| Plan Review Stops For Permit 20031101 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2020-05-15 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2020-05-15 |
Time |
14:46 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2020-05-15 |
Time |
12:22 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2020-03-31 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2020-03-31 |
Time |
15:28 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2020-03-30 |
Time |
14:16 |
Sent To |
|
|
| Notes |
| 2020-03-31 15:34:12 | PLAN REVIEW - BUILDING | | | | | | CODES IN EFFECT: | | | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | | | | CHRISTOPHER S. THROOP, C.B.O. | | | PLANS EXAMINER ? BUILDING - PX3169 | | | PLANS EXAMINER ? 1&2 FAMILY - SFP306 | | | CONSTRUCTION SERVICES DIVISION | | | TEL: 561-805-6726 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | 1ST REVIEW | | | | | | RESULTS: DENIED | | | | | | YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED | | | BELOW. | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | | | 1. DIGITAL SIGNATURE IS NOT ISSUED IN A MANNER WHICH IS | | | ACCEPTABLE TO EITHER FBPE OR FLORIDA BOARD OF | | | PROFESSIONAL ENGINEERS. THIS TYPE OF SELF CERTIFICATION | | | IS NOT INTENDED TO BE USED FOR PROFESSIONAL PURPOSES. | | | THIRD PARTY CERTIFICATION IS REQUIRED. | | | | | | 1A. DIGITAL SIGNATURES/SEALS ARE NOT IN ACCORDANCE WITH | | | FS 471, FS 481 AS NOTED. NEW SHEETS SUBMITTED IN THE | | | NEXT REVIEW CYCLE REQUIRE REVIEW. | | | | | | 1B. UPLOAD VIA THE PROJECTDOX PORTAL WITH DIGITAL | | | SIGNATURES OF DESIGN PROFESSIONALS AS APPLICABLE; USE | | | THE REQUIRED NAMING CONVENTION FOR EACH DOCUMENT. | | | | | | 2. PRODUCT APPROVALS SHALL BE REVIEWED AND APPROVED IN | | | WRITING BY DESIGNER. (PROFESSIONAL SEAL NOT REQUIRED) | | | | | | FBC 107.3.4 ? PROVIDE PRODUCT APPROVALS FOR THOSE | | | PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED | | | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. | | | SPECIFICALLY, PROVIDE WINDOW AND DOOR SUBMITTALS. | | | | | | | | | | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2020-05-15 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2020-05-15 |
Time |
14:50 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2020-05-15 |
Time |
12:21 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2020-03-30 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2020-03-30 |
Time |
12:05 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2020-03-30 |
Time |
10:00 |
Sent To |
|
|
| Notes |
| 2020-03-30 10:36:20 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | FLORIDA BUILDING CODE 2017 6TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED | | | NFPA 70 2014 EDITION | | | | | | JAKE LEAHY BN, BU, PX | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | | | | 1) PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH | | | PANEL INCLUDING INFORMATION FROM THE POWER COMPANY | | | STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR | | | THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE | | | SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE. | | | NEC 110.9, 110.10 | | | | | | 2) PROVIDE NOTE THAT THE SERVICE EQUIPMENT SHALL BE | | | MARKED WITH THE MAXIMUM AVAILABLE SHORT CIRCUIT CURRENT | | | AVAILABLE PER NEC 110.24. | | | | | | 3) PROVIDE COMPLIANCE: "A MINIMUM OF 75 PERCENT OF THE | | | LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL | | | BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF | | | THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL | | | CONTAIN ONLY HIGH EFFICACY LAMPS". A NOTE WILL SUFFICE. | | | FBC CE R404.1 | | | | | | 4) ALL 120-VOLT, SINGLE PHASE, 15 AND 20 AMPERE BRANCH | | | CIRCUITS SUPPLYING OUTLETS IN DWELLING UNIT KITCHENS, | | | LAUNDRY ROOMS, FAMILY ROOMS, DINING ROOMS, LIVING | | | ROOMS, PARLORS, LIBRARIES, DENS, BEDROOMS, SUNROOMS, | | | RECREATION ROOMS, CLOSETS, HALLWAYS, OR SIMILAR AREAS | | | OR ROOMS, SHALL HAVE AFCI PROTECTION. NEC 210.12; FBC | | | RE3902.16 LAUNDRY AREA | | | | | | 5) E3902.9 LAUNDRY AREAS. 125-VOLT, SINGLE-PHASE, 15- | | | AND 20-AMPERE RECEPTACLES INSTALLED IN LAUNDRY AREAS | | | SHALL HAVE GROUND-FAULT CIRCUIT INTERRUPTER PROTECTION | | | FOR PERSONNEL. [210.8(A)(9)] | | | | | | 6) E3902.10 KITCHEN DISHWASHER BRANCH CIRCUIT. | | | GROUND-FAULT CIRCUIT-INTERRUPTER PROTECTION SHALL BE | | | PROVIDED FOR OUTLETS THAT SUPPLY DISHWASHERS IN | | | DWELLING UNIT LOCATIONS. [210.8(D)] | | | | | | 7) SHOW LOCATION OF SERVICE AND PANELS NO LOCATION | | | SHOWN. E3601.6.2 SERVICE DISCONNECT LOCATION. | | | | | | 8) FOR A ONE FAMILY DWELLING AND EACH UNIT OF A | | | TWO-FAMILY DWELLING THAT IS AT GRADE LEVEL, AT LEAST | | | ONE RECEPTACLE OUTLET READILY ACCESSIBLE FROM GRADE AND | | | NOT MORE THAN 2.0 M (6.5 FT) ABOVE GRADE LEVEL SHALL BE | | | INSTALLED AT THE FRONT AND BACK OF THE DWELLING. NEC | | | 210.52(E)(1) FBC RE3901.7 | | | | | | 9) STORAGE OUTLET TO BE GFCI PROTECTED | | | | | | 10) NO LOW VOLTAGE WIRING SHOWN ON PLANS THIS IS NOT | | | REQUIREMENT BUT MAY DELAY JOB FOR A REVISION IN FIELD. | | | | | | 11) PANEL SCHEDULE DOE NOT INCLUDE THE WATER HEATER |
|
|
| Review Stop |
E-LOWVOLT |
ELECTRICAL LOW VOLTAGE |
| Rev No |
1 |
Status |
N |
Date |
2020-05-15 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2020-05-15 |
Time |
13:55 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2020-05-15 |
Time |
13:55 |
Sent To |
|
|
| Notes |
| 2020-05-15 14:41:29 | NO LOW VOLTAGE SHOWN ON PLAN. CT |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2020-05-21 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2020-05-21 |
Time |
09:41 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2020-05-20 |
Time |
18:12 |
Sent To |
I |
|
| Notes |
| 2020-05-20 18:13:01 | ROUTED TO J.GOMEZ FOR SIGNATURE REVIEW |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2020-05-20 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2020-05-20 |
Time |
09:01 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2020-05-04 |
Time |
14:32 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2020-04-07 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2020-04-07 |
Time |
09:09 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2020-03-23 |
Time |
16:29 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
P |
Date |
2020-04-22 |
|
|
Cont ID |
|
| Sent By |
lmarchan |
Date |
2020-04-22 |
Time |
16:57 |
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2020-04-07 |
Time |
16:48 |
Sent To |
|
|
| Notes |
| 2020-04-22 14:14:41 | MU 2020-012051 - $9,785.26 - PAID | | 2020-04-07 16:48:18 | 4/7/20 EMAILED IMPACT FOR REVIEW. LEM |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2020-05-05 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2020-05-05 |
Time |
12:07 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2020-05-05 |
Time |
11:21 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2020-03-31 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2020-03-30 |
Time |
09:04 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2020-03-31 |
Time |
15:14 |
Sent To |
|
|
| Notes |
| 2020-03-31 15:19:32 | PLAN IS CODE COMPLIANT BUT SIGNATURE AND SEAL DO NOT | | | COMPLY WITH STANDARDS | | | . | | | DIGITAL REVIEW | | | | | | DIGITAL SIGNATURE IS NOT ISSUED IN A MANNER WHICH IS | | | ACCEPTABLE TO EITHER FBPE OR FLORIDA BOARD OF | | | PROFESSIONAL ENGINEERS. THIS TYPE OF SELF CERTIFICATION | | | IS NOT INTENDED TO BE USED FOR PROFESSIONAL PURPOSES. | | | THIRD PARTY CERTIFICATION IS REQUIRED. | | | | | | | | | 1. DIGITAL SIGNATURES/SEALS ARE NOT IN ACCORDANCE WITH | | | FS 471, FS 481 AS NOTED. NEW SHEETS SUBMITTED IN THE | | | NEXT REVIEW CYCLE REQUIRE REVIEW. | | | | | | 2. UPLOAD VIA THE PROJECTDOX PORTAL WITH DIGITAL | | | SIGNATURES OF DESIGN PROFESSIONALS AS APPLICABLE; USE | | | THE REQUIRED NAMING CONVENTION FOR EACH DOCUMENT. | | | | | | 3. FLORIDA PROFESSIONAL ENGINEERS MAY NOT SELF CERTIFY | | | DIGITAL SIGATURES AND SEALS PER FS 668.003. | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2020-04-07 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2020-04-07 |
Time |
07:23 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2020-04-07 |
Time |
07:21 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2020-03-27 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2020-03-27 |
Time |
09:31 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2020-03-27 |
Time |
09:23 |
Sent To |
|
|
| Notes |
| 2020-03-27 09:32:32 | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | FBC M = FBC MECHANICAL | | | FBC P = FBC PLUMBING | | | | | | 1. FBC 107.2.1 PROVIDE PLUMBING DRAWINGS FOR REVIEW. I | | | SEE NONE UPLOADED IN THE DRAWINGS. | | | | | | REVIEWED REMOTELY BY JAMES BAKER, PE | | | PX3997, PE77268 | | | 561-805-6724 | | | [email protected] | | | | | | |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
1 |
Status |
N |
Date |
2020-04-07 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2020-03-31 |
Time |
15:24 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2020-03-30 |
Time |
14:17 |
Sent To |
|
|
| Notes |
| 2020-03-31 15:28:11 | PLAN REVIEW - ROOFING | | | | | | PROVISO: | | | | | | DEFERRALS FOR ROOFING PRODUCT APPROVALS. NOTE PLACED ON | | | PLAN SHEET 1. |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
3 |
Status |
P |
Date |
2020-05-21 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2020-05-21 |
Time |
09:40 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2020-05-21 |
Time |
09:40 |
Sent To |
|
|
| Notes |
| 2020-05-21 09:41:47 | RECEIVED SIGNED AND SEALED PLANS ARE THE SAME THAT WERE | | | APPROVED BY THE PLAN REVIEWERS. JG. |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
F |
Date |
2020-05-15 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2020-05-15 |
Time |
14:50 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2020-05-15 |
Time |
12:22 |
Sent To |
|
|
| Notes |
| 2020-05-15 14:55:29 | PLAN REVIEW - DIGITAL SIGNATURE AND SEAL | | | | | | CHRISTOPHER S. THROOP, C.B.O. | | | PLANS EXAMINER BUILDING - PX3169 | | | PLANS EXAMINER 1&2 FAMILY - SFP306 | | | CONSTRUCTION SERVICES DIVISION | | | TEL: 561-805-6726 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | 1ST REVIEW | | | | | | RESULTS: DENIED | | | | | | YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED | | | BELOW. | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | | | DIGITAL SIGNATURES AND SEALS | | | | | | DESIGN PROFESSIONALS | | | | | | 1. DIGITAL SIGNATURES/SEALS ARE NOT IN ACCORDANCE WITH | | | FS 471, FS 481 AS NOTED. NEW SHEETS SUBMITTED IN THE | | | NEXT REVIEW CYCLE REQUIRE REVIEW. | | | | | | 2. UPLOAD VIA THE PROJECTDOX PORTAL WITH DIGITAL | | | SIGNATURES OF DESIGN PROFESSIONALS AS APPLICABLE; USE | | | THE REQUIRED NAMING CONVENTION FOR EACH DOCUMENT. | | | | | | 3. FLORIDA PROFESSIONAL ENGINEERS MAY NOT SELF CERTIFY | | | DIGITAL SIGATURES AND SEALS PER FS 668.003. | | | | | | | | | NON-DESIGN PROFESSIONALS- ELECTRICAL PLAN - REQUIRES | | | SIGNATURE OF CONTRACTOR | | | | | | 1. THE CONTRACTOR OR DESIGNER OF RECORD SHALL PROVIDE A | | | TITLE BLOCK AND SIGNATURE ON PLAN SHEETS UNDER THEIR | | | AUTHORITY ? 2017 WPB AMENDMENTS TO THE FLORIDA BUILDING | | | CODE, CHAPTER 1, SECTION 107.2.1. | | | | | | OPTIONS: | | | | | | OPTION -1: | | | RE-SUBMIT PLANS WITH VALID SIGNATURE AND SEAL. | | | | | | OPTION - 2: | | | YOU MAY ELECT TO PROVIDE A HARD COPY OF PLANS WITH WET | | | SEAL AND SIGNATURE OF DESIGN PROFESSIONAL PRIOR TO | | | PERMIT. A DROP BOX HAS BEEN INSTALLED OUTSIDE CITY HALL | | | FOR THIS PURPOSE. CONTACT THE OFFICE OF DEVELOPMENT | | | SERVICES @ 561-805-8700 OR [email protected] TO STATE YOUR | | | INTENTIONS. CITY STAFF WILL REVIEW YOUR DOCUMENTS AND | | | IF APPROVED YOU WILL RECIEVE AN E-MAIL INSTRUCTING YOU | | | TO DOWNLOAD AND PRINT YOUR PERMIT AND PLANS. | | | | | | OPTION - 3: | | | YOU MAY MAIL IN A HARD COPY OF PLANS WITH WET SEAL AND | | | SIGNATURE. A FINAL INSPECTION HOLD WILL BE PLACED ON | | | YOUR PERMIT UNTIL DESIGN PROFESSIONALS SIGNATURE AND | | | SEAL ARE VERIFIED. | | | | | | PLEASE ADVISE | | | | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
F |
Date |
2020-03-30 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2020-03-30 |
Time |
09:06 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2020-03-30 |
Time |
09:06 |
Sent To |
|
|
| Notes |
| 2020-03-30 09:12:58 | PLEASE PROVIDE DIGITAL SEAL AND SIGNATURE ON THE | | | DESIGN. FBC FS 107.3.4 | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2020-05-19 |
|
|
Cont ID |
|
| Sent By |
awooten |
Date |
2020-05-19 |
Time |
|
Rev Time |
0.00 |
| Received By |
awooten |
Date |
2020-05-19 |
Time |
|
Sent To |
|
|
| Notes |
| 2020-05-19 10:57:11 | **************ZONING PROVISO************ | | | | | | PRIOR TO THE ISSUANCE OF A CERTIFICATE OF OCCUPANCY, | | | THE FOLLOWING CONDITIONS SHALL BE ADDRESSED: | | | | | | 1. A LANDSCAPE PERMIT, WHICH INCLUDES A LANDSCAPE PLAN, | | | SHALL BE SUBMITTED TO THE BUILDING DIVISION FOR REVIEW. | | | | | | 2. THE LANDSCAPE MATERIAL SHOWN ON THE APPROVED | | | LANDSCAPE PERMIT SHALL BE INSTALLED AND PASS A FINAL | | | INSPECTION. | | | | | | ALANA WOOTEN | | | PLANNER | | | PLANNING DIVISION | | | 561-822-1449 | | | [email protected] |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2020-04-06 |
|
|
Cont ID |
|
| Sent By |
awooten |
Date |
2020-04-06 |
Time |
|
Rev Time |
|
| Received By |
awooten |
Date |
2020-04-06 |
Time |
|
Sent To |
|
|
| Notes |
| 2020-04-06 14:18:18 | ************************ZONING REVIEW | | | FAILED************************ | | | | | | PLEASE SUBMIT A SEPARATE LANDSCAPE AND IRRIGATION | | | PERMIT. SHOWING THE FOLLOWING: | | | RESIDENTIAL LANDSCAPE REQUIREMENTS CITY OF WEST PALM | | | BEACH | | | SECTION 94-442(C)(2)A. SINGLE FAMILY DWELLING UNITS | | | | | | O GROSS LOT SQUARE FOOTAGE MINUS | | | O BUILDING FOOTPRINT SQUARE FOOTAGE EQUALS | | | O OPEN SPACE SQUARE FOOTAGE (ALL NON-BUILDING AREA) | | | O ONE TREE REQUIRED FOR EACH 1,000 SQ FT OF OPEN SPACE | | | OR PORTION THEREOF | | | O ONE SHRUB REQUIRED FOR EACH 500 SQ FT OF OPEN SPACE | | | OR PORTION THEREOF | | | | | | SEPARATE PERMIT REQUIRED FOR: | | | | | | FENCE/WALL, AWNINGS, SIGNS, PARKING LOT, GENERATOR, | | | MECHANICAL/AC/POOL EQUIPMENT, DUMPSTER ENCLOSURE, | | | IRRIGATION, LANDSCAPE, AND DRIVEWAYS | | | | | | ADDITIONAL PERMITS REQUIRED: | | | | | | ELECTRI, A/C, PLUMBING, FENCES, FIRE SPRINKLER SYSTEM, | | | PAVING, DRAINAGE, POOLS, AWNINGS, SIGNS, SIDEWALKS, | | | CURBS, APPROACHES, ROOFING | | | | | | ALANA WOOTEN | | | PLANNER | | | PLANNING DIVISION | | | 561-822-1449 | | | [email protected] | | | | | | | | | |
|
|