Plan Review Details - Permit 20031055
Plan Review Stops For Permit 20031055
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 3 Status P Date 2020-04-16 Cont ID  
Sent By jgomez Date 2020-04-16 Time 15:32 Rev Time 0.00
Received By jgomez Date 2020-04-16 Time 15:32 Sent To  
Notes
2020-04-16 15:33:12FROM: ILIE GASPAR
 SENT: THURSDAY, APRIL 16, 2020 8:56 AM
 TO: PERMITS
 SUBJECT: PERMIT # 20031055, ASBESTOS. 3800 WASHINGTON
 RD 810
  
 SEE ATTACHED PDF.
  
  
  
 BEST REGARDS,
  
 ILIE GASPAR
 ___________________________________
 GASPAR CONSTRUCTION AND REMODELING, LLC.
  
 LICENSE # CBC1259341
 TEL: 954.547.3389
 EMAIL: [email protected]
 WEBSITE: HTTP://WWW.ILIEGASPARLLC.COM
  
  

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status F Date 2020-04-15 Cont ID  
Sent By jgomez Date 2020-04-15 Time 08:46 Rev Time 0.00
Received By jgomez Date 2020-04-15 Time 08:46 Sent To  
Notes
2020-04-16 06:57:40FILE SENT TO [email protected] WAS A PNG FILE, NEEDS TO
 BE PDF, NOTIFIED APPLICANT VIA EMAIL 4/16
  
  
2020-04-15 08:52:45PLEASE PROVIDE:
 1) THE ADDRESS, PERMIT NUMBER AND ASBESTOS IN THE
 SUBJECT LINE.
  
 2) PLEASE CLARIFY STATEMENT ON THE ACKNOWLEDGMENT.
 STATEMENT IS TO STATE THAT " THE INSTRUCTIONS ON THE
 WEBSITE OF ASBESTOS PROGRAM COORDINATOR, FLORIDA
 DEPARTMENT OF HEALTH PALM BEACH COUNTY WILL BE FOLLOWED
 AND THAT NOTIFICATION WILL BE GIVEN TIMELY".
  
  
  
  
 ORIGINAL COMMENT:
 PLEASE PROVIDE A SIGNED ACKNOWLEDGMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY.
  
 ADDITIONAL INFORMATION REGARDING ASBESTOS REQUIREMENTS
 CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 NOTE:
 THE CONTRACTOR ACKNOWLEDGMENT TO BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN PDF
 FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE
 THE ADDRESS, PERMIT NUMBER AND ASBESTOS IN THE SUBJECT
 LINE.
  

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2020-03-30 Cont ID  
Sent By jgomez Date 2020-03-30 Time 17:05 Rev Time 0.00
Received By jgomez Date 2020-03-30 Time 16:38 Sent To  
Notes
2020-03-30 17:06:13PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY.
  
 ADDITIONAL INFORMATION REGARDING ASBESTOS REQUIREMENTS
 CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 NOTE:
 THE CONTRACTOR ACKNOWLEDGEMENT TO BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN PDF
 FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE
 THE ADDRESS, PERMIT NUMBER AND ASBESTOS IN THE SUBJECT
 LINE.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2020-06-17 Cont ID  
Sent By cthroop Date 2020-06-17 Time 08:24 Rev Time 0.00
Received By cthroop Date 2020-06-16 Time 12:16 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2020-05-12 Cont ID  
Sent By rmcphers Date 2020-05-12 Time 13:22 Rev Time 0.00
Received By rmcphers Date 2020-05-12 Time 13:18 Sent To  
Notes
2020-05-12 13:21:08REMODEL
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) FOR THE FLOORING UNDERLAYMENT, PROVIDE THE FOLLOWING
 TEST REPORTS. IT IS RECOMMENDED THAT THIS BE RESOLVED
 VIA EMAIL PRIOR TO RESUBMITTAL. EMAIL THE NAME OF THE
 UNDERLAYMENT PROPOSED TO [email protected]. IF THE
 MANUFACTURER HAS ALREADY PROVIDED THE REQUIRED TEST
 REPORTS DIRECTLY TO US, TEST REPORTS DO NOT NEED TO BE
 SUBMITTED WHEN RESUBMITTING.
  
 PLEASE NOTE THAT TEST REPORTS ARE REQUIRED -
 MANUFACTURER SPEC SHEETS ARE NOT ACCEPTABLE DUE TO
 DISCREPANCIES BETWEEN SPEC SHEETS/BROCHURES AND TEST
 REPORTS FOR SOME MANUFACTURERS (NOT NECESSARILY THE
 MANUFACTURER SELECTED; THIS IS A GENERAL COMMENT)
  
 A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR
 BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90.
 THE TEST REPORT CANNOT INCLUDE A DROPPED GYPSUM
 CEILING. PROVIDE A COPY OF THE TEST REPORT.
  
 B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN
 DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN
 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH
 ASTM E 492. THE TEST REPORT CANNOT INCLUDE A DROPPED
 GYPSUM CEILING. PROVIDE A COPY OF THE TEST REPORT.
  
 C. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE
 BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE
 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84
 OR UL 723. PROVIDE A COPY OF THE TEST REPORT.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-03-30 Cont ID  
Sent By jgomez Date 2020-03-30 Time 17:03 Rev Time 0.00
Received By jgomez Date 2020-03-30 Time 15:27 Sent To  
Notes
2020-03-30 17:04:04RESIDENTIAL (R2) BUILDING REVIEW COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 NOTE: SEC. 702.6 FBC-EXISTING BUILDING. ALL NEW WORK
 SHALL COMPLY WITH THE MATERIALS AND METHODS
 REQUIREMENTS IN THE FLORIDA BUILDING CODE.
  
 NOTE: SEC. 801.3 FBC-EXISTING BUILDING. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE.
  
 1- NEED TO PROVIDE TWO COMPLETE SET OF DRAWINGS (ONLY
 ONE PROVIDED THIS TIME) SIGNED AND SEALED BY A LICENSED
 ARCHITECT AS REQUIRED BY SEC. 107.1 CITY AMENDMENTS AND
 CHAPTER 481 F.S.
  
 2- FLOORING SOUND INSULATION MATERIAL:
  
 A) PROVIDE 2 COPIES OF THE FLAME SPREAD INDEX AND SMOKE
 DEVELOPED INDEX TEST DONE IN ACCORDANCE WITH ASTM E 84
 OR UL 723 AS REQUIRED BY SEC. 720.1 OF FBC 6TH EDITION
 (2017).
  
 B) PROVIDE 2 COPIES OF THE SOUND TRANSMISSION CLASS
 (STC) TEST DONE IN ACCORDANCE WITH ASTM E 90 AS
 REQUIRED BY SEC. 1207.2 OF FBC 6TH EDITION (2017).
  
 C) PROVIDE 2 COPIES OF THE IMPACT INSULATION CLASS
 (IIC) TEST DONE IN ACCORDANCE WITH ASTM E 492 AS
 REQUIRED BY SEC. 1207.3 OF FBC 6TH EDITION (2017).
  
 NOTE: TEST SAMPLES TO MATCH BUILDING FLOOR/CEILING
 CONSTRUCTION AND PROPOSED FLOOR FINISH. ALSO, THERE ARE
 TESTS FOR 6" OR 8" CONCRETE SLABS WITH OR WITHOUT
 ACOUSTICAL CEILING. TYPICALLY THERE ARE NOT SUSPENDED
 ACOUSTICAL CEILINGS IN THESE BUILDINGS.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. (NOTE: SUBMIT OLD DRAWINGS FOR REFERENCE). A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2020-06-17 Cont ID  
Sent By jpearson Date 2020-06-10 Time 12:21 Rev Time 0.00
Received By jpearson Date 2020-06-10 Time 11:11 Sent To  
Notes
2020-06-10 12:21:09NONE

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2020-05-06 Cont ID  
Sent By jpearson Date 2020-05-06 Time 08:46 Rev Time 0.00
Received By jpearson Date 2020-05-06 Time 08:36 Sent To  
Notes
2020-05-06 08:44:13CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW
 COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
 1.PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE
 EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE
 IS ADEQUATE. NEC 215.2, 220, 408.30; FBC RE E3602.2
 (NOT PROVIDED ON PLAN)
 2.PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED
 CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS,
 AND AFCI OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY
 WITH CODE. NEC 210.8, 210.12, 210.19, 210.20, 215.5,
 408.4; WPB FBC 107.3.5; FBC RE E3706.2, E3902 (NOT
 PROVIDED)
 3.ELECTRICAL PLAN IS REQUIRED TO BE SIGNED/SEALED BY A
 DESIGN PROFESSIONAL OR SIGNED BY THE ELECTRICAL
 CONTRACTOR QUALIFIER. PROVIDE CORRECTION. FS
 471.003(2)(H); 471.025; WPB FBC 107.1 (NOT PROVIDED,
 ALL SHEETS SUPPLIED ARE REQUIRED TO BE SIGNED. ALL
 INFORMATION SHOULD BE ON PLAN.)
 4.PLEASE COMPLETE PLAN. (UNKNOWN)
  
 NEW COMMENT:
  
 5. PROVIDE RISER DIAGRAM OF EXISTING SERVICE TO CONFIRM
 SIZE. NEC 215.5; WPB FBC 107.2.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-03-31 Cont ID  
Sent By ppetty Date 2020-03-31 Time 08:37 Rev Time 0.00
Received By ppetty Date 2020-03-31 Time 08:37 Sent To  
Notes
2020-03-31 08:48:19CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1.PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE
 EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE
 IS ADEQUATE. NEC 215.2, 220, 408.30; FBC RE E3602.2
 2.PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED
 CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS,
 AND AFCI OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY
 WITH CODE. NEC 210.8, 210.12, 210.19, 210.20, 215.5,
 408.4; WPB FBC 107.3.5; FBC RE E3706.2, E3902
 3.ELECTRICAL PLAN IS REQUIRED TO BE SIGNED/SEALED BY A
 DESIGN PROFESSIONAL OR SIGNED BY THE ELECTRICAL
 CONTRACTOR QUALIFIER. PROVIDE CORRECTION. FS
 471.003(2)(H); 471.025; WPB FBC 107.1
 4.PLEASE COMPLETE PLAN
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 PHIL PETTY
 ELECTRICAL PLANS EXAMINER
 561-805-6742
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2020-05-27 Cont ID  
Sent By pleduc Date 2020-05-27 Time   Rev Time 0.00
Received By pleduc Date 2020-05-27 Time 10:55 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2020-04-24 Cont ID  
Sent By pleduc Date 2020-04-24 Time   Rev Time 0.00
Received By pleduc Date 2020-04-24 Time 15:13 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2020-03-27 Cont ID  
Sent By pleduc Date 2020-03-27 Time   Rev Time 0.00
Received By pleduc Date 2020-03-27 Time 10:29 Sent To  
Notes
2020-03-27 10:36:49THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THERE IS ONLY ONE SET OF PLAN PROVIDED.
  
 2 SETS ARE REQUIRED.
  
 PLEASE PROVIDE THE ADDITIONAL SET
  
  
  
 2) THERE ARE INDCATIONS OF WALL/CEILING REFINISHING.
  
 THE FIRE ALARM SHALL REMAIN ACTIVE WITH ALL DEVICES
 PROTECTED FROM PAINTING.
  
 ANY REMOVAL OF FIRE ALARM DEVICES SHALL BE DONE BY A
 FIRE ALARM CONTRACTOR UNDER SEPARATE PERMIT AND SHOP
 DRAWINGS
  
 PLEASE REVIEW AND ENSURE COMPLIANCE AND PROVIDE AN
 APPLICABLE NOTE OF ACKNOWLEDGEMENT.
  
  
  
 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2020-06-25 Cont ID  
Sent By tklarge Date 2020-06-25 Time 07:25 Rev Time 0.00
Received By tklarge Date 2020-05-26 Time 14:47 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-05-12 Cont ID  
Sent By rmcphers Date 2020-05-12 Time 13:26 Rev Time 0.00
Received By rmcphers Date 2020-04-21 Time 10:45 Sent To  
Notes
2020-04-23 10:45:32CONVERTED TO DIGITAL. JG.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-03-31 Cont ID  
Sent By ppetty Date 2020-03-31 Time 08:48 Rev Time 0.00
Received By ppetty Date 2020-03-26 Time 16:38 Sent To  
Notes
2020-03-26 16:39:02B09

Review Stop P PLUMBING
Rev No 3 Status P Date 2020-06-25 Cont ID  
Sent By tklarge Date 2020-06-25 Time 07:25 Rev Time 0.00
Received By tklarge Date 2020-06-25 Time 07:13 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2020-05-07 Cont ID  
Sent By jpearson Date 2020-05-07 Time 10:26 Rev Time 0.00
Received By jpearson Date 2020-05-07 Time 09:11 Sent To  
Notes
2020-05-07 09:11:37REVIEWED BY JERRY SMITH.
  
 PROVIDE LEGIBLE PLAN FOR REVIEW. QUALITY OF BUILDING
 PLANS. BUILDING PLANS SHALL BE DRAWN TO A MINIMUM 1/8
 INCH SCALE UPON SUBSTANTIAL PAPER, CLOTH OR OTHER
 ACCEPTABLE MEDIUM. THE BUILDING OFFICIAL MAY ESTABLISH
 THROUGH DEPARTMENTAL POLICY, OTHER STANDARDS FOR PLANS
 AND SPECIFICATIONS, IN ORDER TO PROVIDE CONFORMITY TO
 ITS RECORD RETENTION PROGRAM. THIS POLICY MAY INCLUDE
 SUCH THINGS AS MINIMUM SIZE, SHAPE, CONTRAST, CLARITY,
 OR OTHER ITEMS RELATED TO RECORDS MANAGEMENT.
 ELECTRONIC MEDIA MUST BE COMPATIBLE WITH THE ARCHIVE
 REQUIREMENTS OF FLORIDA STATUTES. WPB FBC 107.2.1.3

Review Stop P PLUMBING
Rev No 1 Status F Date 2020-03-30 Cont ID  
Sent By tklarge Date 2020-03-30 Time 14:09 Rev Time 0.00
Received By tklarge Date 2020-03-30 Time 12:29 Sent To  
Notes
2020-03-30 14:09:151) SUBMIT TWO COMPLETE SETS OF PLANS FOR REVIEW. WPB
 AMEND. TO FBC SEC. 107.1.
 2) INDICATE ON THE PLANS IF THE TOILETS ARE BEING
 REPLACED. IF NOT, NOTE ON THE PLANS THAT THEY ARE
 EXISTING TO REMAIN.WPB AMEND. TO FBC SEC. 107.2.1.
 3) THE PLANS NOTE "VERIFY NEW PLUMBING PIPES FROM
 SOURCE IN A/C CLOSET TO EACH END SOURCE.IF THE UNIT IS
 BEING REPIPED, SUBMIT A WATER RISER DIAGRAM. WPB AMEND.
 TO FBC SEC. 107.3.5.1.3.
 4) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE WATER
 HEATER.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status N Date 2020-06-25 Cont ID  
Sent By dbattles Date 2020-06-25 Time 08:31 Rev Time 0.00
Received By dbattles Date 2020-06-25 Time 08:31 Sent To  
Notes
2020-06-25 08:32:58NO SEAL NEEDED. SPOKE TO CONTRACTOR ABOUT ADDING NAME
 OF DESIGNER.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2020-06-10 Cont ID  
Sent By jpearson Date 2020-06-10 Time 12:23 Rev Time 0.00
Received By jpearson Date 2020-06-10 Time 12:23 Sent To  
Notes
2020-06-10 12:23:32PER THE WPB AMENDMENTS TO THE FBC, EACH SHEET OF PLAN
 IS REQUIRED TO BE SIGNED (AND SEALED FOR
 DESIGNPROFESSIONALS) BY THE PERSON RESPONSIBLE FOR THE
 DESIGN. A DIGITAL PLAN REQUIRES A DIGITAL SIGNATURE
 WITH THE PROPER THIRD PARTY VERIFICATION. PROVIDE
 CORRECTION. ALTERNATIVELY, A SIGNED OR SIGNED/SEALED
 PAPER SET MAY BE SUPPLIED TO THE BUILDING DEPARTMENT
 WHEN ALL TRADES ARE APPROVED. WPB FBC 107.1; FS 471/481

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-04-22 Cont ID  
Sent By jgomez Date 2020-04-22 Time 17:49 Rev Time 0.00
Received By jgomez Date 2020-04-22 Time 17:49 Sent To  
Notes
2020-04-22 17:50:28CONVERTED TO DIGITAL.
 1- NEED TO PROVIDE SIGNED AND SEALED PLANS AS REQUIRED
 BY SEC. 107.1 CITY AMENDMENTS AND CHAPTER 481 F.S.
 NOTE: SINCE APPLICATION WAS CONVERTED TO DIGITAL TO
 FACILITATE REVIEWS DURING THE PANDEMIC, THEN IS
 PREFERABLY TO HAVE ARCHITECT/S DIGITAL SIGNATURE.