| 2020-04-03 05:56:39 | 2017 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 20031182 |
| | ADD: 512 BAKER DR. |
| | CONT: MONICA ROSSI CONSTRUCTION |
| | TEL: 561-270-9242 |
| | E-MAIL: [email protected] |
| | |
| | 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION. |
| | |
| | CODE 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL |
| | NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: MONDAY MARCH 30/2020 |
| | ACTION: DENIED |
| | |
| | 1) THE VALUE FOR THE REMOVAL, DISPOSAL OF 2 DOORS, |
| | PURCHASING 2 DOORS AND INSTALLATION OF THE 2 DOORS IS |
| | EXTREMELY LOW. |
| | W 2017 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1 ADMINISTRATIVE CODE 108.3* |
| | BUILDING PERMIT VALUATION. IF, IN THE OPINION OF THE |
| | BUILDING OFFICIAL, THE CLAIMED VALUATION OF BUILDING, |
| | ALTERATION, STRUCTURE, ELECTRICAL, GAS, MECHANICAL, OR |
| | PLUMBING SYSTEMS APPEARS TO BE UNDER ESTIMATED ON THE |
| | APPLICATION, THE PERMIT SHALL BE DENIED. FOR PERMITTING |
| | PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL BE |
| | TOTAL REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND |
| | SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE |
| | STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR |
| | FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR |
| | BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING |
| | COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE. |
| | VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED |
| | DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES |
| | (MARSHALL-SWIFT, MEANS, ETC.) WITH REGIONAL ADJUSTMENTS |
| | FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE |
| | CONGRESS. |
| | 2) 107.3.5. MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS. |
| | MISSING FLOOR PLAN SHOWING THE LOCATION OF THE EXTERIOR |
| | DOORS THAT ARE BEING REPLACED. ALSO INDICATE ROOM USAGE |
| | ON THE FLOOR PLAN. PROVIDE THE SIZE OF THE DOOR AND |
| | DISTANCE FROM THE CORNER OF THE DWELLING UNIT. |
| | 107.2.1.2 ADDITIONAL INFORMATION IS REQUIED. |
| | |
| | 3) 107.3.4.3 CERTIFICATION BY CONTRACTOR. PLEASE NOTE |
| | THE EXCEPTION TO ENGINEERED PLANS UNDER 471.003(H) |
| | ELECTRICAL/ PLUMBING/ MECHANICAL, 481.229(1)(C) |
| | (BUILDING) REQUIRES THE CONTRACTOR TO BE LICENSED IN |
| | THE TRADE THAT THEY WILL BE CREATING THE PLANS TO BE |
| | SUBMITTED TO THE BUILDING DEPARTMENT. FOR EACH TRADE |
| | THE CONTRACTOR RESPONSIBLE FOR THE PLAN MUST PRINT |
| | THEIR NAME, SIGN THEIR NAME AND LICENSE NUMBER. |
| | |
| | 4) MISSING WIND DESIGN CRITERIA. 2017 FBC-B 1603.1.4 |
| | WIND DESIGN DATA. THE FOLLOWING INFORMATION RELATED TO |
| | WIND LOADS SHALL BE SHOWN, REGARDLESS OF WHETHER WIND |
| | LOADS GOVERN THE DESIGN OF THE LATERAL FORCE-RESISTING |
| | SYSTEM OF THE STRUCTURE: |
| | |
| | 4.1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST), |
| | MILES PER HOUR AND NOMINAL DESIGN WIND SPEED, VASD, AS |
| | DETERMINED IN ACCORDANCE WITH SECTION 1609.3.1. |
| | |
| | 4.2. RISK CATEGORY. |
| | |
| | 4.3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE |
| | THAN ONE WIND EXPOSURE IS UTILIZED. TABLE 1609.7.2. |
| | HEIGHT AND EXPOSURE. |
| | |
| | 4.4. APPLICABLE INTERNAL PRESSURE COEFFICIENT. |
| | |
| | 4.5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR |
| | COMPONENTS AND CLADDING MATERIALS NOT SPECIFICALLY |
| | DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL |
| | RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE, PSF. |
| | |
| | 4.6 TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT & |
| | EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE |
| | BUILDING. 1609.3.1 WIND SPEED CONVERSION VULT TO VASD. |
| | |
| | |
| | 5) COMPONENTS & CLADDING. 2017 FBC-B 1609.1.2 |
| | PROTECTION OF OPENINGS, 1609.6.4.4.1 COMPONENTS & |
| | CLADDING. FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS, |
| | ADMINISTRATIVE CODE 61G20-3.005, RULE 9N-3 NOV. 01/ |
| | 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION |
| | SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: |
| | (31)(A) EXTERIOR DOORS ,MULLIONS & SIDELIGHTS. |
| | |
| | 6) IDENTIFY GLAZING/ MULLIONS. THE SUBMITTED PRODUCT |
| | APPROVALS THE ELEMENTS LISTED BELOW ARE NOT IDENTIFIED. |
| | PLEASE IDENTIFY ON THE PRODUCT APPROVAL BEFORE |
| | SUBMITTING TO DESIGNER OF RECORD AND BEFORE SUBMISSION |
| | TO THE BUILDING DEPARTMENT. FOR ALL PRODUCTS WITH |
| | GLAZING, PLEASE IDENTIFY THE OPENING WIDTH & HEIGHT, |
| | TYPE OF GLAZING, MULLION SIZE, LENGTH IF UNREINFORCED |
| | OR REINFORCED INFORMATION IF REQUIRED, ATTACHMENTS AND |
| | ASSOCIATE PRESSURES FOR EACH OPENING SIZE. 2017 FBC-B |
| | 1405.13.1 INSTALLATION. WINDOWS AND DOORS SHALL BE |
| | INSTALLED IN ACCORDANCE WITH APPROVED MANUFACTURER?S |
| | INSTRUCTIONS. FASTENER SIZE AND SPACING SHALL BE |
| | PROVIDED IN SUCH INSTRUCTIONS AND SHALL BE CALCULATED |
| | BASED ON MAXIMUM LOADS AND SPACING USED IN THE TESTS. |
| | |
| | 7) THE SUBMITTED PRODUCT APPROVAL 4940-R7 MASONITE |
| | INTERNATIONAL ONLY HAS THE COVER SHEETS 1-3 SUBMITTED. |
| | NONE OF THE 5 SUB-SYSTEMS ARE HIGHLIGHTED AND NONE OF |
| | THE TECHNICAL SHEETS WERE LOADED. A THROUGH PLAN REVIEW |
| | COULD NOT BE COMPLETED AT THIS TIME BECAUSE OF THE |
| | MISSING DOCUMENTS. |
| | 8) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE |
| | THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED |
| | DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE |
| | MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS |
| | AND INFORMATION LACKING UNDER THE PRIOR REVIEW. |
| | |
| | |
| | JAMES A. WITMER BN, PX, SFP & CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT |
| | 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 |
| | TEL: 561-805-6717 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |
| | |
| | |
| | |
| | |