Plan Review Details - Permit 20031094
Plan Review Stops For Permit 20031094
Review Stop G GAS REVIEW
Rev No 5 Status P Date 2020-08-04 Cont ID  
Sent By lcrespo Date 2020-08-04 Time 12:19 Rev Time 0.00
Received By lcrespo Date 2020-08-04 Time 12:19 Sent To  
Notes
2020-08-04 12:19:5808/04/20 REVIEWED FOR CODE COMPLIANCE (GAS)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS OR THEIR REPRESENTATIVES FROM
 THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, STATE AND
 NATIONAL CODES AND STANDARDS IN EFFECT AT THE TIME OF
 PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK OF EVERY
 ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING INSPECTOR / PLUMBING PLAN REVIEW
 AVAILABLE FROM 6:30 AM TO 7:30 AM / 2:00 PM TO 5:00 PM
 EMAIL: [email protected] CELL: 561-701-6437
  

Review Stop G GAS REVIEW
Rev No 4 Status F Date 2020-06-30 Cont ID  
Sent By tklarge Date 2020-06-30 Time 10:51 Rev Time 0.00
Received By tklarge Date 2020-06-29 Time 11:11 Sent To  
Notes
2020-06-29 13:28:361) SHOW THE DISTANCE FROM THE POINT OF DELIVERY, (GAS
 METER / MP REGULATOR / LP TANK) TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND / OR SYSTEM PER THE 2017
 FBC-FUEL GAS SEC.402.4.1, 402.4.2, OR 2017 FBC-RES.
 SEC. G 2413.4.1, G2413.4.2.
 2) INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM
 ON THE PLAN PER 2017 FBC-FUEL GAS SEC.402.1, 402.4.3
 THRU 402.6 OR 2017 FBC RES. SEC. G2413.2, G2413.4.3.
 3) PLACE A NOTE ON THE PLANS SPECIFYING WHICH SIZING
 TABLE(S) FROM THE FUEL GAS CODE THAT WAS USED IN THE
 DESIGN OF THIS GAS SYSTEM. FBC-FUEL GAS SECS. 401.4,
 401.8, 402.3.
 4) INDICATE ON THE PLAN THE TYPE OF PIPE BEING
 INSTALLED.
 5) SUBMIT A COPY OF THE OPERATION AND INSTALLATION
 MANUAL (OIM) AS REFERENCED ON THE PLANS. WPB AMEND. TO
 FBC SEC. 107.2.1.
 6) SHT. D1 DOES NOT SHOW ANY EXISTING GAS PIPING.
 SUBMIT AN EXISTING PIPING PLAN THAT SHOWS ALL EXISTING
 GAS PIPING TO BE REMOVED. IDENTIFY ALL NEW GAS PIPING
 TO BE INSTALLED AND ANY EXISTING GAS PIPING THAT IS TO
 REMAIN. WPB AMEND. TO FBC SEC. 107.2.1.
 7) SHT. P-3 - THE PLANS SHOW AN EXISTING FAN LABELED AS
 SF-1 (SUPPLY FAN?) TO REMAIN BUT THE PLAN SHOWS A
 DIRECTIONAL ARROW INDICATING THIS MAY BE AN EXHAUST
 FAN. CLARIFY.
 8) COMBUSTION AIR CALCULATIONS HAVE BEEN SUBMITTED FOR
 A MECHANICAL COMBUSTION AIR SUPPLY SYSTEM BUT THERE IS
 NO INFORMATION ON THE PLANS AS TO HOW THIS COMBUSTION
 AIR IS BEING SUPPLIED. THE PLANS ALSO SHOW COMBUSTION
 AIR BEING SUPPLIED BY A LOUVER, NOT BY MECHANICAL
 MEANS. CLARIFY.
 9) PROVIDE DETAILS AS TO HOW THE EXHAUST PIPE
 PENETRATIONS WILL BE SEALED? ARE ANY OF THESE WALLS
 FIRE RATED? IF SO, SUBMIT DETAILS FOR THE LISTED
 FIRESTOPPING SYSTEMS TO BE USED. WPB AMEND. TO FBC SEC.
 107.2.1.
 10) PROVIDE INFORMATION FOR THE TERMINATION LOCATION OF
 THE EXHAUST VENT. THE EXIT TERMINAL OF A MECHANICAL
 DRAFT SYSTEM ( IF INSTALLED ) SHALL COMPLY WITH
 FBC-FUEL GAS SEC. 503.3.3, (1-6), 503.8 (1) (2).
 11) PROVIDE DETAILS FOR THE EXHAUST SSUPPORTS. SHOW
 SUPPORT LOCATIONS, TYPE OF SUPPORTS, SPACING, ETC.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  

Review Stop G GAS REVIEW
Rev No 3 Status F Date 2020-05-28 Cont ID  
Sent By tklarge Date 2020-05-28 Time 08:43 Rev Time 0.00
Received By tklarge Date 2020-05-28 Time 07:18 Sent To  
Notes
2020-05-28 07:18:501) THESE PLANS WERE INITIALLY SUBMITTED AS DIGITAL
 PLANS AND NOW HAVE BEEN SUBMITTED AS PAPER PLANS. THE
 PLANS SHALL BEAR THE ORIGINAL SIGNATURE AND SEAL OF THE
 DESIGN PROFESSIONAL OF RECORD PER THE FL. ADMIN. CODE
 RULE 61G15-23.001.
 2). PRINTED COPIES OF DIGITALLY SIGNED DOCUMENTS ARE
 NOT CONSIDERED SIGNED AND SEALED AND ALL SIGNATURES
 MUST BE VERIFIED ON ANY ELECTRONIC COPIES PER FL.
 ADMIN. CODE RULE 61G15-23.004 (3)(C).
 3) THE SUBMITTED PLANS ARE ILLEGIBLE DUE TO THE SMALL
 SIZE AND MINUTE TYPSET. PLANS SHALL BE DRAWN AT A
 MINIMUM 1/8 INCH SCALE. WPB AMEND. TO FBC SEC.
 107.2.1.3.SUBMIT LEGIBLE PLANS FOR REVIEW IN THE
 DIGITAL FORMAT. WPB AMEND. TO FBC SEC. 107.2.1.
 NOTE: A THOROUGH REVIEW COULD NOT BE DONE AT THIS TIME
 DUE TO THE SUBMITTED PLANS BEING LARGELY ILLEGIBLE.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2020-05-19 Cont ID  
Sent By tklarge Date 2020-05-19 Time 09:28 Rev Time 0.00
Received By tklarge Date 2020-05-19 Time 09:24 Sent To  
Notes
2020-05-19 09:28:50 
  
 1) SUBMIT THE DRAWINGS LISTED ON EXHIBIT A: SK1.0, SK
 2.0, AND SK2.1. THE DRAWINGS SHALL INCLUDE:
  
 A) THE BOILER ROOM AND NEW BOILER LOCATIONS WITH
 REQUIRED CLEARANCES DISTANCE MEASUREMENTS FOR SERVICE
 ACCESS AND REPLACEMENT- SECTION 306.1 FBC FG.
  
 B) VENTING DIAGRAMS SHOWING THE TYPE AND SIZE OF GAS
 VENTS, GAS VENT RUNS, AND TERMINATION LOCATIONS-
 SECTION 503 FBC FG.
  
 2) EXHIBIT A INDICATES THE COST OF THE BOILERS,
 EXPANSION TANK, AND CIRC. PUMP ARE TO BE PROVIDED BY
 OWNER. PLEASE NOTE THAT PERMIT VALUE IS BASED ON LABOR,
 MATERIALS, APPLIANCE AND EQUIPMENT. PLEASE PROVIDE A
 TOTAL VALUE THAT INCLUDES THE COST OF THE EQUIOMENT-
 SECTION 109.3 WPB.
 3) INSULATION OF HOT WATER PIPING SHALL COMPLY WITH
 FBC-PLUMBING SEC.607.5.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  
  

Review Stop G GAS REVIEW
Rev No 1 Status P Date 2020-03-23 Cont ID  
Sent By lcrespo Date 2020-03-23 Time 17:57 Rev Time 0.00
Received By lcrespo Date 2020-03-23 Time 17:57 Sent To  
Notes
2020-03-23 17:58:2003/23/20 REVIEWED FOR CODE COMPLIANCE (GAS)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS OR THEIR REPRESENTATIVES FROM
 THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, STATE AND
 NATIONAL CODES AND STANDARDS IN EFFECT AT THE TIME OF
 PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK OF EVERY
 ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING INSPECTOR / PLUMBING PLAN REVIEW
 AVAILABLE FROM 6:30 AM TO 7:30 AM / 2:00 PM TO 5:00 PM
 EMAIL: [email protected] CELL: 561-701-6437
  

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2020-08-04 Cont ID  
Sent By lcrespo Date 2020-08-04 Time 12:20 Rev Time 0.00
Received By lcrespo Date 2020-07-29 Time 07:03 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2020-07-06 Cont ID  
Sent By shill Date 2020-07-06 Time 14:00 Rev Time 0.00
Received By shill Date 2020-06-10 Time 16:40 Sent To  
Notes
2020-06-12 16:41:07CONVERTED TO DIGITAL.
 UPLOADED DRAWINGS TO PROJECTDOX. JG.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2020-05-29 Cont ID  
Sent By hmoser Date 2020-05-29 Time 08:55 Rev Time 0.00
Received By hmoser Date 2020-05-28 Time 08:59 Sent To  
Notes
2020-05-28 08:59:50ROUTED TO MECHANICAL BIN

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-05-19 Cont ID  
Sent By medwards Date 2020-05-12 Time 07:53 Rev Time 0.00
Received By tklarge Date 2020-04-30 Time 14:55 Sent To  
Notes
2020-05-05 14:55:57CONVERTED TO DIGITAL. JG.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2020-03-24 Time   Rev Time 0.00
Received By lmarchan Date 2020-03-23 Time 16:01 Sent To  
Notes
2020-03-23 16:04:00ROUTED TO PLUMBING INBOX

Review Stop M MECHANICAL (A/C)
Rev No 6 Status P Date 2020-08-03 Cont ID  
Sent By medwards Date 2020-08-03 Time 14:23 Rev Time 0.00
Received By medwards Date 2020-08-03 Time 14:17 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 5 Status F Date 2020-07-06 Cont ID  
Sent By medwards Date 2020-07-06 Time 09:25 Rev Time 0.00
Received By medwards Date 2020-07-06 Time 09:25 Sent To  
Notes
2020-07-06 09:27:02PLEASE SEE 4TH REVISION COMMENTS. ALSO, PLEASE SEE THE
 FIRE REVIEWER COMMENTS.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 4 Status F Date 2020-06-15 Cont ID  
Sent By medwards Date 2020-06-15 Time 11:47 Rev Time 0.00
Received By medwards Date 2020-06-15 Time 11:00 Sent To  
Notes
2020-06-15 11:51:39REVIEW FBC-2017 MECHANICAL
 PERMIT-20031094
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET D-1 NOTE 2- REFERENCES M-1 FOR THE INTELLIHOT
 Q751 WATER HEATERS AND THEIR PIPING. THERE IS NO M-1
 SHEET IN THIS SUBMISSION. PLEASE PROVIDE THIS SHEET.
 FBC FS 107.2.1
  
 2) SHEET P3 INDICATES THE NEW EXHAUST VENTING FOR THE
 NEW WATER HEATERS ARE BEING VENTED IN A NEW LOCATION
 FROM THE EXISTING LOCATION. PLEASE SHOW PROPERTY LINES
 AND DISTANCES FROM PROPERTY LINES AND OPENINGS INTO THE
 BUILDING. FBC M 501.3.1
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2020-05-29 Cont ID  
Sent By hmoser Date 2020-05-29 Time 08:46 Rev Time 0.00
Received By hmoser Date 2020-05-29 Time 08:41 Sent To I
Notes
2020-05-29 08:54:26PLAN DENIED
 REFER TO SECTION 107.2.1.3 WEST PALM BEACH AMENDMENTS
 2017 QUALITY OF PLANS. BUILDING PLANS SHALL BE DRAWN TO
 A
 MINIMUM 1/8 INC. SCALE.
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2020-05-12 Cont ID  
Sent By medwards Date 2020-05-12 Time 07:55 Rev Time 0.00
Received By medwards Date 2020-05-12 Time 07:19 Sent To  
Notes
2020-05-12 07:56:59PLEASE SEE 1ST REVIEWERS COMMENTS. I DO NOT SEE
 ANYTHING IN THESE SUBMITTED FILES THAT HE WAS
 REQUESTING.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2020-03-24 Cont ID  
Sent By ccole Date 2020-03-24 Time 10:41 Rev Time 0.00
Received By medwards Date 2020-03-24 Time 10:23 Sent To I
Notes
2020-05-12 07:55:19PLEASE SEE 1ST REVIEWERS COMMENTS. I DO NOT SEE
 ANYTHING IN THESE SUBMITTED FILES THAT HE WAS
 REQUESTING.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  
2020-03-24 11:31:091ST REVIEW FBC-2017 MECHANICAL
 PERMIT #20031094
 3/24/20
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SUBMIT THE DRAWINGS LISTED ON EXHIBIT A: SK1.0, SK
 2.0, AND SK2.1. THE DRAWINGS SHALL INCLUDE:
  
 A) THE BOILER ROOM AND NEW BOILER LOCATIONS WITH
 REQUIRED CLEARANCES DISTANCE MEASUREMENTS FOR SERVICE
 ACCESS AND REPLACEMENT- SECTION 306.1 FBC FG.
  
 B) GAS PIPING AND WATER PIPING DRAWINGS SHOWING ALL
 REQUIRED ALTERATIONS AND NEW INSULATION INSTALLATIONS.
 PLEASE NOTE THAT A SEPARATE PERMIT IS REQUIRED FOR GAS
 PIPING- SECTION 107.2.1 WPB.
  
 C) COMBUSTION AIR CALCULATIONS AND THE MEANS OF
 PROVIDING THE COMBUSTION AIR- SECTION 304 FBC FG.
  
 D) VENTING DIAGRAMS SHOWING THE TYPE AND SIZE OF GAS
 VENTS, GAS VENT RUNS, AND TERMINATION LOCATIONS-
 SECTION 503 FBC FG.
  
 2) EXHIBIT A INDICATES THE COST OF THE BOILERS,
 EXPANSION TANK, AND CIRC. PUMP ARE TO BE PROVIDED BY
 OWNER. PLEASE NOTE THAT PERMIT VALUE IS BASED ON LABOR,
 MATERIALS, APPLIANCE AND EQUIPMENT. PLEASE PROVIDE A
 TOTAL VALUE THAT INCLUDES THE COST OF THE EQUIOMENT-
 SECTION 109.3 WPB.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 4 Status P Date 2020-08-04 Cont ID  
Sent By lcrespo Date 2020-08-04 Time 12:20 Rev Time 0.00
Received By lcrespo Date 2020-08-04 Time 12:20 Sent To  
Notes
2020-08-04 12:20:4608/04/20 REVIEWED FOR CODE COMPLIANCE (PLUMBING)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS OR THEIR REPRESENTATIVES FROM
 THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, STATE AND
 NATIONAL CODES AND STANDARDS IN EFFECT AT THE TIME OF
 PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK OF EVERY
 ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING INSPECTOR / PLUMBING PLAN REVIEW
 AVAILABLE FROM 6:30 AM TO 7:30 AM / 2:00 PM TO 5:00 PM
 EMAIL: [email protected] CELL: 561-701-6437
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2020-06-30 Cont ID  
Sent By tklarge Date 2020-06-30 Time 10:51 Rev Time 0.00
Received By tklarge Date 2020-06-30 Time 10:51 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2020-05-19 Cont ID  
Sent By tklarge Date 2020-05-19 Time 09:29 Rev Time 0.00
Received By tklarge Date 2020-05-19 Time 09:29 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2020-03-23 Cont ID  
Sent By lcrespo Date 2020-03-23 Time 17:57 Rev Time 0.00
Received By lcrespo Date 2020-03-23 Time 17:57 Sent To  
Notes
2020-03-23 17:59:0003/23/20 REVIEWED FOR CODE COMPLIANCE (PLUMBING)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL,
 CONTRACTORS OR THEIR REPRESENTATIVES FROM THE
 RESPONSIBILITY TO COMPLY WITH ALL LOCAL, STATE AND
 NATIONAL CODES AND STANDARDS IN EFFECT AT THE TIME OF
 PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK OF EVERY
 ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING INSPECTOR / PLUMBING PLAN REVIEW
 AVAILABLE FROM 6:30 AM TO 7:30 / 2:00 PM TO 5:00 PM
 EMAIL: [email protected] CELL: 561-701-6437
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2020-08-03 Cont ID  
Sent By medwards Date 2020-08-03 Time 14:27 Rev Time 0.00
Received By medwards Date 2020-08-03 Time 14:27 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2020-06-12 Cont ID  
Sent By jgomez Date 2020-06-12 Time 16:37 Rev Time 0.00
Received By jgomez Date 2020-06-12 Time 16:17 Sent To  
Notes
2020-06-12 16:39:12CONVERTED TO DIGITAL.
 DRAWINGS WITH ENGINEER'S ORIGINAL SEAL/SIGNATURE IN
 CITY'S FILE. JG
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-05-19 Cont ID  
Sent By tklarge Date 2020-05-19 Time 09:31 Rev Time 0.00
Received By tklarge Date 2020-05-19 Time 09:31 Sent To  
Notes
2020-05-05 14:59:13PLAN REVIEWERS PLEASE NOTE:
 ENGINEER PLANS SUBMITTED HAVE A PRINTED IMAGE OF THE
 DIGITAL SIGNATURE. THEY WERE NOT SUBMITTED
 ELECTRONICALLY. NEED ORIGINALS. EITHER HARD COPY OR
 SUBMIT ELECTRONICALLY. JG.