Plan Review Details - Permit 20031112
Plan Review Stops For Permit 20031112
Review Stop G GAS REVIEW
Rev No 3 Status P Date 2020-06-10 Cont ID  
Sent By ccole Date 2020-06-10 Time 15:21 Rev Time 0.00
Received By ccole Date 2020-06-10 Time 14:45 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2020-04-17 Cont ID  
Sent By ccole Date 2020-04-17 Time 12:33 Rev Time 0.00
Received By ccole Date 2020-04-17 Time 12:33 Sent To  
Notes
2020-04-17 12:38:38 
 1ST REVIEW FBC-2017 PLUMBING/FUEL GAS
 PERMIT #20031112
 4/17/20
  
 CODES IN EFFECT:
  
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE UNDERGROUND PE PIPING RUNS ON THE SITE PLAN AND
 ISOMETRIC DRAWINGS DO NOT MATCH. THE ISO SHOWS A ?? PE
 BRANCH LINE TO THE POOL HEATER TEEING OFF FROM THE ??
 MAIN AT 40? UPSTREAM OF THE TANK. THE SITE PLAN SHOWS A
 STRAIGHT 100? 1/2? PE RUN TO THE POOL HEATER. REVISE
 THE DRAWINGS SO THEY MATCH- SECTION 107.2.1 WPB.
  
 2) IT APPEARS THAT UNDER THE POOL PERMIT #19090743, THE
 EXISTING GAS LINE WAS POSSIBLY REMOVED OR RELOCATED
 DURING POOL CONSTRUCTION. ON THE SITE PLAN OR ISOMETRIC
 DRAWING, INDICATE THE BURIAL DEPTH OF THE PIPE AND TYPE
 OF SLEEVING USED UNDER THE PAVER DECK- SECTION G2415.12
 FBC RES
  
 3) MODIFY THE ISOMETRIC DRAWING TO INDICATE:
 A) THE DELIVERY PRESSURES AT THE 2ND STAGE REGULATORS-
 G2413.2 & G2413.4.3
 B) TOTAL BTUH LOAD ON THE SYSTEM- G2413.3.
 C) THE TYPE AND SIZE OF PIPING, AND THE LENGTHS OF THE
 PIPING RUNS FROM THE REGULATORS TO THE HEATER AND
 GRILL- G2413.3 & G2413.4
 D) LOCATIONS OF REQUIRED PIPE UNIONS AND THE 2ND STAGE
 REGULATOR- G2421.2
 E) LOCATIONS OF SHUTOFF VALVES AT THE HEATER AND GRILL-
 G2420.5.
 F) INDICATE WHICH PIPE SIZING TABLES WERE USED FOR THE
 PE AND THE 2ND STAGE PIPING- TABLES G2413.4.1- G2413.2.
  
 4) PLEASE LIST THE MAKE AND MODEL NUMBER OF THE POOL
 HEATER ON THE ISOMETRIC DRAWING- SECTION 107.2.1 WPB.
  
 5) THE COST OF THE POOL HEATER SHALL BE INCLUDED IN THE
 TOTAL VALUE OF THE PERMIT. PERMIT VALUE INCLUDES THE
 TOTAL COST OF LABOR, MATERIALS, EQUIPMENT AND
 APPLIANCES, SITE WORK, AND DESIGN FEES- SECTION 109.3
 WPB
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
  
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2020-03-24 Cont ID  
Sent By shill Date 2020-03-24 Time 15:35 Rev Time 0.00
Received By shill Date 2020-03-24 Time 11:31 Sent To  
Notes
2020-03-24 15:36:091. FBC 107.2.1 PROVIDE COMPLETE INSTALLATION PLAN
 DRAWING FOR CONNECTION OF GAS TO POOL WATER HEATER,
 INCLUDING GAS RISER DIAGRAM WITH LEGIBLE PRINTING,
 INCLUDING ANY OTHER EXISTING APPLIANCES AND BTUH
 VALUES, PIPE SIZING CRITERIA, WHERE EXISTING IS
 LOCATED, EXISTING PIPING ON PLAN, HOW IT IS TO BE RE
 ROUTED, PIPING MATERIALS AND VALVING. IT APPEARS A BBQ
 IS BEING REMOVED?
 2. FBC 107.2.1 POOL HEATER BROCHURE IS INADEQUATE IN
 THAT THE SIZE, MODEL OR ANY OTHER INFORMATION IS GIVEN.
 3. FBC FUEL GAS SECTION 404. PLEASE NOT THAT PIPING IN
 CONCEALED LOCATIONS SHALL NOT HAVE UNIONS, TUBING
 FITTINGS, RIGHT AND LEFT COUPLINGS, BUSHINGS,
 COMPRESSION COUPLINGS AND SWING JOINTS MADE BY
 COMBINATIONS OF FITTINGS UNLESS THE FITTINGS ARE LISTED
 FOR USE IN CONCEALED LOCATIONS.
 4. FBC 107.2.1 PROVIDE DETAILS OF POOL HEATER
 INSTALLATION INCLUDING APPROVED HURRICANE TIEDOWNS FOR
 THE HEATER.
  
 REVIEWED REMOTELY BY JAMES BAKER, PE
 PX3997, PE77268
 561-805-6724
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2020-06-10 Time   Rev Time 0.00
Received By lmarchan Date 2020-06-08 Time 09:35 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2020-04-17 Time   Rev Time 0.00
Received By lmarchan Date 2020-04-15 Time 14:27 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-03-24 Cont ID  
Sent By shill Date 2020-03-24 Time 15:36 Rev Time 0.00
Received By shill Date 2020-03-23 Time 14:32 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status N Date 2020-06-10 Cont ID  
Sent By ccole Date 2020-06-10 Time 15:21 Rev Time 0.00
Received By ccole Date 2020-06-10 Time 14:45 Sent To  
Notes
2020-06-10 15:22:00POOL HEATER PLUMBING UNDER A SEPARATE PERMIT

Review Stop P PLUMBING
Rev No 2 Status N Date 2020-04-17 Cont ID  
Sent By ccole Date 2020-04-17 Time 12:38 Rev Time 0.00
Received By ccole Date 2020-04-17 Time 12:38 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2020-03-24 Cont ID  
Sent By jbaker Date 2020-03-24 Time 15:36 Rev Time 0.00
Received By shill Date 2020-03-24 Time 11:31 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status N Date 2020-03-24 Cont ID  
Sent By shill Date 2020-03-24 Time 16:06 Rev Time 0.00
Received By shill Date 2020-03-24 Time 16:06 Sent To  
Notes
***NONE***