| 2020-04-23 10:45:23 | FIELD INSPECTOR WILL VERIFY DUCT SIZES AND LOCATION OF |
| | RETURN AIR DUCT ON LOCATION. |
| 2020-04-15 08:13:49 | 2RD REVIEW FBC-2017 MECHANICAL |
| | PERMIT-20031121 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| | EDITION 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) PLEASE REVIEW THE SUBMITTED DRAWING AND MAKE |
| | NECESSARY CHANGES PER YOUR SUBMITTED HVAC LOAD |
| | CALCULATIONS. PAGE 5 OF THE CALCULATION REPORT SPECS |
| | OUT FOR SYSTEM 1- MAIN DUCT IS 12?X16? THE DRAWING |
| | SHOWS 16?X5.5?. SYSTEM 2- THE CALCULATION REPORT SPECS. |
| | OUT AN 8?X11? MAIN TRUNK. THE SUBMITTED DRAWING SHOWS A |
| | 24?X5.5? DROPPING DOWN TO A 18?X5.5?. SYSTEM 3- THE |
| | CALCULATIONS SPEC OUT A 13?X18? MAIN DUCT. THE |
| | SUBMITTED DRAWING SHOWS A 11?X5.5? WITH A 9? METAL MAIN |
| | TRUNK. THE CALCULATIONS SPEC (2) 6? DUCT FOR BEDROOM 3, |
| | THE DRAWING SHOWS(1) 11?X5.5?. LABEL DUCT SIZE RUNNING |
| | TO THE LAUNDRY ROOM. THE CALCULATIONS SPEC (2) 3? FOR |
| | BATHROOM 3-4 CLOSET AREA, THERE IS NOT A DUCT IN THE |
| | CLOSET AREA. |
| | |
| | 2) THE RETURN FOR SYSTEM 3 MUST MEET FBC RES M1602.2 |
| | FOR RETURNS IN A KITCHEN. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD |
| | SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER |
| | SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN |
| | THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS |
| | PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS |
| | PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR |
| | UPDATED. |
| | |
| | |