Plan Review Details - Permit 20031208
Plan Review Stops For Permit 20031208
Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-09-21 Cont ID  
Sent By medwards Date 2021-09-21 Time 10:08 Rev Time 0.00
Received By medwards Date 2021-09-20 Time 06:37 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-03-31 Cont ID  
Sent By lmarchan Date 2020-03-31 Time 16:53 Rev Time 0.00
Received By lmarchan Date 2020-03-26 Time 10:41 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2021-09-21 Cont ID  
Sent By medwards Date 2021-09-21 Time 10:06 Rev Time 0.00
Received By medwards Date 2021-09-21 Time 09:55 Sent To  
Notes
2021-09-21 10:07:52REVISION WAS FROM THE INSPECTOR WANTED TO SEE THE
 ANCHORAGE DETAILS OF THE UNITS ON THE ROOF. ME

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2020-03-27 Cont ID  
Sent By ccole Date 2020-03-27 Time 08:26 Rev Time 0.00
Received By medwards Date 2020-03-27 Time 07:49 Sent To  
Notes
2020-03-27 08:27:391ST REVIEW FBC-2017 MECHANICAL
 PERMIT- 20031208
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE PROVIDE MORE INFORMATION: DRAWINGS SHOWING
 LOCATION UNITS WILL BE LOCATED, NUMBER OF UNITS TO BE
 INSTALLED.
 2) PLEASE PROVIDE ENERGY GAUGE AND MANUAL S FOR EACH
 UNIT. FBC EC 101.5.1.1.2.
  
 3) . ANCHORAGE OF APPLIANCES ? FBC M 301.15
  
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status N Date 2020-03-31 Cont ID  
Sent By medwards Date 2020-03-31 Time 16:46 Rev Time 0.00
Received By medwards Date 2020-03-31 Time 16:34 Sent To  
Notes
2020-03-31 16:48:11SIGNATURE REVIEW IS NOT REQUIRED AT THIS TIME. ONCE THE
 CONTRACTOR SENDS IN THE REQUIRED DOCUMENTATION A
 SIGNATURE REVIEW WILL BE REQUIRED.