Plan Review Details - Permit 20031125
Plan Review Stops For Permit 20031125
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2020-06-30 Cont ID  
Sent By rmcphers Date 2020-06-30 Time 11:21 Rev Time 0.00
Received By rmcphers Date 2020-06-30 Time 11:21 Sent To  
Notes
2020-06-30 11:23:54CAR CHARGERS
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) PLEASE SHOW THE ACCESSIBLE ACCESS TO THE CAR
 CHARGING STATION PER FBC ACCESSIBILITY

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status N Date 2020-05-29 Cont ID  
Sent By rmcphers Date 2020-05-29 Time 11:07 Rev Time 0.00
Received By rmcphers Date 2020-05-29 Time 11:07 Sent To  
Notes
2020-05-29 07:33:47PLEASE CHECK FOR ACCESSIBILITY.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2020-05-28 Cont ID  
Sent By jpearson Date 2020-05-28 Time 15:41 Rev Time 0.00
Received By jpearson Date 2020-05-28 Time 15:41 Sent To  
Notes
2020-05-28 15:08:05CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW
 COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
 1. CORRECTED.
 2. PROVIDE ACCURATE LOAD CALCULATION FOR SERVICE,
 INCLUDE EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF
 SERVICE IS ADEQUATE. NEC 215.2, 220, 408.30 (A LOAD
 CALCULATION HAS NOT BEEN PROVIDED FOR THE 1200 AMP
 SERVICE. PROVIDE AS PREVIOULY REQUESTED.)
 3. CORRRECTED.
 4. CORRECTED.
 5. PROVIDE DETAILS ON VENTILATION IF REQUIRED. NEC
 625.52 (NO RESPONSE RECEIVED.)
  
 NEW COMMENT:
  
 6. PROVIDE DETAILS OF COMPLIANCE WITH ACCESSIBILITY
 CODE. FBC ACCESSIBILITY 101.1.2; NEC INFORMATIVE ANNEX
 J
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, PROVIDE A RESPONSE LETTER ADDRESSING EACH
 ITEM ALONG WITH THE CITY RESUBMITTAL FORM.
 ADDITIONALLY, INSERT CORRECTED PAGES INTO THE ORIGINAL
 SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS.
 ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD
 REMAIN IN PACKAGE AND BE MARKED OLD SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-03-24 Cont ID  
Sent By jpearson Date 2020-03-24 Time 14:33 Rev Time 0.00
Received By jpearson Date 2020-03-24 Time 14:33 Sent To  
Notes
2020-03-24 13:37:32CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE RISER DIAGRAM OF EXISTING SERVICE SHOWING
 WHERE THIS NEW PANEL IS FED FROM. NEC 215.5; WPB FBC
 107.2.1
 2. PROVIDE ACCURATE LOAD CALCULATION FOR SERVICE,
 INCLUDE EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF
 SERVICE IS ADEQUATE. NEC 215.2, 220, 408.30
 3. PROVIDE WIRE AND CONDUIT SIZES FOR FEED TO NEW
 PANEL. WPB FBC 107.2.1; NEC 215.2, 240.4, 310.15
 4. INDICATE ON SPECIFICATIONS WHICH MODEL WILL BE
 INSTALLED. WPB FBC 107.2.1
 5. PROVIDE DETAILS ON VENTILATION IF REQUIRED. NEC
 625.52
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, PROVIDE A RESPONSE LETTER ADDRESSING EACH
 ITEM ALONG WITH THE CITY RESUBMITTAL FORM.
 ADDITIONALLY, INSERT CORRECTED PAGES INTO THE ORIGINAL
 SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS.
 ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD
 REMAIN IN PACKAGE AND BE MARKED OLD SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-05-29 Cont ID  
Sent By rmcphers Date 2020-05-29 Time 11:09 Rev Time 0.00
Received By rmcphers Date 2020-05-18 Time 14:25 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2020-03-24 Time   Rev Time 0.00
Received By lmarchan Date 2020-03-23 Time 08:00 Sent To  
Notes
2020-03-24 08:01:03ROUTED TO ELECTRICAL INBOX


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved