| Plan Review Stops For Permit 20031138 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2020-06-01 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2020-06-01 |
Time |
09:24 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2020-06-01 |
Time |
09:24 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2020-05-05 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2020-05-05 |
Time |
11:21 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2020-05-05 |
Time |
09:48 |
Sent To |
|
|
| Notes |
| 2020-05-05 11:12:05 | GUEST HOUSE | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected]. | | | | | | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 | | | 1) ATTIC ACCESS - THE ROUGH-FRAMED OPENING SHALL BE NOT | | | LESS THAN 22 INCHES BY 30 INCHES FBC R807.1 | | | 2) FORM R405 ENERGY CALCS. AND THE DRAWINGS DO NOT | | | MATCH - PLEASE CLARIFY - ATTIC SPACE ENERGY CALCS. SAY | | | UNVENTED - DRAWINGS ATTIC SPACE SAYS VENTED. | | | 3) DON'T KNOW WHAT HAPPENED BUT, THE STRUCTURAL | | | DRAWINGS ARE MISSING (FOUNDATION, EXTERIOR WALL, ROOF | | | FRAMING, ROOF SHEATHING ETC.) |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2020-03-27 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2020-03-27 |
Time |
12:34 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2020-03-27 |
Time |
10:37 |
Sent To |
|
|
| Notes |
| 2020-03-27 11:59:59 | GUEST HOUSE | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | | | | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 | | | 1) PLEASE SHOW THE ATTIC ACCESS TO COMPLY WITH FBC | | | R807.1 | | | | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2020-05-06 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2020-05-06 |
Time |
15:26 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2020-05-06 |
Time |
14:29 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2020-03-30 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2020-03-30 |
Time |
09:20 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2020-03-30 |
Time |
08:43 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2020-06-01 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2020-06-01 |
Time |
09:28 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2020-05-27 |
Time |
13:48 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2020-05-27 |
|
|
Cont ID |
|
| Sent By |
lmarchan |
Date |
2020-05-27 |
Time |
12:01 |
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2020-04-24 |
Time |
08:45 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2020-04-03 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2020-04-03 |
Time |
17:23 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2020-03-24 |
Time |
13:37 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
2 |
Status |
P |
Date |
2020-06-02 |
|
|
Cont ID |
|
| Sent By |
lmarchan |
Date |
2020-06-02 |
Time |
13:28 |
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2020-06-01 |
Time |
10:54 |
Sent To |
|
|
| Notes |
| 2020-06-02 07:52:29 | MU-2020-18375 - $3501.02 - PAID | | 2020-06-01 10:54:56 | 6/1/20 EMAILED IMPACT FEE OFFICE FOR REVIEW. LEM |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
F |
Date |
2020-03-27 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2020-03-27 |
Time |
12:35 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2020-03-27 |
Time |
12:35 |
Sent To |
|
|
| Notes |
| 2020-03-27 12:36:48 | PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE OFFICE. CALL | | | (561) 233-5025. UPON APPROVAL, YOU MAY CHECK OUT ONE | | | PLAN SET AND TAKE TO THAT OFFICE FOR REVIEW. PLEASE | | | RETURNED STAMPED AND WITH A COPY OF THE RECEIPT AS | | | APPLICABLE. PLEASE PROVIDE THE MUNICIPAL IMPACT FEE | | | QUESTIONNAIRE FORM TO THE PBC IMPACT FEE OFFICE. THE | | | FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/AD | | | MINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2020-05-05 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2020-05-05 |
Time |
11:08 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2020-05-05 |
Time |
10:57 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2020-03-25 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2020-03-25 |
Time |
13:25 |
Rev Time |
|
| Received By |
medwards |
Date |
2020-03-25 |
Time |
|
Sent To |
|
|
| Notes |
| 2020-03-25 13:26:18 | 1ST REVIEW FBC-2017 MECHANICAL | | | PERMIT- 20031138 | | | | | | CODES IN EFFECT: | | | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION | | | 2017 | | | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION | | | 2017 | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH | | | EDITION 2017 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH | | | EDITION 2017 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | PLEASE PROVIDE THE MANUAL J CALCULATIONS AND SPECS FOR | | | THE REQUIRED HEATING SYSTEM. SEE: FBC FS- 107.2.1: FBC | | | EC- 101.5.1.1.2 | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD | | | SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER | | | SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN | | | THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS | | | PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS | | | PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR | | | UPDATED. | | | | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2020-05-08 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2020-05-08 |
Time |
07:55 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2020-05-07 |
Time |
16:37 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2020-03-31 |
|
|
Cont ID |
|
| Sent By |
lcrespo |
Date |
2020-03-31 |
Time |
17:26 |
Rev Time |
0.00 |
| Received By |
lcrespo |
Date |
2020-03-31 |
Time |
07:31 |
Sent To |
|
|
| Notes |
| 2020-03-31 17:28:02 | 03/31/20 1ST PLUMBING REVIEW **DENIED** WITH COMMENTS | | | | | | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS | | | TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE | | | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. | | | | | | 1. IS THE TANKLESS ELECTRIC OR GAS AND IF IT IS GOING | | | OUTSIDE ELECTRIC, THEY SHOULD BE RATED FOR OUTSIDE | | | ELEMENTS WHICH MOST ARE NOT. IF YOU PLAN ON PUTTING IT | | | IN AS CASE TO PROTECT IT FROM THE ELEMENTS IT NEEDS TO | | | BE APPROVED BY THE MANUFACTURE AND PLEASE SUBMIT | | | SPECIFICATIONS FOR UNIT AND OR CASE PER THE WPB | | | AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON | | | CONSTRUCTION DOCUMENTS. | | | | | | 2. ON P-3 THE ISOMETRIC ON TOILET AND SHOWER HAS NO | | | VENT FOR THE P-TRAP PLEASE WYE OFF BEFORE TOILET TO | | | PICK UP LABORATORY AWAY FROM THE WET VENT BATHROOM | | | GROUP PER THE 2017 FBC R 3101.2.1. | | | | | | 3. ON P-3 THE ISOMETRIC IT SHOWS A WASHING MACHINE | | | WITHOUT NO VENT AND IT MUST RUN A 3? DRAIN LINE PER | | | MOST MANUFACTURES SPECIFICATION UNITS. YOU MAY USE AN | | | AIR ADMITTANCE VALVE, BUT IT MUST BE A 3? LINE AS WELL | | | PER MANUFACTURE SPECIFICATION ON A AIR ADMITTANCE VALVE | | | USE PER THE 2017 FBC R 3114.2. | | | | | | 4. THE WASHING MACHINE VALVE OR BOX MUST BE ACCESSIBLE | | | WITHOUT MOVE THE UNITS SO PLEASE SHOW THE VALVES ON THE | | | SIDE OF WALLS PER THE 2017 FBC R2903.9.3. | | | | | | 5. BACKFLOW DEVICE REQUIRED PER THE CITY OF WEST PALM | | | BEACH CROSS CONNECTION PROGRAM AS THIS IS CONSIDERED A | | | DUAL DWELLING. | | | | | | 6. A SEPARATE PERMIT AND APPLICATION ARE REQUIRED FOR | | | BACKFLOW DEVICE BY A LICENSE CONTRACTOR IN A FORM OF A | | | RPZ DEVICE AND CERTIFIED BY THE UTILITIES DEPARTMENT. | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & | | | REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS | | | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL | | | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE | | | REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO | | | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED | | | COOPERATION. | | | LUIS A. CRESPO | | | PLUMBING INSPECTOR / | | | PLUMBING PLAN REVIEW | | | AVAILABLE FROM 6:30 AM 7:30 / 2:00 PM TO 5:00 PM | | | [email protected] | | | 561-701-6437 | | | |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
1 |
Status |
P |
Date |
2020-03-27 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2020-03-27 |
Time |
12:35 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2020-03-27 |
Time |
12:35 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
3 |
Status |
P |
Date |
2020-06-01 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2020-06-01 |
Time |
09:27 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2020-06-01 |
Time |
09:27 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
P |
Date |
2020-05-05 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2020-05-05 |
Time |
11:17 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2020-05-05 |
Time |
11:09 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
P |
Date |
2020-05-02 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2020-05-02 |
Time |
13:45 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2020-05-02 |
Time |
13:45 |
Sent To |
|
|
| Notes |
| 2020-05-02 13:45:57 | ROUND 1 PAGES ARE PAPER ORIGINALS | | | ROUND 2 PAGES ARE DIGITALLY SIGNED, ADDED TO SIGNATURE | | | FOLDER | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2020-05-26 |
|
|
Cont ID |
|
| Sent By |
awooten |
Date |
2020-05-26 |
Time |
|
Rev Time |
0.00 |
| Received By |
awooten |
Date |
2020-05-26 |
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2020-04-03 |
|
|
Cont ID |
|
| Sent By |
awooten |
Date |
2020-04-03 |
Time |
|
Rev Time |
|
| Received By |
awooten |
Date |
2020-04-03 |
Time |
|
Sent To |
|
|
| Notes |
| 2020-04-03 14:28:58 | ******************ZONING REVIEW | | | FAILED************************* | | | | | | PROVIDE A SURVEY FOR THE PROPERTY. | | | | | | THIS PROPERTY IS ZONED SINGLE FAMILY (SF-7) AND ONLY | | | PERMITS ONE FULL KITCHEN IN THE MAIN HOUSE. THE GUEST | | | SUITE IS PERMITTED TO HAVE A SMALL SINK AND AN UNDER | | | THE COUNTER REFRIDGERATOR, BUT THE OVEN RANGE HAS TO BE | | | REMOVED FROM THE PLANS. | | | | | | ALANA WOOTEN | | | PLANNER | | | PLANNING DIVISION | | | 561-822-1449 | | | [email protected] |
|
|