Plan Review Details - Permit 20031176
Plan Review Stops For Permit 20031176
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2020-04-10 Cont ID  
Sent By cpuell Date 2020-04-10 Time 14:51 Rev Time 0.00
Received By cpuell Date 2020-04-10 Time 14:51 Sent To  
Notes
2020-04-10 14:51:23GAVE @ ADDRESS

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-04-06 Cont ID  
Sent By rmcphers Date 2020-04-06 Time 10:32 Rev Time 0.00
Received By rmcphers Date 2020-04-06 Time 10:21 Sent To  
Notes
2020-04-06 10:33:39ELEC. EQUIPMENT
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) PLEASE SHOW THE ATTACHMENT OF THE ANTENNA BRACKET TO
 THE POLE ( ANCHOR TYPE, SIZE, AND AMOUNT OF ANCHORS).

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-04-01 Cont ID  
Sent By jpearson Date 2020-04-01 Time 14:07 Rev Time 0.00
Received By jpearson Date 2020-04-01 Time 14:07 Sent To  
Notes
2020-04-01 14:07:03CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR
 SERVICE INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR
 THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE
 SERVICE EQUIPMENT IS ADEQUATE. NEC 110.9, 110.10
 2. PROVIDE NOTES TO INDICATE THE REQUIRED MARKING OF
 SERVICE EQUIPMENT FOR ARC FLASH HAZARD WARNING AND
 AVAILABLE FAULT CURRENT PER CODE. NEC 110.16, 110.24
 3. VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS
 LOW. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND
 VALUE OF WORK, TO INCLUDE ALL MATERIALS AND LABOR. THIS
 IS FOR TOTAL PROJECT, NOT JUST ELECTRICAL. WPB FBC
 109.3
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, PROVIDE A RESPONSE LETTER ADDRESSING EACH
 ITEM ALONG WITH THE CITY RESUBMITTAL FORM.
 ADDITIONALLY, INSERT CORRECTED PAGES INTO THE ORIGINAL
 SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS.
 ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD
 REMAIN IN PACKAGE AND BE MARKED OLD SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-04-10 Cont ID  
Sent By cpuell Date 2020-04-10 Time 14:51 Rev Time 0.00
Received By cpuell Date 2020-03-27 Time 13:28 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-04-01 Cont ID  
Sent By jpearson Date 2020-04-01 Time 14:05 Rev Time 0.00
Received By jpearson Date 2020-04-01 Time 14:05 Sent To  
Notes
2020-04-01 14:05:00ALL SHEETS THIS SUBMISSION ARE GOOD EXCEPT SURVEY. PER
 THE WPB AMENDMENTS TO THE FBC, EACH SHEET OF PLAN IS
 REQUIRED TO BE SIGNED AND SEALED BY THE PERSON
 RESPONSIBLE FOR THE DESIGN. A DIGITAL PLAN REQUIRES A
 DIGITAL SIGNATURE WITH THE PROPER THIRD PARTY
 VERIFICATION. PROVIDE CORRECTION. WPB FBC 107.1; FS
 471/481