Plan Review Details - Permit 20031096
Plan Review Stops For Permit 20031096
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2020-09-17 Cont ID  
Sent By cthroop Date 2020-09-17 Time 10:56 Rev Time 0.00
Received By cthroop Date 2020-09-17 Time 09:38 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2020-08-17 Cont ID  
Sent By jgomez Date 2020-08-17 Time 10:12 Rev Time 0.00
Received By rmcphers Date 2020-08-17 Time 10:02 Sent To  
Notes
2020-08-17 10:12:49REVISION - GATE AND SHUTTER
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) ROLLUP SHUTTER - CANNOT BE USED AS A DOOR - UNLESS
 IT CAN BE UNLATCHED OR UNLOCKED FROM THE INSIDE (EGRESS
 SIDE) FBC 1010.1.9
 2) PLEASE SHOW THE GATE DOOR LOCKING HARDWARE TO COMPLY
 WITH FBC 1010.1.9
 3) THE SHOP DRAWINGS FOR THE GATE DOOR DO NOT SHOW IN
 "ADOBE READER" AS ELECTRONICALLY/DIGITALLY SIGNED -
 PLEASE TRY UPLOADING (F1 AND F2) A SECOND TIME WITHOUT
 THE APPROVAL STAMPS. (ELECTRONICALLY SIGNED DRAWINGS
 AND DOCUMENTS CANNOT BE PRINTED OUT THEY WILL LOSE
 THEIR ELECTRONIC SIGNATURE)

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2020-03-26 Cont ID  
Sent By jgomez Date 2020-03-26 Time 08:49 Rev Time 0.00
Received By jgomez Date 2020-03-26 Time 08:33 Sent To  
Notes
2020-03-26 08:34:08 
  
 REVISION BUILDING REVIEW COMMENTS.
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 1- THE REVISION IS TO CHANGE DOOR TO ROLL DOWN
 HURRICANE SHUTTERS. THIS WAS DISCUSSED WITH ROBERT
 BROWN AND AND DYLAN BATTLES. SHUTTERS ARE OK BUT EGRESS
 NEEDS TO BE CLARIFIED. PROVIDE SPECIFICATIONS SHOWING
 HOW THE SHUTTERS ARE OPERABLE FROM THE INSIDE TO ALLOW
 EGRESS IN CASE THE SHUTTERS ARE CLOSED DOWN. SEC.
 1001.1 FBC-BUILDING. SEC. 107.2.1 CITY AMENDMENTS.
  
 2- THIS IS A REVISION TO THE ALREADY APPROVED DOOR
 PRODUCT APPROVAL NOA 18-0301.08.
 PRODUCT APPROVAL SUBMITTED NOW IS FOR ROLL UP HURRICANE
 SHUTTERS NOT FOR A DOOR. NEED TO PROVIDE COMPLETE
 HURRICANE SHUTTERS INSTALLATION SCHEDULE AS REQUIRED BY
 CITY POLICY FOR ALL HURRICANE SHUTTERS INSTALLATIONS.
 SEE HURRICANE SHUTTERS INSTALLATION SCHEDULE SAMPLE OR
 PROVIDE COMPLETE INFORMATION IN A DIFFERENT FORMAT THAT
 WILL SPECIFY ALL THE REQUIRED INFORMATION.
 SEC. 107.2.1 CITY AMENDMENTS.
  
 3- CORRECTED MASTER NUMBER REFERENCED IN THE SUBMITTAL.
 THE MASTER FOR THE GENERATOR ENCLOSURE IS 19100813 NOT
 19100815.
 THIS IS A REVISION TO THE ALREADY APPROVED DOOR PRODUCT
 APPROVAL NOT A SUBMITTAL. REVISION FEES APPLY. OWE
 $175.25 FOR REVISION FEES.
  
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
 I SPOKE TO ROBERT ABOUT THIS ONE AND HE IS OK WITH THE
 ROLLUP SHUTTER BUT IT NEEDS TO BE ABLE TO OPEN FROM THE
 INSIDE IF SOMEONE CLOSES IT.
 JUST COMMENT ABOUT THAT ASPECT OF IT AND HOW THE
 HARDWARE WORKS.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-03-27 Cont ID  
Sent By jgomez Date 2020-03-24 Time 17:18 Rev Time 0.00
Received By jgomez Date 2020-03-24 Time 17:15 Sent To  
Notes
2020-03-24 17:18:52 
 *****REVIEW IN PROGRESS. COORDINATING WITH DYLAN
 BATTLES CONCERN ABOUT EGRESS...
  
 REVISION BUILDING REVIEW COMMENTS.
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 1- THIS IS A REVISION TO THE ALREADY APPROVED DOOR
 PRODUCT APPROVAL NOA 18-0301.08.
 PRODUCT APPROVAL SUBMITTED NOW IS FOR ROLL UP HURRICANE
 SHUTTERS NOT FOR A DOOR. NEED TO PROVIDE COMPLETE
 HURRICANE SHUTTERS INSTALLATION SCHEDULE AS REQUIRED BY
 CITY POLICY FOR ALL HURRICANE SHUTTERS INSTALLATIONS.
 SEE HURRICANE SHUTTERS INSTALLATION SCHEDULE SAMPLE OR
 PROVIDE COMPLETE INFORMATION IN A DIFFERENT FORMAT THAT
 WILL SPECIFY ALL THE REQUIRED INFORMATION.
 SEC. 107.2.1 CITY AMENDMENTS.
  
 2- CORRECTED MASTER NUMBER REFERENCED IN THE SUBMITTAL.
 THE MASTER FOR THE GENERATOR ENCLOSURE IS 19100813 NOT
 19100815.
 THIS IS A REVISION TO THE ALREADY APPROVED DOOR PRODUCT
 APPROVAL NOT A SUBMITTAL. REVISION FEES APPLY. OWE
 $175.25 FOR REVISION FEES.
  
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2020-09-02 Cont ID  
Sent By pleduc Date 2020-09-02 Time   Rev Time 0.00
Received By pleduc Date 2020-09-02 Time 13:56 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2020-07-14 Cont ID  
Sent By sathomas Date 2020-07-14 Time 00:00 Rev Time 0.00
Received By sathomas Date 2020-07-14 Time 00:00 Sent To B
Notes
2020-07-14 14:37:45PREVIOUS FIRE COMMENTS NOT ADDRESSED AS FOLLOWS:
  
 1. WHAT IS THE LOCATION OF THE HURRICANE IMPACT ROLL UP
 DOOR? IT IS NOT REFLECTED ON THE PLANS.
 2. SHOULD SOMEONE BECOME "LOCKED" INSIDE THE ENCLOSURE,
 WHAT MEANS OF EGRESS WILL BE PROVIDED?
  
 S. THOMAS
 561-804-4728

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2020-03-25 Cont ID  
Sent By sathomas Date 2020-03-25 Time 00:00 Rev Time 0.00
Received By sathomas Date 2020-03-25 Time 00:00 Sent To I
Notes
2020-03-25 13:50:231. WHAT IS THE LOCATION OF THE HURRICANE IMPACT ROLL UP
 DOOR? IT IS NOT REFLECTED ON THE PLANS.
 2. SHOULD SOMEONE BECOME "LOCKED" INSIDE THE ENCLOSURE,
 WHAT MEANS OF EGRESS WILL BE PROVIDED?
  
 S. THOMAS
 561-804-4728

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2020-09-17 Cont ID  
Sent By cthroop Date 2020-09-17 Time 10:56 Rev Time 0.00
Received By cthroop Date 2020-08-31 Time 10:54 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-08-17 Cont ID  
Sent By rmcphers Date 2020-08-17 Time 10:14 Rev Time 0.00
Received By rmcphers Date 2020-07-10 Time 09:01 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-03-26 Cont ID  
Sent By jgomez Date 2020-03-26 Time 08:49 Rev Time 0.00
Received By jgomez Date 2020-03-23 Time 17:17 Sent To I
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2020-09-17 Cont ID  
Sent By cthroop Date 2020-09-17 Time 10:38 Rev Time 0.00
Received By cthroop Date 2020-09-17 Time 09:38 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2020-08-17 Cont ID  
Sent By rmcphers Date 2020-08-17 Time 10:13 Rev Time 0.00
Received By rmcphers Date 2020-08-17 Time 10:13 Sent To  
Notes
2020-08-17 10:14:23DRAWINGS (F1 AND F2) = DRAWINGS/DOCUMENTS DO NOT SHOW
 IN "ADOBE READER" AS DIGITALLY/ELECTRONICALLY SIGNED.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status N Date 2020-03-26 Cont ID  
Sent By jgomez Date 2020-03-26 Time 09:06 Rev Time 0.00
Received By jgomez Date 2020-03-23 Time 09:02 Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved