-31 Time 09:13 Sent To  
Notes
2020-03-31 09:56:55THERE IS NO PLUMBING SHOWN ON THE PLANS FOR THIS
 PROJECT.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2020-04-23 Cont ID  
Sent By rmcphers Date 2020-04-23 Time 15:31 Rev Time 0.00
Received By rmcphers Date 2020-04-23 Time 15:31 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-03-31 Cont ID  
Sent By rmcphers Date 2020-03-31 Time 08:40 Rev Time 0.00
Received By rmcphers Date 2020-03-31 Time 08:40 Sent To  
Notes
2020-03-31 08:41:13ARCHITECTURAL DRAWINGS DO NOT SHOW AS ELECTRONICALLY
 SIGNED IN "ADOBE" .