| Plan Review Stops For Permit 20031094 |
| Review Stop |
G |
GAS REVIEW |
| Rev No |
5 |
Status |
P |
Date |
2020-08-04 |
|
|
Cont ID |
|
| Sent By |
lcrespo |
Date |
2020-08-04 |
Time |
12:19 |
Rev Time |
0.00 |
| Received By |
lcrespo |
Date |
2020-08-04 |
Time |
12:19 |
Sent To |
|
|
| Notes |
| 2020-08-04 12:19:58 | 08/04/20 REVIEWED FOR CODE COMPLIANCE (GAS) | | | | | | BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE | | | COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN | | | PROFESSIONAL, CONTRACTORS OR THEIR REPRESENTATIVES FROM | | | THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, STATE AND | | | NATIONAL CODES AND STANDARDS IN EFFECT AT THE TIME OF | | | PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK OF EVERY | | | ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM | | | REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES | | | / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO | | | AVOID VOIDING OF THE PERMIT. | | | | | | LUIS A. CRESPO | | | PLUMBING INSPECTOR / PLUMBING PLAN REVIEW | | | AVAILABLE FROM 6:30 AM TO 7:30 AM / 2:00 PM TO 5:00 PM | | | EMAIL: [email protected] CELL: 561-701-6437 | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
4 |
Status |
F |
Date |
2020-06-30 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2020-06-30 |
Time |
10:51 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2020-06-29 |
Time |
11:11 |
Sent To |
|
|
| Notes |
| 2020-06-29 13:28:36 | 1) SHOW THE DISTANCE FROM THE POINT OF DELIVERY, (GAS | | | METER / MP REGULATOR / LP TANK) TO THE MOST REMOTE | | | OUTLET IN THE BUILDING AND / OR SYSTEM PER THE 2017 | | | FBC-FUEL GAS SEC.402.4.1, 402.4.2, OR 2017 FBC-RES. | | | SEC. G 2413.4.1, G2413.4.2. | | | 2) INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM | | | ON THE PLAN PER 2017 FBC-FUEL GAS SEC.402.1, 402.4.3 | | | THRU 402.6 OR 2017 FBC RES. SEC. G2413.2, G2413.4.3. | | | 3) PLACE A NOTE ON THE PLANS SPECIFYING WHICH SIZING | | | TABLE(S) FROM THE FUEL GAS CODE THAT WAS USED IN THE | | | DESIGN OF THIS GAS SYSTEM. FBC-FUEL GAS SECS. 401.4, | | | 401.8, 402.3. | | | 4) INDICATE ON THE PLAN THE TYPE OF PIPE BEING | | | INSTALLED. | | | 5) SUBMIT A COPY OF THE OPERATION AND INSTALLATION | | | MANUAL (OIM) AS REFERENCED ON THE PLANS. WPB AMEND. TO | | | FBC SEC. 107.2.1. | | | 6) SHT. D1 DOES NOT SHOW ANY EXISTING GAS PIPING. | | | SUBMIT AN EXISTING PIPING PLAN THAT SHOWS ALL EXISTING | | | GAS PIPING TO BE REMOVED. IDENTIFY ALL NEW GAS PIPING | | | TO BE INSTALLED AND ANY EXISTING GAS PIPING THAT IS TO | | | REMAIN. WPB AMEND. TO FBC SEC. 107.2.1. | | | 7) SHT. P-3 - THE PLANS SHOW AN EXISTING FAN LABELED AS | | | SF-1 (SUPPLY FAN?) TO REMAIN BUT THE PLAN SHOWS A | | | DIRECTIONAL ARROW INDICATING THIS MAY BE AN EXHAUST | | | FAN. CLARIFY. | | | 8) COMBUSTION AIR CALCULATIONS HAVE BEEN SUBMITTED FOR | | | A MECHANICAL COMBUSTION AIR SUPPLY SYSTEM BUT THERE IS | | | NO INFORMATION ON THE PLANS AS TO HOW THIS COMBUSTION | | | AIR IS BEING SUPPLIED. THE PLANS ALSO SHOW COMBUSTION | | | AIR BEING SUPPLIED BY A LOUVER, NOT BY MECHANICAL | | | MEANS. CLARIFY. | | | 9) PROVIDE DETAILS AS TO HOW THE EXHAUST PIPE | | | PENETRATIONS WILL BE SEALED? ARE ANY OF THESE WALLS | | | FIRE RATED? IF SO, SUBMIT DETAILS FOR THE LISTED | | | FIRESTOPPING SYSTEMS TO BE USED. WPB AMEND. TO FBC SEC. | | | 107.2.1. | | | 10) PROVIDE INFORMATION FOR THE TERMINATION LOCATION OF | | | THE EXHAUST VENT. THE EXIT TERMINAL OF A MECHANICAL | | | DRAFT SYSTEM ( IF INSTALLED ) SHALL COMPLY WITH | | | FBC-FUEL GAS SEC. 503.3.3, (1-6), 503.8 (1) (2). | | | 11) PROVIDE DETAILS FOR THE EXHAUST SSUPPORTS. SHOW | | | SUPPORT LOCATIONS, TYPE OF SUPPORTS, SPACING, ETC. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
3 |
Status |
F |
Date |
2020-05-28 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2020-05-28 |
Time |
08:43 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2020-05-28 |
Time |
07:18 |
Sent To |
|
|
| Notes |
| 2020-05-28 07:18:50 | 1) THESE PLANS WERE INITIALLY SUBMITTED AS DIGITAL | | | PLANS AND NOW HAVE BEEN SUBMITTED AS PAPER PLANS. THE | | | PLANS SHALL BEAR THE ORIGINAL SIGNATURE AND SEAL OF THE | | | DESIGN PROFESSIONAL OF RECORD PER THE FL. ADMIN. CODE | | | RULE 61G15-23.001. | | | 2). PRINTED COPIES OF DIGITALLY SIGNED DOCUMENTS ARE | | | NOT CONSIDERED SIGNED AND SEALED AND ALL SIGNATURES | | | MUST BE VERIFIED ON ANY ELECTRONIC COPIES PER FL. | | | ADMIN. CODE RULE 61G15-23.004 (3)(C). | | | 3) THE SUBMITTED PLANS ARE ILLEGIBLE DUE TO THE SMALL | | | SIZE AND MINUTE TYPSET. PLANS SHALL BE DRAWN AT A | | | MINIMUM 1/8 INCH SCALE. WPB AMEND. TO FBC SEC. | | | 107.2.1.3.SUBMIT LEGIBLE PLANS FOR REVIEW IN THE | | | DIGITAL FORMAT. WPB AMEND. TO FBC SEC. 107.2.1. | | | NOTE: A THOROUGH REVIEW COULD NOT BE DONE AT THIS TIME | | | DUE TO THE SUBMITTED PLANS BEING LARGELY ILLEGIBLE. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
2 |
Status |
F |
Date |
2020-05-19 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2020-05-19 |
Time |
09:28 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2020-05-19 |
Time |
09:24 |
Sent To |
|
|
| Notes |
| 2020-05-19 09:28:50 | | | | | | | 1) SUBMIT THE DRAWINGS LISTED ON EXHIBIT A: SK1.0, SK | | | 2.0, AND SK2.1. THE DRAWINGS SHALL INCLUDE: | | | | | | A) THE BOILER ROOM AND NEW BOILER LOCATIONS WITH | | | REQUIRED CLEARANCES DISTANCE MEASUREMENTS FOR SERVICE | | | ACCESS AND REPLACEMENT- SECTION 306.1 FBC FG. | | | | | | B) VENTING DIAGRAMS SHOWING THE TYPE AND SIZE OF GAS | | | VENTS, GAS VENT RUNS, AND TERMINATION LOCATIONS- | | | SECTION 503 FBC FG. | | | | | | 2) EXHIBIT A INDICATES THE COST OF THE BOILERS, | | | EXPANSION TANK, AND CIRC. PUMP ARE TO BE PROVIDED BY | | | OWNER. PLEASE NOTE THAT PERMIT VALUE IS BASED ON LABOR, | | | MATERIALS, APPLIANCE AND EQUIPMENT. PLEASE PROVIDE A | | | TOTAL VALUE THAT INCLUDES THE COST OF THE EQUIOMENT- | | | SECTION 109.3 WPB. | | | 3) INSULATION OF HOT WATER PIPING SHALL COMPLY WITH | | | FBC-PLUMBING SEC.607.5. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | | | | | | | | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
P |
Date |
2020-03-23 |
|
|
Cont ID |
|
| Sent By |
lcrespo |
Date |
2020-03-23 |
Time |
17:57 |
Rev Time |
0.00 |
| Received By |
lcrespo |
Date |
2020-03-23 |
Time |
17:57 |
Sent To |
|
|
| Notes |
| 2020-03-23 17:58:20 | 03/23/20 REVIEWED FOR CODE COMPLIANCE (GAS) | | | | | | BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE | | | COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN | | | PROFESSIONAL, CONTRACTORS OR THEIR REPRESENTATIVES FROM | | | THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, STATE AND | | | NATIONAL CODES AND STANDARDS IN EFFECT AT THE TIME OF | | | PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK OF EVERY | | | ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM | | | REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES | | | / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO | | | AVOID VOIDING OF THE PERMIT. | | | | | | LUIS A. CRESPO | | | PLUMBING INSPECTOR / PLUMBING PLAN REVIEW | | | AVAILABLE FROM 6:30 AM TO 7:30 AM / 2:00 PM TO 5:00 PM | | | EMAIL: [email protected] CELL: 561-701-6437 | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2020-08-04 |
|
|
Cont ID |
|
| Sent By |
lcrespo |
Date |
2020-08-04 |
Time |
12:20 |
Rev Time |
0.00 |
| Received By |
lcrespo |
Date |
2020-07-29 |
Time |
07:03 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2020-07-06 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2020-07-06 |
Time |
14:00 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2020-06-10 |
Time |
16:40 |
Sent To |
|
|
| Notes |
| 2020-06-12 16:41:07 | CONVERTED TO DIGITAL. | | | UPLOADED DRAWINGS TO PROJECTDOX. JG. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2020-05-29 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2020-05-29 |
Time |
08:55 |
Rev Time |
0.00 |
| Received By |
hmoser |
Date |
2020-05-28 |
Time |
08:59 |
Sent To |
|
|
| Notes |
| 2020-05-28 08:59:50 | ROUTED TO MECHANICAL BIN |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2020-05-19 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2020-05-12 |
Time |
07:53 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2020-04-30 |
Time |
14:55 |
Sent To |
|
|
| Notes |
| 2020-05-05 14:55:57 | CONVERTED TO DIGITAL. JG. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2020-03-24 |
Time |
|
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2020-03-23 |
Time |
16:01 |
Sent To |
|
|
| Notes |
| 2020-03-23 16:04:00 | ROUTED TO PLUMBING INBOX |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
6 |
Status |
P |
Date |
2020-08-03 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2020-08-03 |
Time |
14:23 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2020-08-03 |
Time |
14:17 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
5 |
Status |
F |
Date |
2020-07-06 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2020-07-06 |
Time |
09:25 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2020-07-06 |
Time |
09:25 |
Sent To |
|
|
| Notes |
| 2020-07-06 09:27:02 | PLEASE SEE 4TH REVISION COMMENTS. ALSO, PLEASE SEE THE | | | FIRE REVIEWER COMMENTS. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
4 |
Status |
F |
Date |
2020-06-15 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2020-06-15 |
Time |
11:47 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2020-06-15 |
Time |
11:00 |
Sent To |
|
|
| Notes |
| 2020-06-15 11:51:39 | REVIEW FBC-2017 MECHANICAL | | | PERMIT-20031094 | | | | | | CODES IN EFFECT: | | | | | | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 | | | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 | | | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION | | | 2017 | | | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 | | | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION | | | 2017 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH | | | EDITION 2017 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SHEET D-1 NOTE 2- REFERENCES M-1 FOR THE INTELLIHOT | | | Q751 WATER HEATERS AND THEIR PIPING. THERE IS NO M-1 | | | SHEET IN THIS SUBMISSION. PLEASE PROVIDE THIS SHEET. | | | FBC FS 107.2.1 | | | | | | 2) SHEET P3 INDICATES THE NEW EXHAUST VENTING FOR THE | | | NEW WATER HEATERS ARE BEING VENTED IN A NEW LOCATION | | | FROM THE EXISTING LOCATION. PLEASE SHOW PROPERTY LINES | | | AND DISTANCES FROM PROPERTY LINES AND OPENINGS INTO THE | | | BUILDING. FBC M 501.3.1 | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD | | | SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER | | | SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN | | | THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS | | | PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS | | | PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR | | | UPDATED. | | | | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
F |
Date |
2020-05-29 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2020-05-29 |
Time |
08:46 |
Rev Time |
0.00 |
| Received By |
hmoser |
Date |
2020-05-29 |
Time |
08:41 |
Sent To |
I |
|
| Notes |
| 2020-05-29 08:54:26 | PLAN DENIED | | | REFER TO SECTION 107.2.1.3 WEST PALM BEACH AMENDMENTS | | | 2017 QUALITY OF PLANS. BUILDING PLANS SHALL BE DRAWN TO | | | A | | | MINIMUM 1/8 INC. SCALE. | | | | | | PLAN REVIEW BY HAROLD MOSER | | | [email protected] | | | OFFICE 561-805-6732 | | | FAX 561-805-6676 | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2020-05-12 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2020-05-12 |
Time |
07:55 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2020-05-12 |
Time |
07:19 |
Sent To |
|
|
| Notes |
| 2020-05-12 07:56:59 | PLEASE SEE 1ST REVIEWERS COMMENTS. I DO NOT SEE | | | ANYTHING IN THESE SUBMITTED FILES THAT HE WAS | | | REQUESTING. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2020-03-24 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2020-03-24 |
Time |
10:41 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2020-03-24 |
Time |
10:23 |
Sent To |
I |
|
| Notes |
| 2020-05-12 07:55:19 | PLEASE SEE 1ST REVIEWERS COMMENTS. I DO NOT SEE | | | ANYTHING IN THESE SUBMITTED FILES THAT HE WAS | | | REQUESTING. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | | | 2020-03-24 11:31:09 | 1ST REVIEW FBC-2017 MECHANICAL | | | PERMIT #20031094 | | | 3/24/20 | | | | | | CODES IN EFFECT: | | | | | | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 | | | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 | | | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION | | | 2017 | | | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 | | | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION | | | 2017 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH | | | EDITION 2017 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SUBMIT THE DRAWINGS LISTED ON EXHIBIT A: SK1.0, SK | | | 2.0, AND SK2.1. THE DRAWINGS SHALL INCLUDE: | | | | | | A) THE BOILER ROOM AND NEW BOILER LOCATIONS WITH | | | REQUIRED CLEARANCES DISTANCE MEASUREMENTS FOR SERVICE | | | ACCESS AND REPLACEMENT- SECTION 306.1 FBC FG. | | | | | | B) GAS PIPING AND WATER PIPING DRAWINGS SHOWING ALL | | | REQUIRED ALTERATIONS AND NEW INSULATION INSTALLATIONS. | | | PLEASE NOTE THAT A SEPARATE PERMIT IS REQUIRED FOR GAS | | | PIPING- SECTION 107.2.1 WPB. | | | | | | C) COMBUSTION AIR CALCULATIONS AND THE MEANS OF | | | PROVIDING THE COMBUSTION AIR- SECTION 304 FBC FG. | | | | | | D) VENTING DIAGRAMS SHOWING THE TYPE AND SIZE OF GAS | | | VENTS, GAS VENT RUNS, AND TERMINATION LOCATIONS- | | | SECTION 503 FBC FG. | | | | | | 2) EXHIBIT A INDICATES THE COST OF THE BOILERS, | | | EXPANSION TANK, AND CIRC. PUMP ARE TO BE PROVIDED BY | | | OWNER. PLEASE NOTE THAT PERMIT VALUE IS BASED ON LABOR, | | | MATERIALS, APPLIANCE AND EQUIPMENT. PLEASE PROVIDE A | | | TOTAL VALUE THAT INCLUDES THE COST OF THE EQUIOMENT- | | | SECTION 109.3 WPB. | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD | | | SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER | | | SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN | | | THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS | | | PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS | | | PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR | | | UPDATED. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
P |
Date |
2020-08-04 |
|
|
Cont ID |
|
| Sent By |
lcrespo |
Date |
2020-08-04 |
Time |
12:20 |
Rev Time |
0.00 |
| Received By |
lcrespo |
Date |
2020-08-04 |
Time |
12:20 |
Sent To |
|
|
| Notes |
| 2020-08-04 12:20:46 | 08/04/20 REVIEWED FOR CODE COMPLIANCE (PLUMBING) | | | | | | BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE | | | COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN | | | PROFESSIONAL, CONTRACTORS OR THEIR REPRESENTATIVES FROM | | | THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, STATE AND | | | NATIONAL CODES AND STANDARDS IN EFFECT AT THE TIME OF | | | PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK OF EVERY | | | ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM | | | REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES | | | / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO | | | AVOID VOIDING OF THE PERMIT. | | | | | | LUIS A. CRESPO | | | PLUMBING INSPECTOR / PLUMBING PLAN REVIEW | | | AVAILABLE FROM 6:30 AM TO 7:30 AM / 2:00 PM TO 5:00 PM | | | EMAIL: [email protected] CELL: 561-701-6437 | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2020-06-30 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2020-06-30 |
Time |
10:51 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2020-06-30 |
Time |
10:51 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2020-05-19 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2020-05-19 |
Time |
09:29 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2020-05-19 |
Time |
09:29 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2020-03-23 |
|
|
Cont ID |
|
| Sent By |
lcrespo |
Date |
2020-03-23 |
Time |
17:57 |
Rev Time |
0.00 |
| Received By |
lcrespo |
Date |
2020-03-23 |
Time |
17:57 |
Sent To |
|
|
| Notes |
| 2020-03-23 17:59:00 | 03/23/20 REVIEWED FOR CODE COMPLIANCE (PLUMBING) | | | | | | BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE | | | COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN | | | PROFESSIONAL, | | | CONTRACTORS OR THEIR REPRESENTATIVES FROM THE | | | RESPONSIBILITY TO COMPLY WITH ALL LOCAL, STATE AND | | | NATIONAL CODES AND STANDARDS IN EFFECT AT THE TIME OF | | | PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK OF EVERY | | | ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM | | | REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES | | | / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO | | | AVOID VOIDING OF THE PERMIT. | | | | | | LUIS A. CRESPO | | | PLUMBING INSPECTOR / PLUMBING PLAN REVIEW | | | AVAILABLE FROM 6:30 AM TO 7:30 / 2:00 PM TO 5:00 PM | | | EMAIL: [email protected] CELL: 561-701-6437 | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
3 |
Status |
P |
Date |
2020-08-03 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2020-08-03 |
Time |
14:27 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2020-08-03 |
Time |
14:27 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
P |
Date |
2020-06-12 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2020-06-12 |
Time |
16:37 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2020-06-12 |
Time |
16:17 |
Sent To |
|
|
| Notes |
| 2020-06-12 16:39:12 | CONVERTED TO DIGITAL. | | | DRAWINGS WITH ENGINEER'S ORIGINAL SEAL/SIGNATURE IN | | | CITY'S FILE. JG | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
F |
Date |
2020-05-19 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2020-05-19 |
Time |
09:31 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2020-05-19 |
Time |
09:31 |
Sent To |
|
|
| Notes |
| 2020-05-05 14:59:13 | PLAN REVIEWERS PLEASE NOTE: | | | ENGINEER PLANS SUBMITTED HAVE A PRINTED IMAGE OF THE | | | DIGITAL SIGNATURE. THEY WERE NOT SUBMITTED | | | ELECTRONICALLY. NEED ORIGINALS. EITHER HARD COPY OR | | | SUBMIT ELECTRONICALLY. JG. |
|
|