Plan Review Details - Permit 20031138
Plan Review Stops For Permit 20031138
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2020-06-01 Cont ID  
Sent By rmcphers Date 2020-06-01 Time 09:24 Rev Time 0.00
Received By rmcphers Date 2020-06-01 Time 09:24 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2020-05-05 Cont ID  
Sent By rmcphers Date 2020-05-05 Time 11:21 Rev Time 0.00
Received By rmcphers Date 2020-05-05 Time 09:48 Sent To  
Notes
2020-05-05 11:12:05GUEST HOUSE
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) ATTIC ACCESS - THE ROUGH-FRAMED OPENING SHALL BE NOT
 LESS THAN 22 INCHES BY 30 INCHES FBC R807.1
 2) FORM R405 ENERGY CALCS. AND THE DRAWINGS DO NOT
 MATCH - PLEASE CLARIFY - ATTIC SPACE ENERGY CALCS. SAY
 UNVENTED - DRAWINGS ATTIC SPACE SAYS VENTED.
 3) DON'T KNOW WHAT HAPPENED BUT, THE STRUCTURAL
 DRAWINGS ARE MISSING (FOUNDATION, EXTERIOR WALL, ROOF
 FRAMING, ROOF SHEATHING ETC.)

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-03-27 Cont ID  
Sent By rmcphers Date 2020-03-27 Time 12:34 Rev Time 0.00
Received By rmcphers Date 2020-03-27 Time 10:37 Sent To  
Notes
2020-03-27 11:59:59GUEST HOUSE
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) PLEASE SHOW THE ATTIC ACCESS TO COMPLY WITH FBC
 R807.1
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2020-05-06 Cont ID  
Sent By jpearson Date 2020-05-06 Time 15:26 Rev Time 0.00
Received By jpearson Date 2020-05-06 Time 14:29 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2020-03-30 Cont ID  
Sent By jpearson Date 2020-03-30 Time 09:20 Rev Time 0.00
Received By jpearson Date 2020-03-30 Time 08:43 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2020-06-01 Cont ID  
Sent By rmcphers Date 2020-06-01 Time 09:28 Rev Time 0.00
Received By rmcphers Date 2020-05-27 Time 13:48 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-05-27 Cont ID  
Sent By lmarchan Date 2020-05-27 Time 12:01 Rev Time 0.00
Received By lmarchan Date 2020-04-24 Time 08:45 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-04-03 Cont ID  
Sent By shill Date 2020-04-03 Time 17:23 Rev Time 0.00
Received By shill Date 2020-03-24 Time 13:37 Sent To  
Notes
2020-03-24 13:37:58R17

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2020-06-02 Cont ID  
Sent By lmarchan Date 2020-06-02 Time 13:28 Rev Time 0.00
Received By lmarchan Date 2020-06-01 Time 10:54 Sent To  
Notes
2020-06-02 07:52:29MU-2020-18375 - $3501.02 - PAID
2020-06-01 10:54:566/1/20 EMAILED IMPACT FEE OFFICE FOR REVIEW. LEM

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2020-03-27 Cont ID  
Sent By rmcphers Date 2020-03-27 Time 12:35 Rev Time 0.00
Received By rmcphers Date 2020-03-27 Time 12:35 Sent To  
Notes
2020-03-27 12:36:48PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE OFFICE. CALL
 (561) 233-5025. UPON APPROVAL, YOU MAY CHECK OUT ONE
 PLAN SET AND TAKE TO THAT OFFICE FOR REVIEW. PLEASE
 RETURNED STAMPED AND WITH A COPY OF THE RECEIPT AS
 APPLICABLE. PLEASE PROVIDE THE MUNICIPAL IMPACT FEE
 QUESTIONNAIRE FORM TO THE PBC IMPACT FEE OFFICE. THE
 FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/AD
 MINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2020-05-05 Cont ID  
Sent By medwards Date 2020-05-05 Time 11:08 Rev Time 0.00
Received By medwards Date 2020-05-05 Time 10:57 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2020-03-25 Cont ID  
Sent By medwards Date 2020-03-25 Time 13:25 Rev Time  
Received By medwards Date 2020-03-25 Time   Sent To  
Notes
2020-03-25 13:26:181ST REVIEW FBC-2017 MECHANICAL
 PERMIT- 20031138
  
 CODES IN EFFECT:
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 PLEASE PROVIDE THE MANUAL J CALCULATIONS AND SPECS FOR
 THE REQUIRED HEATING SYSTEM. SEE: FBC FS- 107.2.1: FBC
 EC- 101.5.1.1.2
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2020-05-08 Cont ID  
Sent By ccole Date 2020-05-08 Time 07:55 Rev Time 0.00
Received By ccole Date 2020-05-07 Time 16:37 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2020-03-31 Cont ID  
Sent By lcrespo Date 2020-03-31 Time 17:26 Rev Time 0.00
Received By lcrespo Date 2020-03-31 Time 07:31 Sent To  
Notes
2020-03-31 17:28:0203/31/20 1ST PLUMBING REVIEW **DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. IS THE TANKLESS ELECTRIC OR GAS AND IF IT IS GOING
 OUTSIDE ELECTRIC, THEY SHOULD BE RATED FOR OUTSIDE
 ELEMENTS WHICH MOST ARE NOT. IF YOU PLAN ON PUTTING IT
 IN AS CASE TO PROTECT IT FROM THE ELEMENTS IT NEEDS TO
 BE APPROVED BY THE MANUFACTURE AND PLEASE SUBMIT
 SPECIFICATIONS FOR UNIT AND OR CASE PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 2. ON P-3 THE ISOMETRIC ON TOILET AND SHOWER HAS NO
 VENT FOR THE P-TRAP PLEASE WYE OFF BEFORE TOILET TO
 PICK UP LABORATORY AWAY FROM THE WET VENT BATHROOM
 GROUP PER THE 2017 FBC R 3101.2.1.
  
 3. ON P-3 THE ISOMETRIC IT SHOWS A WASHING MACHINE
 WITHOUT NO VENT AND IT MUST RUN A 3? DRAIN LINE PER
 MOST MANUFACTURES SPECIFICATION UNITS. YOU MAY USE AN
 AIR ADMITTANCE VALVE, BUT IT MUST BE A 3? LINE AS WELL
 PER MANUFACTURE SPECIFICATION ON A AIR ADMITTANCE VALVE
 USE PER THE 2017 FBC R 3114.2.
  
 4. THE WASHING MACHINE VALVE OR BOX MUST BE ACCESSIBLE
 WITHOUT MOVE THE UNITS SO PLEASE SHOW THE VALVES ON THE
 SIDE OF WALLS PER THE 2017 FBC R2903.9.3.
  
 5. BACKFLOW DEVICE REQUIRED PER THE CITY OF WEST PALM
 BEACH CROSS CONNECTION PROGRAM AS THIS IS CONSIDERED A
 DUAL DWELLING.
  
 6. A SEPARATE PERMIT AND APPLICATION ARE REQUIRED FOR
 BACKFLOW DEVICE BY A LICENSE CONTRACTOR IN A FORM OF A
 RPZ DEVICE AND CERTIFIED BY THE UTILITIES DEPARTMENT.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 LUIS A. CRESPO
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 AVAILABLE FROM 6:30 AM 7:30 / 2:00 PM TO 5:00 PM
 [email protected]
 561-701-6437
  

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2020-03-27 Cont ID  
Sent By rmcphers Date 2020-03-27 Time 12:35 Rev Time 0.00
Received By rmcphers Date 2020-03-27 Time 12:35 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2020-06-01 Cont ID  
Sent By rmcphers Date 2020-06-01 Time 09:27 Rev Time 0.00
Received By rmcphers Date 2020-06-01 Time 09:27 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2020-05-05 Cont ID  
Sent By medwards Date 2020-05-05 Time 11:17 Rev Time 0.00
Received By medwards Date 2020-05-05 Time 11:09 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2020-05-02 Cont ID  
Sent By shill Date 2020-05-02 Time 13:45 Rev Time 0.00
Received By shill Date 2020-05-02 Time 13:45 Sent To  
Notes
2020-05-02 13:45:57ROUND 1 PAGES ARE PAPER ORIGINALS
 ROUND 2 PAGES ARE DIGITALLY SIGNED, ADDED TO SIGNATURE
 FOLDER
  

Review Stop Z ZONING
Rev No 2 Status P Date 2020-05-26 Cont ID  
Sent By awooten Date 2020-05-26 Time   Rev Time 0.00
Received By awooten Date 2020-05-26 Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2020-04-03 Cont ID  
Sent By awooten Date 2020-04-03 Time   Rev Time  
Received By awooten Date 2020-04-03 Time   Sent To  
Notes
2020-04-03 14:28:58******************ZONING REVIEW
 FAILED*************************
  
 PROVIDE A SURVEY FOR THE PROPERTY.
  
 THIS PROPERTY IS ZONED SINGLE FAMILY (SF-7) AND ONLY
 PERMITS ONE FULL KITCHEN IN THE MAIN HOUSE. THE GUEST
 SUITE IS PERMITTED TO HAVE A SMALL SINK AND AN UNDER
 THE COUNTER REFRIDGERATOR, BUT THE OVEN RANGE HAS TO BE
 REMOVED FROM THE PLANS.
  
 ALANA WOOTEN
 PLANNER
 PLANNING DIVISION
 561-822-1449
 [email protected]