Plan Review Details - Permit 20031184
Plan Review Stops For Permit 20031184
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2020-03-27 Cont ID  
Sent By rmcphers Date 2020-03-27 Time 15:06 Rev Time 0.00
Received By rmcphers Date 2020-03-27 Time 15:06 Sent To  
Notes
2020-03-27 15:07:10ASBESTOS ? PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM
 THE CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-03-27 Cont ID  
Sent By rmcphers Date 2020-03-27 Time 15:06 Rev Time 0.00
Received By rmcphers Date 2020-03-27 Time 13:23 Sent To  
Notes
2020-03-27 14:36:23CHANGE OF OCCUPANCY
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
  
 CORRECTIONS NEEDED -
 1) JOB APPEARS TO BE A CHANGE OF OCCUPANCY FROM AN R2
 TO AN ALF WHICH MAYBE R4 OR I - PLEASE CLARIFY - SEE
 FBC CHAPTER 3.
 2) PLEASE SHOW FIRE RATED WALLS BETWEEN UNITS TO COMPLY
 WITH FBC 420.2
 3) PLEASE SHOW THE FIRE RATED "HORIZONTAL SEPARATION"
 FROM THE UNIT ABOVE TO COMPLY WITH FBC 420.3
 4) PLEASE SHOW THE NUMBER OF PERSONS TO OCCUPY THE
 BUILDING.
 5) PLEASE SHOW THAT THE BUILDING HAS OR ADDING FIRE
 SPRINKLERS TO COMPLY WITH FBC 420.5
 6) DRAWING A2 SHOWS WIND LOAD PER FBC 1606 - SHOULD BE
 FBC 1609 (WIND SPEED 170MPH AND ASCE 7-10)
 7) DOOR NUMBER 1 IS NOT SHOWN ON THE DOOR SCHEDULE.
 8) PLEASE PROVIDE COMPLETE (FRONT PAGES AND THE
 INSTALLATION INSTRUCTIONS) MIAMI DADE OR FLORIDA STATE
 PRODUCT APPROVAL FOR THE NEW EXTERIOR WINDOWS AND
 DOORS.
 THIS MAY NOT BE A COMPLETE LIST OF REQUIREMENTS THE
 OCCUPANCY CLASSIFICATION HAS NOT BEEN DETERMINED.
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-04-01 Cont ID  
Sent By ppetty Date 2020-04-01 Time 09:58 Rev Time 0.00
Received By ppetty Date 2020-04-01 Time 08:04 Sent To  
Notes
2020-04-01 09:58:51CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1.PROVIDE ACCURATE LOAD CALCULATION INCLUDING ALL
 LOADS. NEC 220; FBC RE E3602.2
 2.NOTE ALL NEW AND OLD WORK.
 3.IS THIS A CHANGE OF USE?
 4.VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS
 LOW. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND
 VALUE OF WORK, TO INCLUDE ALL MATERIALS AND LABOR. THIS
 IS FOR TOTAL PROJECT, NOT JUST ELECTRICAL. WPB FBC
 109.3
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 PHIL PETTY
 ELECTRICAL PLANS EXAMINER
 561-805-6742
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2020-03-25 Cont ID  
Sent By pleduc Date 2020-03-25 Time   Rev Time 0.00
Received By pleduc Date 2020-03-25 Time 10:55 Sent To  
Notes
2020-03-25 11:14:47THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THERE ARE INDICATIONS OF AN ALF OCCUPANCY.
  
 PER THE LIFE SAFETY CODE THIS IS A RESIDENTIAL BOARD
 AND CARE OCCUPANCY, PER NFPA 101 CHAPTER 32
  
 32.1.1.3 GENERAL. THE PROVISIONS OF CHAPTER 4, GENERAL,
 SHALL
 APPLY.
 32.1.1.4 RESERVED.
 32.1.1.5 CHAPTER SECTIONS. THIS CHAPTER IS DIVIDED INTO
 FIVESECTIONS AS FOLLOWS:
 (1) SECTION 32.1 ? GENERAL REQUIREMENTS
 (2) SECTION 32.2 ? SMALL FACILITIES (THAT IS, SLEEPING
 ACCOMMODATIONS FOR NOT MORE THAN 16 RESIDENTS)
 (3) SECTION 32.3 ? LARGE FACILITIES (THAT IS, SLEEPING
 ACCOMMODATIONS FOR MORE THAN 16 RESIDENTS)
 (4) SECTION 32.4 ? SUITABILITY OF AN APARTMENT BUILDING
 TO
 HOUSE A BOARD AND CARE OCCUPANCY (SECTIONS 32.5 AND
 32.6
 ARE RESERVED.)
  
 WHAT IS THE PROPOSED OCCUPANCY SLEEPING ACCOMODATIONS?
  
 PLEASE PROVIDE AN APPLICABLE NOTE AND ENSURE THAT THIS
 OCCUPANCY IS REVIEWED WITH THIS CODE INCLUDING, BUT NOT
 LIMITED TO, THE ITEM BELOW.
  
  
  
 2) THERE DOES NOT APPEAR TO BE A FIRE ALARM SYSTEM
  
 32.2.3.4 DETECTION, ALARM, AND COMMUNICATIONS SYSTEMS.
 32.2.3.4.1 GENERAL. A MANUAL FIRE ALARM SYSTEM SHALL BE
 PROVIDED
 IN ACCORDANCE WITH SECTION 9.6.
 32.2.3.4.2 OCCUPANT NOTIFICATION. OCCUPANT NOTIFICATION
 SHALL BE
 PROVIDED AUTOMATICALLY, WITHOUT DELAY, IN ACCORDANCE
 WITH 9.6.3.
  
 IF EXISTING, ALL WORK ON THE FIRE ALARM SHALL BE UNDER
 SEPARATE PERMIT AND SHOP DRAWINGS.
  
 PLEASE REVIEW AND CORRECT OR PROVIDE IS A SYSTEM IS
 EXISITNG.
  
  
 3) THERE DOES NO APPEAR TO BE AN INDICATION OF FIRE
 SPRINKLER SYSTEM
  
 32.2.3.5* EXTINGUISHMENT REQUIREMENTS.
 32.2.3.5.1* ALL FACILITIES, OTHER THAN THOSE MEETING
 THE
 REQUIREMENT OF 32.2.3.5.2, SHALL BE PROTECTED
 THROUGHOUT BY AN
 APPROVED AUTOMATIC SPRINKLER SYSTEM, INSTALLED IN
 ACCORDANCE WITH
 32.2.3.5.3, USING QUICK-RESPONSE OR RESIDENTIAL
 SPRINKLERS.
 32.2.3.5.2* IN CONVERSIONS, SPRINKLERS SHALL NOT BE
 REQUIRED IN
 SMALL BOARD AND CARE HOMES SERVING EIGHT OR FEWER
 RESIDENTS WHEN
 ALL OCCUPANTS HAVE THE ABILITY AS A GROUP TO MOVE
 RELIABLY TO A
 POINT OF SAFETY WITHIN 3 MINUTES.
 32.2.3.5.3 WHERE AN AUTOMATIC SPRINKLER SYSTEM IS
 INSTALLED, FOR
 EITHER TOTAL OR PARTIAL BUILDING COVERAGE, ALL OF THE
 FOLLOWING
 REQUIREMENTS SHALL BE MET:
 (1) THE SYSTEM SHALL BE IN ACCORDANCE WITH NFPA 13,
 STANDARD
 FOR THE INSTALLATION OF SPRINKLER SYSTEMS, AND SHALL
 INITIATE THE
 FIRE ALARM SYSTEM IN ACCORDANCE WITH 32.2.3.4.1.
 (2) THE ADEQUACY OF THE WATER SUPPLY SHALL BE
 DOCUMENTED TO THE
 AUTHORITY HAVING JURISDICTION.
 32.2.3.5.3.1 IN BUILDINGS FOUR OR FEWER STORIES ABOVE
 GRADE PLANE,
 SYSTEMS IN ACCORDANCE WITH NFPA 13R, STANDARD FOR THE
 INSTALLATION OF SPRINKLER SYSTEMS IN LOW-RISE
 RESIDENTIAL
 OCCUPANCIES, SHALL BE PERMITTED. ALL HABITABLE AREAS,
 CLOSETS,
 ROOFED PORCHES, ROOFED DECKS, AND ROOFED BALCONIES
 SHALL BE
 SPRINKLERED.
  
 PLEASE REVIEW AND PROVIDE SIGNED AND SEALED, 61G
 COMPLIANT FIRE SPRINKLER PLANS WITH THIS PERMIT.
  
  
  
 4) THERE DOES NOT APPEAR TO BE SECONDARY ESCAPE WINDOWS
  
 32.2.2.3 SECONDARY MEANS OF ESCAPE.
 32.2.2.3.1 SLEEPING ROOMS, OTHER THAN THOSE COMPLYING
 WITH
 32.2.2.3.2 OR 32.2.2.3.3, AND LIVING AREAS IN
 FACILITIES WITHOUT A
 SPRINKLER SYSTEM INSTALLED IN ACCORDANCE WITH 32.2.3.5
 SHALL HAVE A
 SECOND MEANS OF ESCAPE CONSISTING OF ONE OF THE
 FOLLOWING:
 (1) DOOR, STAIRWAY, PASSAGE, OR HALL PROVIDING A WAY OF
 UNOBSTRUCTED TRAVEL TO THE OUTSIDE OF THE DWELLING AT
 STREET OR
 THE FINISHED GROUND LEVEL THAT IS INDEPENDENT OF, AND
 REMOTELY LOCATED FROM, THE PRIMARY MEANS OF ESCAPE
 (2) PASSAGE THROUGH AN ADJACENT NONLOCKABLE SPACE
 INDEPENDENT
 OF, AND REMOTELY LOCATED FROM, THE PRIMARY MEANS OF
 ESCAPE
 TO ANY APPROVED MEANS OF ESCAPE
 (3) *OUTSIDE WINDOW OR DOOR OPERABLE FROM THE INSIDE,
 WITHOUT
 THE USE OF TOOLS, KEYS, OR SPECIAL EFFORT, THAT
 PROVIDES A CLEAR
 OPENING OF NOT LESS THAN 5.7 FT2 (0.53 M2), WITH THE
 WIDTH NOT
 LESS THAN 20 IN. (510 MM), THE HEIGHT NOT LESS THAN 24
 IN. (610
 MM), AND THE BOTTOM OF THE OPENING NOT MORE THAN 44 IN.
 (1120 MM) ABOVE THE FLOOR, WITH SUCH MEANS OF ESCAPE
 ACCEPTABLE, PROVIDED THAT ONE OF THE FOLLOWING CRITERIA
 IS MET:
 (A) THE WINDOW IS WITHIN 20 FT (6100 MM) OF THE
 FINISHED
 GROUND LEVEL.
 (B) THE WINDOW IS DIRECTLY ACCESSIBLE TO FIRE
 DEPARTMENT
 RESCUE APPARATUS, AS APPROVED BY THE AHJ.
 (C) THE WINDOW OR DOOR OPENS ONTO AN EXTERIOR BALCONY.
 (4) WINDOWS HAVING A SILL HEIGHT BELOW THE ADJACENT
 FINISHED
 GROUND LEVEL THAT ARE PROVIDED WITH A WINDOW WELL
 MEETING
 THE FOLLOWING CRITERIA:
 (A) THE WINDOW WELL HAS HORIZONTAL DIMENSIONS THAT
 ALLOW
 THE WINDOW TO BE FULLY OPENED.
 (B) THE WINDOW WELL HAS AN ACCESSIBLE NET CLEAR OPENING
 OF
 NOT LESS THAN 9 FT2 (0.84 M2), WITH A LENGTH AND WIDTH
 OF
 NOT LESS THAN 36 IN. (915 MM).
 (C) A WINDOW WELL WITH A VERTICAL DEPTH OF MORE THAN 44
 IN.
 (1120 MM) IS EQUIPPED WITH AN APPROVED PERMANENTLY
 AFFIXED LADDER OR WITH STEPS MEETING THE FOLLOWING
 CRITERIA:
 I. THE LADDER OR STEPS DO NOT ENCROACH MORE THAN 6 IN.
 (150 MM) INTO THE REQUIRED DIMENSIONS OF THE
 WINDOW WELL.
 II. THE LADDER OR STEPS ARE NOT OBSTRUCTED BY THE
 WINDOW.
 32.2.2.3.2 SLEEPING ROOMS THAT HAVE A DOOR LEADING
 DIRECTLY TO THE
 OUTSIDE OF THE BUILDING WITH ACCESS TO THE FINISHED
 GROUND LEVEL OR
 TO AN EXTERIOR STAIRWAY MEETING THE REQUIREMENTS OF
 32.2.2.6.3
 SHALL BE CONSIDERED AS MEETING ALL THE REQUIREMENTS FOR
 A SECOND
 MEANS OF ESCAPE.
 32.2.2.3.3 SLEEPING ROOMS SHALL NOT BE REQUIRED TO HAVE
 A
 SECONDARY MEANS OF ESCAPE WHERE THE CLINICAL NEEDS OF
 THE
 RESIDENTS REQUIRE SPECIAL SECURITY MEASURES, PROVIDED
 ALL OF THE
 FOLLOWING ARE MET:
 (1) THE BUILDING IS PROTECTED THROUGHOUT BY AN APPROVED
 AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE WITH 32.3.3.5.
 (2) A FIRE ALARM SYSTEM IS PROVIDED IN ACCORDANCE WITH
 32.3.3.4.1 THROUGH 32.3.3.4.3 AND 32.3.3.4.6.
 (3) SMOKE DETECTORS ARE PROVIDED IN ACCORDANCE WITH
 32.3.3.4.8.
  
 PLEASE REVIEW AND PROVIDE AS APPLICABLE.
  
  
  
 5) THE DOOR SCEDULE DOES NO INDICATE COMPLIANCE WITH
 THE FOLLOWING:
  
 32.2.2.5.3 EVERY CLOSET DOOR LATCH SHALL BE READILY
 OPENED FROM
 THE INSIDE.
 32.2.2.5.4 EVERY BATHROOM DOOR SHALL BE DESIGNED TO
 ALLOW
 OPENING FROM THE OUTSIDE DURING AN EMERGENCY WHEN
 LOCKED.
 32.2.2.5.5 NO DOOR IN ANY MEANS OF ESCAPE, OTHER THAN
 THOSE
 MEETING THE REQUIREMENT OF 32.2.2.5.5.1, 32.2.2.5.5.2,
 OR
 32.2.2.5.5.3, SHALL BE LOCKED AGAINST EGRESS WHEN THE
 BUILDING IS
 OCCUPIED.
 32.2.2.5.5.1 DELAYED-EGRESS LOCKS COMPLYING WITH
 7.2.1.6.1 SHALL
 BE PERMITTED ON EXTERIOR DOORS ONLY.
 32.2.2.5.5.2 ACCESS-CONTROLLED EGRESS DOOR ASSEMBLIES
 COMPLYING
 WITH 7.2.1.6.2 SHALL BE PERMITTED.
 32.2.2.5.5.3 DOOR-LOCKING ARRANGEMENTS SHALL BE
 PERMITTED WHERE
 THE CLINICAL NEEDS OF RESIDENTS REQUIRE SPECIALIZED
 SECURITY
 MEASURES OR WHERE RESIDENTS POSE A SECURITY THREAT,
 PROVIDED ALL OF
 THE FOLLOWING CONDITIONS ARE MET:
 (1) STAFF CAN READILY UNLOCK DOORS AT ALL TIMES IN
 ACCORDANCE WITH
 32.2.2.5.5.4.
 (2) THE BUILDING IS PROTECTED BY AN APPROVED AUTOMATIC
 SPRINKLER
 SYSTEM IN ACCORDANCE WITH 32.2.3.5.
 (3) THE PROVISION OF 32.2.3.5.2 FOR CONVERSIONS IS NOT
 BE
 PERMITTED TO BE USED.
 32.2.2.5.5.4 DOORS LOCATED IN THE MEANS OF EGRESS AND
 PERMITTED TO
 BE LOCKED IN ACCORDANCE WITH 32.2.2.5.5.3 SHALL COMPLY
 WITH ALL OF
 THE FOLLOWING:
 (1) PROVISIONS SHALL BE MADE FOR THE RAPID REMOVAL OF
 OCCUPANTS
 BY MEANS OF ONE OF THE FOLLOWING:
 (A) REMOTE CONTROL OF LOCKS FROM WITHIN THE LOCKED
 BUILDING
 (B) KEYING OF ALL LOCKS TO KEYS CARRIED BY STAFF AT ALL
 TIMES
 (C) OTHER SUCH RELIABLE MEANS AVAILABLE TO STAFF AT ALL
 TIMES
 (2) ONLY ONE LOCKING DEVICE SHALL BE PERMITTED ON EACH
 DOOR.
 32.2.2.5.6 FORCES TO OPEN DOORS SHALL COMPLY WITH
 7.2.1.4.5.
 32.2.2.5.7 DOOR-LATCHING DEVICES SHALL COMPLY WITH
 7.2.1.5.10.
  
 PLEAE PROVIDE DETAILS IN COMPLIANCE.
  
  
  
 6) THE CORRIDOR WALLS DO NOT INDICATE THE FOLLOWING:
  
 32.2.3.6 CONSTRUCTION OF CORRIDOR WALLS.
 32.2.3.6.1 CORRIDOR WALLS, OTHER THAN THOSE MEETING THE
 PROVISIONS
 OF 32.2.3.6.2, SHALL MEET ALL OF THE FOLLOWING
 REQUIREMENTS:
 (1) WALLS SEPARATING SLEEPING ROOMS SHALL HAVE A
 MINIMUM ?-
 HOUR FIRE RESISTANCE RATING. THE MINIMUM ?-HOUR FIRE
 RESISTANCE RATING SHALL BE CONSIDERED TO BE ACHIEVED IF
 THE
 PARTITIONING IS FINISHED ON BOTH SIDES WITH LATH AND
 PLASTER OR
 MATERIALS PROVIDING A 15-MINUTE THERMAL BARRIER.
 (2) SLEEPING ROOM DOORS SHALL BE SUBSTANTIAL DOORS,
 SUCH AS THOSE
 OF 1? IN. (44 MM) THICK, SOLID-BONDED WOOD-CORE
 CONSTRUCTION
 OR OF OTHER CONSTRUCTION OF EQUAL OR GREATER STABILITY
 AND FIRE
 INTEGRITY.
 (3) ANY VISION PANELS SHALL BE FIXED FIRE WINDOW
 ASSEMBLIES IN
 ACCORDANCE WITH 8.3.4 OR SHALL BE WIRED GLASS NOT
 EXCEEDING 9
 FT2 (0.84 M2) EACH IN AREA AND INSTALLED IN APPROVED
 FRAMES.
  
  
  
 7) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
  
 8) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-05-22 Cont ID  
Sent By ppetty Date 2020-05-22 Time 11:28 Rev Time 0.00
Received By rsklarew Date 2020-03-24 Time 15:45 Sent To  
Notes
2020-03-24 15:46:01B05

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2020-03-27 Cont ID  
Sent By rmcphers Date 2020-03-27 Time 15:07 Rev Time 0.00
Received By rmcphers Date 2020-03-27 Time 15:07 Sent To  
Notes
2020-03-27 15:08:49PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE OFFICE. CALL
 (561) 233-5025. UPON APPROVAL, YOU MAY CHECK OUT ONE
 PLAN SET AND TAKE TO THAT OFFICE FOR REVIEW. PLEASE
 RETURNED STAMPED AND WITH A COPY OF THE RECEIPT AS
 APPLICABLE. PLEASE PROVIDE THE MUNICIPAL IMPACT FEE
 QUESTIONNAIRE FORM TO THE PBC IMPACT FEE OFFICE. THE
 FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/AD
 MINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2020-03-26 Cont ID  
Sent By medwards Date 2020-03-26 Time 16:33 Rev Time 0.00
Received By medwards Date 2020-03-26 Time 16:16 Sent To  
Notes
2020-03-26 16:34:031ST REVIEW FBC-2017 MECHANICAL
 PERMIT- 20031184
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE PROVIDE SPEC SHEETS FOR THE MECHANICAL
 SYSTEMS. FBC M 309.
 2) PLEASE PROVIDE ENERGY GAUGE AND MANUAL S
 CALCULATIONS FOR THE NEW MECHANICAL EQUIPMENT. FBC EC
 101.5.1.1.2; FBC M 403.7.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2020-03-30 Cont ID  
Sent By ccole Date 2020-03-30 Time 10:53 Rev Time 0.00
Received By ccole Date 2020-03-30 Time 09:11 Sent To  
Notes
2020-03-30 11:19:551ST REVIEW FBC-2017 MECHANICAL
 PERMIT #20031184
 3/30/20
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET A.2: THE PROPOSED PROJECT IS A CHANGE OF
 OCCUPANCY FROM EITHER AN R-2 TO AN R-4 OR AN I-1
 HOWEVER NO OCCUPANT LOAD HAS BEEN PROVIDED TO MAKE THAT
 DETERMINATION- SEE SECTIONS 420.1, 308.3, & 310.6 FBC
 B.
  
 2) REFER TO SECTION 202.3 FBC ACC: THE NEW BATHROOMS
 SHALL BE DESIGNED IN ACCORDANCE WITH CHAPER 6 OF THE
 FBC AA. PLEASE PROVIDE ENLARGED BATHROOM DRAWINGS
 SHOWING ALL REQUIRED CLEAR FLOOR SPACES AND
 INSTALLATION REQUIREMENTS FOR FIXTURES AND ACCESSORIES-
 REFER TO SECTIONS 603, 604, 606, 607, 609, & 610 FBC
 ACC. NOTE: NO LAUNDRY FACILITES ARE SHOWN ON THE PLANS,
 BUT IF INSTALLED THE WASHING MACHINE AND CLOTHES DRYER
 SHALL BE INSTALLED IN ACCORDANCE WITH SECTION 611.
  
 3) P-1: REFER TO TABLE 403.1 FBC P AND PROVIDE A
 SCHEDULE ON THE PLAN INDICATING THE NUMBER OF REQUIRED
 PLUMBING FIXTURES TO BE INSTALLED FOR BOTH MALE AND
 FEMALE USE. PLEASE NOTE THAT BOTH I-1 AND R-4
 OCCUPANCIES REQUIRE THE INSTALLATION OF SERVICE SINKS
 AND DRINKING FOUNTAINS WHICH ARE SHOWN ON THE PLANS AND
 PROPOSD TO BE INSTALLED. PLEASE REVISE THE PLANS TO
 SHOW THE FIXTURE LOCATIONS, ADD THEM TO THE ISOMETRIC
 DRAWING ON SHEET P-3, AND PROVIDE ACCESSIBILITY DETAILS
 FOR THE DRINKING FOUNTAIN- SECTION 602 FBC ACC.
  
 4) P-1: LABEL THE BATHROOMS AS EITHER MALE OR FEMALE-
 SECTION 403.2 FBC P.
  
 5) P-1 & P-2: SHOW THE LOCATION OF THE NEW WATER HEATER
 WITH THE REQUIRED SEVICE ACCESS AND 30X30" WORKING
 SPACE- SECTIONS 501.4 & 502.5 FBC P. PLEASE SUBMIT A
 SPEC SHEET FOR THE WATER HEATER.
  
 6) P-2: REFER TO SECTION 607.3 FBC P. A THERMAL
 EXPANSION CONTROL DEVICE MAY BE REQUIRED TO BE
 INSTALLED ON THE COLD WATER SUPPLY PIPE IF THERE IS THE
 COLD WATER SUPPLY PASSES THROUGH A CHECK OR PRESSURE
 REDUCING VALVE, OR A BACKFLOW PREVENTER- SECTION 607.3
 FBC P.
  
 7) P-3: PROVIDE A WATER RISER DRAWING- SECTION 604.2
 FBC P. THE RISER SHALL INDICATE PIPE SIZES, LOCATIONS
 OF SHUT OFF VALVES, LOCATIONS OF HAMMER ARRESTORS,
 MIXING VALVES ETC- SECTION 107.2.1 WPB.
  
 8) THE $16,000 PROJECT COST ON THE PERMIT APPLICATION
 APPEARS VERY LOW FOR THE ENTIRE SCOPE OF WORK SHOWN
 THUS FAR ON THE PLANS. PLEASE PROVIDE COPIES OF SIGNED
 CONTRACTS, AND/OR ESTIMATES, INVOICES ETC. FOR ALL
 PHASES OF THE PROJECT INCLUDING BUILDING, MECHANICAL,
 ELECTRICAL, PLUMBING, INTERIOR AND EXTERIOR
 ARCHITECTURAL FINISHES, SITE WORK, AND DESIGN FEES. THE
 TOTAL COST SHALL INCLUDE LABOR, MATERIALS, FIXTURES,
 APPLIANCES, AND EQUIPMENT- SECTION 109.3 WPB.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop Z ZONING
Rev No 1 Status F Date 2020-05-20 Cont ID  
Sent By rthermid Date 2020-05-20 Time   Rev Time 0.00
Received By rthermid Date 2020-05-20 Time   Sent To I
Notes
2020-05-20 07:32:46ZONING PLAN REVIEW
 ________________________________________
  
 DATE OF REVIEW:
 ________________________________________
  
 REVIEW STATUS: FAILED
 ________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. PROVIDE CLEAR DESCRIPTION OF THE SCOPE OF WORK ON
 THE PLANS.
  
 2. SPECIFY THE TYPE OF USE THIS PROPERTY IS CHANGING TO
 AS THERE ARE PARKING REQUIREMENTS DEPENDING ON THE
 NUMBER OF RESIDENTS, AND SERVICES PROVIDED. CODE
 SECTION 96-611 AND SECTION 94-486 OF THE ZLDR
  
 ________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 IF THE RESUBMITTAL IS NOT PREPARED BY A DESIGN
 PROFESSIONAL (ARCHITECT OR ENGINEER), AND THE PAGES ARE
 11X17 OR SMALLER, YOU MAY RESUBMIT, ALONG WITH A
 COMPLETED RESUBMITTAL FORM, VIA EMAIL TO
 [email protected]. THE EMAIL SHOULD INCLUDE THE PERMIT
 NUMBER AND "RESUBMITTAL" IN THE SUBJECT LINE. THE
 RESUBMITTAL FORM CAN BE FOUND AT THIS WEBSITE:
  
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS
  
 IF THE FORM IS TEMPORARILY UNAVAILABLE, PLEASE REQUEST
 THAT IT BE SENT TO YOU BY EMAILING [email protected]
 ________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 RAFAELA THERMIDOR, ASSOCIATE PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1443
 TTY: 800.955.8771
 E: [email protected]
  
 W: WPB.ORG


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved