| 2020-04-23 14:52:42 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | FAC = FLORIDA ADMINISTRATIVE CODE |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. PERMIT APPLICATION STATES THERE ARE 8 LOCATIONS TO |
| | BE INSTALLED, BUT PLAN ONLY SHOWS 3 LOCATIONS ON |
| | ELECTRICAL SHEET. PROVIDE FLOOR PLAN SHOWING ALL |
| | LOCATIONS TO BE INSTALLED. ADDITIONALLY, PROVIDE |
| | CIRCUITRY INFORMATION. WILL THESE ALL BE ON ONE |
| | CIRCUIT? HOW WILL THE INSTALLATION BE COMPLETED ON |
| | LOCAL CIRCUITS WHILE CONFIRMING THEY ARE NOT |
| | OVERLOADED? PROVIDE CLARIFICATION. WPB FBC 107.2.1; NEC |
| | 210.20 |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, PROVIDE A RESPONSE LETTER ADDRESSING EACH |
| | ITEM ALONG WITH THE CITY RESUBMITTAL FORM. |
| | ADDITIONALLY, INSERT CORRECTED PAGES INTO THE ORIGINAL |
| | SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS. |
| | ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD |
| | REMAIN IN PACKAGE AND BE MARKED OLD SHEETS. |
| | |